Security Advisory

CVE-2016-0868: MicroLogix 1100 Web Server Stack Overflow

Last updated:
  • CVE-2016-0868

CVE-2016-0868 is a stack-based buffer overflow in the built-in web server of Rockwell Automation Allen-Bradley MicroLogix 1100 PLCs running firmware 15.000 or earlier. A remote attacker with no credentials can send a crafted web request that may run code on the controller. NVD and CISA both score it 9.8. Series B is fixed in firmware 15.002.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

8.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2016-0868 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation Allen-Bradley MicroLogix 1100 controllers 1763-L16AWA, 1763-L16BBB, 1763-L16BWA, 1763-L16DWDcpe:2.3:a:rockwellautomation:1763-l16awa_series_b:15.000:*:*:*:*:*:*:*Series A and B, firmware 15.000 and earlier (CISA ICSA-16-026-02); Series B fixed in 15.002; Series A: disable the web server

What does this mean for affected devices?

The CVE record from CISA says the stack-based buffer overflow on MicroLogix 1100 devices "A through 15.000 and B before 15.002 allows remote attackers to execute arbitrary code via a crafted web request." NVD maps it to CWE-119 and CISA to CWE-121, stack-based buffer overflow (NVD, CVE record).

How severe is CVE-2016-0868?

NVD's Primary score is CVSS v3.0 9.8, CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with a CVSS v2 score of 10.0. CISA scores it the same 9.8. The web server is enabled by default, so any controller whose HTTP port is reachable is exposed without a login.

Which MicroLogix 1100 controllers are affected and what fixes it?

CISA's ICSA-16-026-02, released on 2016-01-26, lists catalog numbers 1763-L16AWA, 1763-L16BBB, 1763-L16BWA and 1763-L16DWD, Series A and B, firmware 15.000 and earlier. It credits David Atch of CyberX and says the controllers are used worldwide in chemical, critical manufacturing, food and agriculture, and water and wastewater systems. Rockwell Automation's fix depends on the hardware series:

  • Series B: update to firmware 15.002 or later.
  • Series A: no fixed firmware is named. Rockwell asks users to disable the web server, which is on by default, and to set the key switch to RUN so it cannot be re-enabled through RSLogix 500.

CISA adds its usual network advice: keep the PLC off the internet, behind a firewall and apart from the business network. The memory corruption fix guide covers the code-level class, and the Rockwell Logix controller guide covers this controller family. Other MicroLogix pages: CVE-2021-33012, a later remote fault in the same MicroLogix 1100, and CVE-2017-16740, a stack overflow in the MicroLogix 1400.

Is CVE-2016-0868 exploited?

CVE-2016-0868 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit. FIRST EPSS gives it 0.08731, the 95.90th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2016-01-28; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 10.0; CWE-119; CPEs 1763-l16awa/bbb/bwa/dwd series_a and series_b version 15.000. — NVD
  • CISA ICSA-16-026-02 CSAF (read 2026-11-27): 1763-L16AWA/BBB/BWA/DWD Series A and B <=15.000; CWE-121; CVSS 9.8; Series B update to latest firmware; Series A disable the web server (enabled by default), set key switch to RUN to prohibit re-enabling via RSLogix 500. — CISA ICSA-16-026-02
  • CISA advisory page (read 2026-11-27 via a page fetch): released 2016-01-26; Series B fixed firmware 15.002; researcher David Atch of CyberX; sectors chemical, critical manufacturing, food and agriculture, water and wastewater; worldwide; no known public exploits. — CISA
  • CVE record (read 2026-11-27): CNA ICS-CERT; no CNA CVSS in the record. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.08731, percentile 0.95895, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-16-026-02: Rockwell Automation MicroLogix 1100 PLC Overflow Vulnerability (CSAF)
  3. CISA ICSA-16-026-02 advisory page
  4. CVE.org record CVE-2016-0868
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2016-0868?

For Series B MicroLogix 1100 controllers, firmware 15.002 or later. CISA ICSA-16-026-02 names no fixed firmware for Series A.

What should Series A owners do?

Rockwell Automation asks them to disable the controller's web server, which is enabled by default, and to set the key switch to RUN so the web server cannot be re-enabled through RSLogix 500. Network isolation from the internet and business network also applies.

Which catalog numbers are affected?

1763-L16AWA, 1763-L16BBB, 1763-L16BWA and 1763-L16DWD, Series A and B, on firmware 15.000 and earlier.

Is CVE-2016-0868 in the CISA KEV catalog?