CVE-2021-33012 lets a remote, unauthenticated attacker send crafted commands to a Rockwell Automation MicroLogix 1100 PLC so that it faults every time it is switched to RUN mode, stopping the process it controls. NVD scores it 8.6. All versions are affected and there is no firmware fix; Rockwell's mitigations are RUN mode, network filtering and project backups.
Vulnerability summary
CVSS base score
8.6
High severity
EPSS score (FIRST)
2.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-33012 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation MicroLogix 1100 | cpe:2.3:o:rockwellautomation:micrologix_1100_firmware:*:*:*:*:*:*:*:* | All versions (CISA ICSA-21-189-01, NVD); no fixed firmware; recover by downloading the project, mitigate with RUN mode and port filtering; Rockwell suggests migrating to Micro870 |
What does this mean for affected devices?
The CVE record from CISA says that the Rockwell Automation MicroLogix 1100, all versions, "allows a remote, unauthenticated attacker sending specially crafted commands to cause the PLC to fault when the controller is switched to RUN mode, which results in a denial-of-service condition," and that once exploited the controller "will fault whenever the controller is switched to RUN mode." NVD's Primary score is 8.6, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H; CISA's advisory gives the same 8.6. The CISA ADP entry in the CVE record scores it 7.5 with an unchanged scope, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. CISA classifies the weakness as CWE-20 (improper input validation); NVD records it as "insufficient information". NVD published the record on 2021-07-09 and marks every MicroLogix 1100 firmware version as vulnerable (NVD, CVE record).
What is affected?
CISA's ICSA-21-189-01, released on 2021-07-08, covers all versions of the MicroLogix 1100 controller, used in the Chemical, Critical Manufacturing, Food and Agriculture and Water and Wastewater Systems sectors. Beau Taub reported the flaw. The fault persists: a controller in this state stays down each time it enters RUN mode until it is recovered.
How do you fix CVE-2021-33012?
No fixed firmware is listed. Rockwell Automation's measures, as published by CISA, are:
- recover a faulted controller by downloading a new project or an offline copy of the project to it, and keep a backup copy of the project for that purpose;
- set the controller's key switch to RUN mode to prevent remote programming, and use hardware mode switch settings where the product documentation allows, to block unauthorized changes;
- block EtherNet/IP and other CIP traffic from outside the Manufacturing Zone by restricting TCP and UDP ports 44818 and 2222 at firewalls or other security appliances;
- keep the controller off the internet, behind firewalls and isolated from business networks, with a current VPN for remote access;
- consider migrating to the Micro870 controller.
Rockwell's own advisory requires a customer login. Other MicroLogix and Logix denial-of-service flaws on this site include CVE-2021-22659 in the MicroLogix 1400 and CVE-2023-3596 in ControlLogix communication modules. Our Rockwell Logix controller guide and EtherNet/IP and CIP protocol guide cover the network controls in more depth.
Is CVE-2021-33012 exploited?
CVE-2021-33012 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.02637, the 86.29th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2021-07-09; NVD Primary CVSS v3.1 8.6 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H, CVSS v2 5.0; CISA ADP Secondary 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; NVD CWE NVD-CWE-noinfo, ICS-CERT CWE-20; CPE cpe:2.3:o:rockwellautomation:micrologix_1100_firmware (all versions) on micrologix_1100 hardware. — NVD
- CISA ICSA-21-189-01 CSAF (released 2021-07-08, read 2026-11-27): Rockwell Automation MicroLogix 1100, all versions; CVE-2021-33012 CWE-20 8.6; recover by downloading new project or offline copy; set controller switch to RUN mode; keep project backup; consider migrating to Micro870; block TCP/UDP 2222 and 44818 from outside the Manufacturing Zone; hardware mode switch; Rockwell advisory login required; sectors Chemical, Critical Manufacturing, Food and Agriculture, Water and Wastewater Systems; reported by Beau Taub. — CISA ICSA-21-189-01
- CVE record (checked 2026-11-27): PUBLISHED, CNA ICS-CERT, published 2021-07-09, no CNA CVSS; affected MicroLogix 1100 all versions; CISA-ADP CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.02637, percentile 0.86291, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which MicroLogix 1100 versions are affected by CVE-2021-33012?
All versions of the MicroLogix 1100 controller (CISA ICSA-21-189-01 and NVD).
Is there a firmware fix for CVE-2021-33012?
No fixed firmware is listed. Rockwell recommends the RUN key switch position, blocking CIP ports 44818 and 2222 from outside the Manufacturing Zone, keeping project backups and considering migration to the Micro870 controller.
How do you recover a MicroLogix 1100 hit by CVE-2021-33012?
Download a new project or an offline copy of the project to the controller. Until then, it faults each time it is switched to RUN mode.
Is CVE-2021-33012 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02637 (86.29th percentile) in the 2026-11-26 dataset.