Security Advisory

CVE-2015-8214: SIMATIC CP and TIM Authentication Bypass

Last updated:
  • CVE-2015-8214

CVE-2015-8214 is an authentication bypass in Siemens SIMATIC communication processors and TIM telecontrol modules: an unauthenticated user who reaches port 102/TCP may perform administrative operations on the module when its configuration is stored on the CPU. NVD scores it 9.7 (CVSS v2). Siemens fixed the Ethernet CPs and TIM modules in 2016; the CP 342-5 and CP 443-5 PROFIBUS processors get no fix.

Vulnerability summary

CVSS base score

9.7

Critical severity

EPSS score (FIRST)

2.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2015-8214 · Source: NVD

Affected components

ComponentCPEVersion range
Siemens SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant)cpe:2.3:o:siemens:simatic_cp_343-1_firmware:*:*:*:*:advanced:*:*:*Before V3.0.44; fixed in V3.0.44 (Siemens SSA-763427). NVD's CPE ends at 3.0 inclusive
Siemens SIMATIC CP 343-1 and CP 343-1 Lean (incl. SIPLUS NET variants)cpe:2.3:o:siemens:simatic_cp_343-1_firmware:*:*:*:*:lean:*:*:*Before V3.1.1; fixed in V3.1.1 (Siemens SSA-763427). NVD has a CPE for the Lean model only, with no version limit
Siemens SIMATIC CP 443-1 and CP 443-1 Advanced (incl. SIPLUS NET variants)cpe:2.3:o:siemens:simatic_cp_443-1_firmware:*:*:*:*:*:*:*:*Before V3.2.9; fixed in V3.2.9 (Siemens SSA-763427). NVD's CPEs carry no version limit
Siemens TIM 3V-IE, TIM 3V-IE Advanced and TIM 4R-IE (incl. SIPLUS NET variants)cpe:2.3:o:siemens:simatic_tim_4r-ie_firmware:*:*:*:*:*:*:*:*Before V2.6; fixed in V2.6 (Siemens SSA-763427)
Siemens TIM 3V-IE DNP3 and TIM 4R-IE DNP3 (incl. SIPLUS NET variants)cpe:2.3:o:siemens:simatic_tim_4r-ie_firmware:*:*:*:*:dnp3:*:*:*Before V3.1; fixed in V3.1 (Siemens SSA-763427)
Siemens SIMATIC CP 342-5, CP 342-5 FO, CP 443-5 Basic and CP 443-5 Extended PROFIBUS CPs (incl. SIPLUS NET CP 342-5 and CP 443-5)—All versions; no fix (Siemens SSA-763427 V7, 2025-07-08). No NVD CPE

What does this mean for affected devices?

NVD carries the Siemens description: "The implemented access protection level enforcement of the affected communication processors (CP) could possibly allow unauthenticated users to perform administrative operations on the CPs if network access (port 102/TCP) is available and the CPs' configuration was stored on their corresponding CPUs." NVD's Primary score is CVSS v2 9.7 (AV:N/AC:L/Au:N/C:P/I:C/A:C) with CWE-264; NVD has no v3 score of its own. The CVE was assigned by MITRE and published on 2015-11-27; the CVE record lists no product or score (NVD, CVE record).

How does Siemens score it today?

Siemens ProductCERT SSA-763427 is at version 7 (2025-07-08) and classes the flaw CWE-306, missing authentication for a critical function. It scores the Ethernet CPs and TIM modules CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and the PROFIBUS CPs 8.8 (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), because for those "potential exploitation requires access to the PROFIBUS network". CISA republishes the same content as ICSA-15-335-03 (Update C).

Which modules are affected and fixed?

Product (incl. SIPLUS NET variants) Fixed version (SSA-763427)
CP 343-1 Advanced V3.0.44
CP 343-1, CP 343-1 Lean V3.1.1
CP 443-1, CP 443-1 Advanced V3.2.9
TIM 3V-IE, TIM 3V-IE Advanced, TIM 4R-IE V2.6
TIM 3V-IE DNP3, TIM 4R-IE DNP3 V3.1
CP 342-5, CP 342-5 FO, CP 443-5 Basic, CP 443-5 Extended no fix

The revision history explains the gap: fixes for the Ethernet modules arrived between January and April 2016, the PROFIBUS CPs were added to the advisory on 2021-04-13, and the 2025-07-08 revision states that they will receive no fix. NVD's CPE configuration predates that change and has no rows for the PROFIBUS CPs or the plain CP 343-1, so a CPE-only scan misses them.

What should operators do?

Update every Ethernet CP and TIM module to the version above. For the CP 342-5 and CP 443-5, Siemens gives only its general advice: protect network access to the devices and follow its operational guidelines for industrial security. In practice that means controlling who can reach port 102/TCP on these CPs and their CPUs, and who can attach to the PROFIBUS segment itself. Our PROFIBUS security guide covers that segment, the S7comm guide covers port 102/TCP, and the authentication bypass fix guide covers the weakness class. Other port 102 flaws on the same controller families are CVE-2016-3949, CVE-2018-16561 and CVE-2018-16556.

CVE-2015-8214 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.0209, the 82.1st percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2015-11-27; NVD Primary CVSS v2 9.7 AV:N/AC:L/Au:N/C:P/I:C/A:C, no v3 metric; CWE-264; CPE rows for simatic_cp_443-1 (standard, advanced), tim_4r-ie (standard, dnp3), cp_343-1 lean, cp_343-1 advanced up to 3.0 inclusive, tim_3v-ie (standard, advanced, dnp3); no rows for CP 342-5, CP 443-5 or plain CP 343-1. — NVD
  • Siemens SSA-763427 CSAF version 7 (2025-07-08), read 2026-11-23: CWE-306; CVSS v3.1 9.8 for Ethernet CPs and TIMs, 8.8 AV:A for CP 342-5, CP 342-5 FO, CP 443-5 Basic/Extended and SIPLUS NET CP 342-5/443-5 ('Potential exploitation requires access to the PROFIBUS network'); fixes CP 343-1 Advanced V3.0.44, CP 343-1/Lean V3.1.1, CP 443-1/Advanced V3.2.9, TIM 3V-IE/4R-IE V2.6, TIM DNP3 V3.1; PROFIBUS CPs no fix; revisions 2016-01-29 to 2016-04-29 fixes, 2021-04-13 PROFIBUS CPs added, 2025-07-08 no fix for them. — Siemens ProductCERT SSA-763427
  • CISA CSAF ICSA-15-335-03, title 'Siemens SIMATIC Communication Processor Vulnerability (Update C)', current release 2025-07-08, read 2026-11-23: same products, scores and remediations as SSA-763427. — CISA CSAF ICSA-15-335-03
  • CVE record (checked 2026-11-23): state PUBLISHED, assigner MITRE, published 2015-11-27; affected n/a, no CNA metric; references Siemens SSA-763427. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.0209, percentile 0.82092, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-763427: Authentication Bypass Vulnerability in SIMATIC CP and TIM Devices (CSAF)
  3. Siemens ProductCERT SSA-763427 (PDF)
  4. CISA CSAF: ICSA-15-335-03 Siemens SIMATIC Communication Processor Vulnerability (Update C)
  5. CVE.org record CVE-2015-8214
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2015-8214?

Per Siemens SSA-763427: CP 343-1 Advanced V3.0.44, CP 343-1 and CP 343-1 Lean V3.1.1, CP 443-1 and CP 443-1 Advanced V3.2.9, TIM 3V-IE, TIM 3V-IE Advanced and TIM 4R-IE V2.6, and the TIM DNP3 variants V3.1, including the SIPLUS NET versions.

Are the PROFIBUS CPs fixed?

No. The CP 342-5, CP 342-5 FO, CP 443-5 Basic and CP 443-5 Extended were added to the advisory in 2021, and the 2025-07-08 revision says they get no fix. Siemens scores them 8.8 because an attacker needs access to the PROFIBUS network.

What conditions make a module exploitable?

Siemens says an attacker needs network access to port 102/TCP, and the CP's configuration must be stored on its CPU. Then an unauthenticated user may perform administrative operations on the CP.

Is CVE-2015-8214 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.0209, the 82.1st percentile, in the 2026-11-22 dataset.