Security Advisory

CVE-2015-3974: EasyIO-30P-SF Controller Hard-Coded Password

Last updated:
  • CVE-2015-3974

CVE-2015-3974 is a hard-coded password in EasyIO-30P-SF controllers with firmware before 0.5.21 and 2.x before 2.0.5.21, a controller that NVD lists in the products of nine other vendors, including Johnson Controls and Tridium. NVD scores it 9.0 (CVSS v2). The fix is firmware build 0.5.21 or 2.0.5.21, installed through each brand's own patch process.

Vulnerability summary

CVSS base score

9

Critical severity

EPSS score (FIRST)

1.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2015-3974 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
EasyIO-30P-SF controller firmware (also in OEM-branded products)cpe:2.3:o:easyio:easyio-30p-sf_firmware:*:*:*:*:*:*:*:*Before 0.5.21 and 2.x before 2.0.5.21 (NVD CPE up to and including 0.5.20 and 2.0.5.20); fixed in builds 0.5.21 and 2.0.5.21

What does this mean for affected devices?

NVD's description reads: "EasyIO EasyIO-30P-SF controllers with firmware before 0.5.21 and 2.x before 2.0.5.21, as used in Accutrol, Bar-Tech Automation, Infocon/EasyIO, Honeywell Automation India, Johnson Controls, SyxthSENSE, Transformative Wave Technologies, Tridium Asia Pacific, and Tridium Europe products, have a hardcoded password, which makes it easier for remote attackers to obtain access via unspecified vectors." NVD's Primary score is CVSS v2 9.0 (AV:N/AC:L/Au:S/C:C/I:C/A:C) with CWE-255; NVD's CPE list matches EasyIO-30P-SF firmware up to and including 0.5.20 and 2.0.5.20. ICS-CERT assigned the record with vendor and product n/a and no CNA score; it was published on 2015-09-28 (NVD, CVE record).

Why do so many brands appear in this CVE?

NVD names nine vendors whose products use the EasyIO-30P-SF, so one firmware flaw reaches several brands at once. CISA's advisory ICSA-15-237-02 (CSAF), "EasyIO-30P-SF Hard-Coded Credential Vulnerability", maps the flaw to CWE-259, use of hard-coded password, and gives the same CVSS v2 9.0.

How do I fix CVE-2015-3974?

Install the patched firmware, build 0.5.21 or 2.0.5.21 depending on the branch. CISA says the method depends on the vendor whose product contains the controller, and that the per-vendor mitigation plans are in its supplement to ICSA-15-237-02. Owners of a Johnson Controls, Honeywell, Tridium or other branded unit should therefore get the update from that brand's support channel. Until the update is done, keep the controller off the internet, reachable only from the building management workstation, and use a VPN for remote service, in line with CISA's practices.

The hard-coded credentials fix guide covers replacing built-in passwords, and the Niagara Fox guide and Johnson Controls Metasys guide cover two of the building automation ecosystems named in the CVE. CVE-2015-7906 is a LOYTEC building automation finding from the same year.

CVE-2015-3974 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0187, a percentile of 79.9, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2015-09-28; NVD Primary CVSS v2 9.0 AV:N/AC:L/Au:S/C:C/I:C/A:C; CWE-255; CPE easyio easyio-30p-sf_firmware up to and including 0.5.20 and up to and including 2.0.5.20. — NVD
  • CISA ICSA-15-237-02 CSAF (read 2026-11-27): CVE-2015-3974 CWE-259, CVSS v2 9.0 AV:N/AC:L/Au:S/C:C/I:C/A:C; products 30P-SF controller all firmware prior to build v0.5.21 and v2.0.5.21; remediation: install latest patch, various methods depending on the vendor, mitigation plans in the Supplement to ICSA-15-237-02. — CISA ICSA-15-237-02
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA icscert; published 2015-09-28, affected n/a / n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.01869, percentile 0.79881, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-15-237-02: EasyIO-30P-SF Hard-Coded Credential Vulnerability
  3. CISA ICSA-15-237-02 CSAF (machine-readable advisory)
  4. CVE.org record CVE-2015-3974
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2015-3974?

Build 0.5.21 for the 0.x branch and 2.0.5.21 for the 2.x branch. NVD's CPE data lists 0.5.20 and 2.0.5.20 as the last affected builds.

My controller carries another brand. Is it affected?

Possibly. NVD lists Accutrol, Bar-Tech Automation, Infocon/EasyIO, Honeywell Automation India, Johnson Controls, SyxthSENSE, Transformative Wave Technologies, Tridium Asia Pacific and Tridium Europe products as using the EasyIO-30P-SF. Get the patch through that brand; CISA's supplement lists the per-vendor plans.

Can the site change the hard-coded password?

Neither NVD nor CISA describes a way to change it; the fix is the patched firmware. Until it is installed, restrict network access to the controller.

Is CVE-2015-3974 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0187 (percentile 79.9) in the 2026-11-26 dataset.