CVE-2016-2308 is cleartext password storage in the American Auto-Matrix Aspect-Nexus (before 3.0.0) and Aspect-Matrix building automation front-end units: a remote attacker who can read the file holding the passwords gets valid logins. NVD and CISA both score it 8.6. The vendor's update is installed as an .aam file through the unit's web interface.
Vulnerability summary
CVSS base score
8.6
High severity
EPSS score (FIRST)
1.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2016-2308 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| American Auto-Matrix Aspect-Nexus Building Automation Front-End Solutions | cpe:2.3:a:american_auto-matrix:aspect-nexus_building_automation_front-end_solutions_application:*:*:*:*:*:*:*:* | Versions before 3.0.0 (CISA ICSA-16-273-01); NVD CPE up to and including 2.0 |
| American Auto-Matrix Aspect-Matrix Building Automation Front-End Solutions | cpe:2.3:a:american_auto-matrix:aspect-matrix_building_automation_front-end_solutions_application:-:*:*:*:*:*:*:* | All versions (CISA ICSA-16-273-01) |
What does this mean for affected devices?
The CVE description reads: "American Auto-Matrix Aspect-Nexus Building Automation Front-End Solutions application before 3.0.0 and Aspect-Matrix Building Automation Front-End Solutions application store passwords in cleartext, which allows remote attackers to obtain sensitive information by reading a file." NVD's Primary score is 8.6 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L, CVSS 2.0 7.5) and files it under NVD-CWE-Other; CISA classes it as CWE-256, plaintext storage of a password. NVD's CPE configuration covers Aspect-Nexus up to and including 2.0 and every Aspect-Matrix version (NVD, CVE record).
Why does a file read become a login?
CISA's ICSA-16-273-01, released on 2016-09-29, pairs this flaw with CVE-2016-2307 (CISA 7.5): the same front ends let a remote attacker read arbitrary files, including the configuration file, without logging in. Combined, the two flaws could let an unauthenticated attacker read the stored passwords and log in to the building automation front end. CISA gives CVE-2016-2308 the same 8.6 vector as NVD, says an attacker with low skill could exploit it remotely, and reported no known public exploits. Maxim Rupp reported both flaws.
Which Aspect products are affected?
- Aspect-Nexus Building Automation Front-End Solutions, versions before 3.0.0;
- Aspect-Matrix Building Automation Front-End Solutions, all versions.
CISA lists commercial facilities, critical manufacturing, energy and water systems among the sectors, mainly in the United States. American Auto-Matrix is a US company.
How do you fix CVE-2016-2308?
American Auto-Matrix's steps, as published by CISA (CISA CSAF):
- download the update zip file from the Dealer Toolbox under Product Support > Software Updates;
- unzip it and install the .aam file through the web interface under System Administration > System Updates;
- reboot the unit to complete the upgrade.
After the update, change every account password on the unit, since the old ones may already have been read. Keep the front end off the Internet, behind a firewall separated from the business network, and use a VPN for remote access.
The OT security guide for small manufacturers covers zoning and remote access, and the BACnet protocol security guide covers building automation networks. Related building automation pages: CVE-2019-7593 (Johnson Controls Metasys shared RSA key pair) and CVE-2017-13996 (LOYTEC LVIS-3ME path traversal).
Is CVE-2016-2308 exploited?
CVE-2016-2308 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01392, the 72.53th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2016-10-05; [email protected] Primary CVSS 3.0 8.6 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L, CVSS 2.0 7.5; NVD-CWE-Other; CPE aspect-nexus up to and including 2.0, aspect-matrix (no version). — NVD
- CISA ICSA-16-273-01 (CSAF): Aspect-Nexus <3.0.0, Aspect-Matrix all versions; CVE-2016-2307 file read 7.5; CVE-2016-2308 CWE-256 8.6; update via Dealer Toolbox zip, install .aam file through WebUI System Administration > System Updates, reboot the unit. — CISA CSAF
- CISA ICSA-16-273-01 page: release 2016-09-29; researcher Maxim Rupp; commercial facilities, critical manufacturing, energy, water and others, mainly United States; US company; remote, low skill; no known public exploits. — CISA
- CVE.org record (MITRE-era format): published 2016-10-05; same description; no CNA CVSS. — CVE.org
- CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2016-2308 not listed; checked 2026-11-27. — CISA KEV
- EPSS 0.01392, percentile 0.72530, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Aspect versions are affected by CVE-2016-2308?
Aspect-Nexus Building Automation Front-End Solutions before 3.0.0 and every version of Aspect-Matrix, per CISA ICSA-16-273-01.
How is the American Auto-Matrix update installed?
Download the zip from the Dealer Toolbox, install the .aam file through the web interface under System Administration > System Updates, then reboot the unit.
Why change passwords after patching?
The passwords were stored in cleartext and a sibling flaw, CVE-2016-2307, let attackers read files without logging in, so existing credentials may already be known.
Is CVE-2016-2308 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01392, the 72.53th percentile, in the 2026-11-26 dataset.
Questions about this page?