Security Advisory

CVE-2018-16557: SIMATIC S7-400 CPU DoS Needing Reflash

Last updated:
  • CVE-2018-16557

CVE-2018-16557 is a denial of service in Siemens SIMATIC S7-400 and S7-410 CPUs: specially crafted packets sent to port 102/tcp over Ethernet, PROFIBUS or MPI can stop the CPU, and Siemens warns that flashing a firmware image may be required to recover it. NVD scores it 7.8 (CVSS v2), Siemens 8.2 (CVSS v3.1). Configuring protection level 3 is the main mitigation where no fix exists.

Vulnerability summary

CVSS base score

7.8

High severity

EPSS score (FIRST)

0.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-16557 · Source: NVD

Affected components

ComponentCPEVersion range
Siemens SIMATIC S7-400 PN/DP V7 CPUs: CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN/DP (incl. SIPLUS 414-3 and 416-3 PN/DP)cpe:2.3:o:siemens:simatic_s7-400_pn\/dp_v7_firmware:*:*:*:*:*:*:*:*Before V7.0.3; fixed in V7.0.3 (Siemens SSA-113131). NVD's CPE carries no version limit
Siemens SIMATIC S7-400 DP V7 CPUs: CPU 412-1 DP, 412-2 DP, 414-2 DP, 414-3 DP, 416-2 DP, 416-3 DP, 416F-2 DP, 417-4 DP (incl. SIPLUS 416-3 V7 and 417-4 V7)cpe:2.3:o:siemens:simatic_s7-400_pn\/dp_v7_firmware:*:*:*:*:*:*:*:*All versions; no fix (Siemens SSA-113131 V6, 2023-05-09)
Siemens SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)cpe:2.3:o:siemens:simatic_s7-400_firmware:*:*:*:*:*:*:*:*All versions; no fix (Siemens SSA-113131). NVD's CPE: up to and including v6.0
Siemens SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants)cpe:2.3:o:siemens:simatic_s7-400h_firmware:*:*:*:*:*:*:*:*All versions; no fix (Siemens SSA-113131). NVD's CPE: up to and including v4.5
Siemens SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)cpe:2.3:o:siemens:simatic_s7-400h_firmware:*:*:*:*:*:*:*:*Before V6.0.9; fixed in V6.0.9 (Siemens SSA-113131). NVD's CPE: 6.0.0 up to but excluding 6.0.9
Siemens SIMATIC S7-410 CPU family (incl. SIPLUS variants)cpe:2.3:o:siemens:simatic_s7-410_firmware:*:*:*:*:*:*:*:*Before V8.2.1; fixed in V8.2.1 (Siemens SSA-113131, NVD before 8.2.1)

What does this mean for affected devices?

NVD carries the Siemens description: "Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU." Siemens adds: "If no access protection is configured, no privileges are required to exploit the security vulnerability." The record was published on 2018-12-13 (NVD, CVE record).

Why do the scores and CWEs differ?

NVD's Primary score is CVSS v2 7.8 (AV:N/AC:L/Au:N/C:N/I:N/A:C); NVD also lists a Secondary v3.1 7.5 with an availability impact only. Siemens, the CNA, scores CVSS v3.1 8.2 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H, temporal E:P/RL:O/RC:C), adding a low integrity impact, and classes the flaw CWE-347, improper verification of a cryptographic signature. NVD's own weakness entry is NVD-CWE-noinfo. The CWE and the reflash warning separate it from its twin CVE-2018-16556, which needs only a manual reboot.

Which S7-400 CPUs are fixed?

Siemens ProductCERT SSA-113131 covers both CVEs with the same product list; it reached version 6 on 2023-05-09, and CISA mirrors it as ICSA-18-317-02 (Update B).

CPU line (incl. SIPLUS variants) Fix (SSA-113131)
S7-400 PN/DP V7: CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN/DP V7.0.3
S7-400 H V6 V6.0.9
S7-410 V8.2.1
S7-400 DP V7: CPU 412-1 DP, 412-2 DP, 414-2 DP, 414-3 DP, 416-2 DP, 416-3 DP, 416F-2 DP, 417-4 DP no fix
S7-400 PN/DP V6 and below no fix
S7-400 H V4.5 and below no fix

NVD's CPE configuration matches every S7-400 PN/DP V7 firmware version, so a CPE-only scan flags CPUs that already run V7.0.3; check the installed version against the Siemens fix line.

How do you protect a CPU without a fix?

For this CVE Siemens names one extra countermeasure for every affected CPU: configure protection level 3 (read/write protection). Its other advice is to restrict network access to the devices and to port 102/tcp on Ethernet interfaces, and, for the S7-410, to activate Field Interface Security in PCS 7 V9.0 and use a CP 443-1 Advanced for communication with engineering and operator stations. Keep a known-good firmware image and the project at hand, since recovery may mean a reflash. Our PROFIBUS security guide and S7comm guide cover both attack paths, and the input handling fix guide covers the weakness class. Port 102 flaws on the S7-300 include CVE-2016-3949 and CVE-2018-16561.

CVE-2018-16557 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00821, the 58.2nd percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2018-12-13; NVD Primary CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; NVD Secondary CVSS v3.1 7.5 (A:H); Siemens Secondary CVSS v3.1 8.2; CWE-347 (Siemens), NVD-CWE-noinfo (NVD); CPE simatic_s7-400_firmware up to v6.0 inclusive, s7-400_pn/dp_v7_firmware all versions, s7-400h_firmware up to v4.5 inclusive and 6.0.0 to before 6.0.9, s7-410_firmware before 8.2.1. — NVD
  • Siemens SSA-113131 CSAF version 6 (2023-05-09), read 2026-11-23: DoS, flashing with a firmware image may be required to recover; no privileges needed if no access protection configured; CVSS v3.1 8.2; CWE-347; fixes V7.0.3, V6.0.9, V8.2.1; no fix for S7-400 DP V7 CPUs, PN/DP V6 and below, H V4.5 and below; mitigations: protection level 3 (read/write protection), restrict network access and port 102/tcp, S7-410 Field Interface Security in PCS 7 V9.0 with CP443-1 Adv. — Siemens ProductCERT SSA-113131
  • CISA CSAF ICSA-18-317-02, title 'Siemens S7-400 CPUs (Update B)', current 2023-05-09, read 2026-11-23: same products, scores and remediations as SSA-113131. — CISA CSAF ICSA-18-317-02
  • CVE record (checked 2026-11-23): state PUBLISHED, CNA Siemens, published 2018-12-13; CNA CVSS v3.1 8.2 with temporal E:P/RL:O/RC:C; CWE-347. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.00821, percentile 0.58226, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-113131: Denial of Service Vulnerabilities in SIMATIC S7-400 CPUs (CSAF)
  3. Siemens ProductCERT SSA-113131 (PDF)
  4. CISA CSAF: ICSA-18-317-02 Siemens S7-400 CPUs (Update B)
  5. CVE.org record CVE-2018-16557 (CNA: Siemens)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

How is CVE-2018-16557 different from CVE-2018-16556?

Both come from crafted packets to port 102/tcp on the same S7-400 CPUs. CVE-2018-16556 puts the CPU into defect mode until a manual reboot; CVE-2018-16557 may require flashing a firmware image to recover, and Siemens classes it CWE-347 rather than CWE-20.

Does protection level 3 stop the attack?

Siemens lists configuring protection level 3 (read/write protection) as a countermeasure for every affected CPU and says no privileges are needed when no access protection is configured. It does not claim the setting removes the flaw, so restrict access to port 102/tcp as well.

Which firmware fixes CVE-2018-16557?

V7.0.3 for the S7-400 PN/DP V7 CPUs, V6.0.9 for the S7-400 H V6 family and V8.2.1 for the S7-410 family. The S7-400 DP V7 CPUs, the PN/DP V6 and below family and the H V4.5 and below family get no fix (SSA-113131).

Is CVE-2018-16557 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.00821, the 58.2nd percentile, in the 2026-11-22 dataset.