CVE-2016-2298 is an information exposure in Meteocontrol WEB'log data loggers (Basic 100, Light, Pro, Pro Unlimited), used to monitor and manage photovoltaic and energy plants. A remote attacker can read sensitive data in cleartext, which the researcher says is the administrator password. NVD and CISA both score it 9.8. Meteocontrol released a fixed version.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
25.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2016-2298 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Meteocontrol WEB'log Basic 100, Light, Pro and Pro Unlimited | cpe:2.3:a:meteocontrol:web\'log_pro:-:*:*:*:*:*:*:* | All versions (CISA ICSA-16-133-01A); NVD CPEs carry no version; Meteocontrol released a new version that fixes the issues |
What does this mean for affected devices?
The CVE record from CISA says Meteocontrol WEB'log Basic 100, Light, Pro and Pro Unlimited allow "remote attackers to obtain sensitive cleartext information via unspecified vectors." NVD files it under CWE-200, exposure of sensitive information (NVD, CVE record). The researcher, Karn Ganeshen, wrote in his Full Disclosure post that the information is the administrator password, stored in cleartext and readable without logging in.
How severe is CVE-2016-2298?
NVD's Primary score is CVSS v3.0 9.8, CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with a CVSS v2 score of 10.0. CISA scores it the same 9.8. The high integrity and availability ratings follow from what the password unlocks: full administrative control of the logger and, through it, the plant data and connected device settings it manages.
Which WEB'log products are affected and what fixes it?
CISA's ICSA-16-133-01A, first released on 2016-05-12, lists all versions of WEB'log Basic 100, Light, Pro and Pro Unlimited. It describes them as web-based SCADA systems used mainly in Europe, with a small share in the United States, across commercial facilities, critical manufacturing, energy, and water and wastewater systems. Meteocontrol "has produced a new version that fixes the vulnerabilities" and "strongly recommends users install the WEB'log behind a firewall," adding that the logger "is not intended to be used with a direct connection to the Internet." The researcher also lists rebranded editions sold by other solar companies (Siemens WEB'log Pro, KACO Powador-proLOG, Power-One Aurora Easy Control, Mastervolt Data Control Pro).
The same advisory covers three sibling flaws: CVE-2016-2296 (improper access control, 9.4), CVE-2016-2297 (a command shell in an externally accessible directory, 9.4) and CVE-2016-4504 (cross-site request forgery, 9.4). The distributed energy resources guide covers how to secure inverter and logger communications, and the OT security guide for small manufacturers covers firewalling such devices. Other solar logger pages: CVE-2017-7920 for the ABB VSN300 and CVE-2023-33869 for the Enphase Envoy.
Is CVE-2016-2298 exploited?
CVE-2016-2298 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit targeting it. FIRST EPSS gives it 0.25087, the 98.40th percentile, in the 2026-11-26 dataset, a high value for an ICS CVE (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2016-05-14; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 10.0; CWE-200; CPEs meteocontrol web'log_basic_100, web'log_light, web'log_pro, web'log_pro_unlimited (no version). — NVD
- CISA ICSA-16-133-01A CSAF (read 2026-11-27): all versions of WEB'log Basic 100, Light, Pro, Pro Unlimited; CVE-2016-2298 CWE-200, CVSS 9.8; siblings CVE-2016-2296 (CWE-284), CVE-2016-2297 (CWE-553), CVE-2016-4504 (CSRF), each 9.4; Meteocontrol recommends installing behind a firewall, not intended for direct Internet connection, new version fixes the vulnerabilities. — CISA ICSA-16-133-01A
- CISA advisory page (read 2026-11-27 via a page fetch): original release 2016-05-12; sectors commercial facilities, critical manufacturing, energy, water and wastewater; primarily Europe with a small percentage in the US; researcher Karn Ganeshen; no known public exploits. — CISA
- Full Disclosure post by Karn Ganeshen, 2016-05-15 (read 2026-11-27): CVE-2016-2298 = administrator password stored in clear text and readable without authentication; rebranded editions Siemens WEB'log Pro (US), KACO Powador-proLOG, power-one Aurora Easy Control, Mastervolt Data Control Pro. — seclists.org
- CVE record (read 2026-11-27): CNA ICS-CERT; no CNA CVSS in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.25087, percentile 0.98395, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which WEB'log versions are affected by CVE-2016-2298?
CISA ICSA-16-133-01A lists all versions of WEB'log Basic 100, Light, Pro and Pro Unlimited at the time of the advisory. Meteocontrol released a new version that fixes the issue; the advisory gives no version number.
What should operators do besides updating?
Meteocontrol says the WEB'log is not intended for a direct internet connection and should sit behind a firewall. CISA adds isolation from the business network and VPN-only remote access.
Are rebranded loggers affected too?
The researcher reports that the same WEB'log design is sold under other names, including Siemens WEB'log Pro, KACO Powador-proLOG, Power-One Aurora Easy Control and Mastervolt Data Control Pro. Check with the brand owner for the matching update.
Is CVE-2016-2298 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.25087 (98.40th percentile) in the 2026-11-26 dataset.