CVE-2018-16556 is a denial of service in Siemens SIMATIC S7-400 and S7-410 CPUs: specially crafted packets sent to port 102/tcp over Ethernet, PROFIBUS or MPI put the CPU into defect mode, and only a manual reboot restores operation. No login or user interaction is needed. NVD scores it 7.8 (CVSS v2), Siemens 7.5 (CVSS v3.1). Fixes exist for three CPU lines; the rest get none.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
1.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-16556 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SIMATIC S7-400 PN/DP V7 CPUs: CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN/DP (incl. SIPLUS 414-3 and 416-3 PN/DP) | cpe:2.3:o:siemens:simatic_s7-400_pn\/dp_v7_firmware:*:*:*:*:*:*:*:* | Before V7.0.3; fixed in V7.0.3 (Siemens SSA-113131). NVD's CPE carries no version limit |
| Siemens SIMATIC S7-400 DP V7 CPUs: CPU 412-1 DP, 412-2 DP, 414-2 DP, 414-3 DP, 416-2 DP, 416-3 DP, 416F-2 DP, 417-4 DP (incl. SIPLUS 416-3 V7 and 417-4 V7) | cpe:2.3:o:siemens:simatic_s7-400_pn\/dp_v7_firmware:*:*:*:*:*:*:*:* | All versions; no fix (Siemens SSA-113131 V6, 2023-05-09) |
| Siemens SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-400_firmware:*:*:*:*:*:*:*:* | All versions; no fix (Siemens SSA-113131). NVD's CPE: up to and including v6.0 |
| Siemens SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-400h_firmware:*:*:*:*:*:*:*:* | All versions; no fix (Siemens SSA-113131). NVD's CPE: up to and including v4.5 |
| Siemens SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-400h_v6_firmware:*:*:*:*:*:*:*:* | Before V6.0.9; fixed in V6.0.9 (Siemens SSA-113131). NVD's CPE carries no version limit |
| Siemens SIMATIC S7-410 CPU family (incl. SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-410_firmware:*:*:*:*:*:*:*:* | Before V8.2.1; fixed in V8.2.1 (Siemens SSA-113131, NVD before 8.2.1) |
What does this mean for affected devices?
NVD carries the Siemens description: "Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation." Siemens adds that "no user interaction and no user privileges are required". NVD's Primary score is CVSS v2 7.8 (AV:N/AC:L/Au:N/C:N/I:N/A:C). Siemens, the CNA, scores it CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, temporal E:P/RL:O/RC:C), and both Siemens and NVD class it CWE-20, improper input validation. The record was published on 2018-12-13 (NVD, CVE record).
Which S7-400 CPUs are fixed?
Siemens ProductCERT SSA-113131 first appeared on 2018-11-13 and reached version 6 on 2023-05-09; CISA mirrors it as ICSA-18-317-02 (Update B). Revisions in 2022 and 2023 moved several lines to no fix and added the V7.0.3 fix for the PN/DP V7 CPUs.
| CPU line (incl. SIPLUS variants) | Fix (SSA-113131) |
|---|---|
| S7-400 PN/DP V7: CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN/DP | V7.0.3 |
| S7-400 H V6 | V6.0.9 |
| S7-410 | V8.2.1 |
| S7-400 DP V7: CPU 412-1 DP, 412-2 DP, 414-2 DP, 414-3 DP, 416-2 DP, 416-3 DP, 416F-2 DP, 417-4 DP | no fix |
| S7-400 PN/DP V6 and below | no fix |
| S7-400 H V4.5 and below | no fix |
NVD's CPE configuration is coarser than this table. It matches every S7-400 PN/DP V7 and every S7-400 H V6 firmware version, so a CPE-only scan flags CPUs that already run V7.0.3 or V6.0.9; check the installed version against the Siemens fix line instead.
How do you protect a CPU without a fix?
Siemens recommends restricting network access to the affected devices and to port 102/tcp on Ethernet interfaces. For the S7-410, it also suggests activating Field Interface Security in PCS 7 V9.0 and using a CP 443-1 Advanced for communication with the engineering and operator stations. Because the attack also runs over PROFIBUS and MPI, access to those segments matters as much as the Ethernet firewall; our PROFIBUS security guide and S7comm guide cover both paths, and the input handling fix guide covers the weakness class. The same advisory carries CVE-2018-16557, which can require a firmware reflash to recover. Similar port 102 flaws on the S7-300 are CVE-2016-3949 and CVE-2018-16561.
CVE-2018-16556 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01545, the 75.6th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2018-12-13; NVD Primary CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; Siemens Secondary CVSS v3.1 7.5; CWE-20 (Siemens and NVD, Secondary); CPE simatic_s7-400_firmware up to v6.0 inclusive, s7-400_pn/dp_v7_firmware all versions, s7-400h_firmware up to v4.5 inclusive, s7-410_firmware before 8.2.1, s7-400h_v6_firmware all versions. — NVD
- Siemens SSA-113131 CSAF version 6 (2023-05-09), read 2026-11-23: defect mode, manual reboot; no privileges, no user interaction; CVSS v3.1 7.5; fixes V7.0.3 (S7-400 PN/DP V7 CPUs incl. 412-2 PN and SIPLUS), V6.0.9 (S7-400 H V6), V8.2.1 (S7-410); no fix for S7-400 DP V7 CPUs, S7-400 PN/DP V6 and below, S7-400 H V4.5 and below; mitigations: restrict network access and port 102/tcp; S7-410: Field Interface Security in PCS 7 V9.0 with CP443-1 Adv. — Siemens ProductCERT SSA-113131
- CISA CSAF ICSA-18-317-02, title 'Siemens S7-400 CPUs (Update B)', initial 2018-11-13, current 2023-05-09, read 2026-11-23: same products, scores and remediations as SSA-113131. — CISA CSAF ICSA-18-317-02
- CVE record (checked 2026-11-23): state PUBLISHED, CNA Siemens, published 2018-12-13; CNA CVSS v3.1 7.5 with temporal E:P/RL:O/RC:C; CWE-20. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.01545, percentile 0.75645, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2018-16556?
Per Siemens SSA-113131: V7.0.3 for the S7-400 PN/DP V7 CPUs (CPU 412-2 PN, 414-3 PN/DP, 414F-3 PN/DP, 416-3 PN/DP, 416F-3 PN/DP and their SIPLUS versions), V6.0.9 for the S7-400 H V6 family and V8.2.1 for the S7-410 family.
Which S7-400 CPUs get no fix?
The S7-400 DP V7 CPUs (412-1 DP, 412-2 DP, 414-2 DP, 414-3 DP, 416-2 DP, 416-3 DP, 416F-2 DP, 417-4 DP and SIPLUS 416-3 and 417-4 V7), the S7-400 PN/DP V6 and below family and the S7-400 H V4.5 and below family. Siemens recommends restricting network access to them and to port 102/tcp.
Does the CPU recover by itself?
No. The CPU goes into defect mode and Siemens says a manual reboot is required to resume normal operation.
Is CVE-2018-16556 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.01545, the 75.6th percentile, in the 2026-11-22 dataset.
Questions about this page?