Security Advisory

CVE-2016-2310: GE MultiLink Switch Hard-Coded Password

Last updated:
  • CVE-2016-2310

CVE-2016-2310 is a hard-coded password in the web interface of GE MultiLink managed Ethernet switches (ML800, ML810, ML1200, ML1600, ML2400, ML3000, ML3100). A remote attacker who knows it can change the switch configuration without an account of their own. NVD scores it 9.8 and CISA 10.0. GE fixed it in firmware 5.5.0 and 5.5.0k.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

3.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2016-2310 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
GE MultiLink ML800, ML1200, ML1600 and ML2400 managed switchescpe:2.3:o:ge:multilink_firmware:*:*:*:*:*:*:*:*Firmware before 5.5.0 (CISA ICSA-16-154-01); NVD CPE range reads up to and including 5.5.0; fixed in 5.5.0
GE MultiLink ML810, ML3000 and ML3100 managed switchescpe:2.3:o:ge:multilink_firmware:*:*:*:*:*:*:*:*Firmware before 5.5.0k (CISA ICSA-16-154-01); NVD CPE range reads up to and including 5.5.0k; fixed in 5.5.0k

What does this mean for affected devices?

The CVE record from CISA says GE MultiLink ML800, ML1200, ML1600 and ML2400 switches with firmware before 5.5.0, and ML810, ML3000 and ML3100 switches with firmware before 5.5.0k, "have hardcoded credentials, which allows remote attackers to modify configuration settings via the web interface." NVD files it under CWE-798, use of hard-coded credentials; CISA uses the narrower CWE-259, use of a hard-coded password (NVD, CVE record).

Why does NVD score it 9.8 and CISA 10.0?

NVD's Primary score is CVSS v3.1 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with a CVSS v2 score of 10.0. CISA, which assigned the CVE, scores 10.0 with CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H. The only difference is scope: CISA treats the switch as a component whose compromise reaches the control network behind it. Either way, a switch that carries plant traffic can be reconfigured by anyone who can reach its web interface.

Which MultiLink switches are affected and what fixes it?

CISA's ICSA-16-154-01, released on 2016-06-02, names seven models and says the switches are used worldwide in critical manufacturing, energy, and water and wastewater systems. GE released firmware 5.5.0 for the ML800, ML1200, ML1600 and ML2400 and firmware 5.5.0k for the ML810, ML3000 and ML3100, and asks asset owners to install it. GE Vernova's ML800 software page lists MultiLink firmware 5.5.0 dated 2016-06-07 and a later 6.0.0 release from 2019; the ML810 and ML3000 pages list 6.0.0 and 7.0.1 (2022). Note that NVD's CPE range reads "up to and including" 5.5.0 and 5.5.0k, while CISA and GE name those versions as the fix.

Until the firmware is updated, CISA's advice applies: keep the switch management interface off the internet, behind a firewall and apart from the business network, with remote access only over an up-to-date VPN. The hard-coded credentials fix guide covers how vendors remove fixed passwords, and the OT security guide for small manufacturers covers network separation. Related GE pages: CVE-2021-27440, a hard-coded password in the GE Reason DR60 recorder, and CVE-2019-6548, hard-coded accounts in GE Communicator.

Is CVE-2016-2310 exploited?

CVE-2016-2310 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit. FIRST EPSS gives it 0.03219, the 88.98th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2016-06-09; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 10.0; CWE-798; CPE ge:multilink_firmware up to and including 5.5.0 and up to and including 5.5.0k, with ML800/810/1200/1600/2400/3000/3100 hardware. — NVD
  • CISA ICSA-16-154-01 CSAF (read 2026-11-27): ML800/ML1200/ML1600/ML2400 before 5.5.0, ML810/ML3000/ML3100 before 5.5.0k; CWE-259; CISA CVSS v3 10.0 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H; GE firmware 5.5.0 and 5.5.0k resolve it. — CISA ICSA-16-154-01
  • CISA advisory page (read 2026-11-27 via a page fetch): released 2016-06-02; sectors critical manufacturing, energy, water and wastewater; deployed worldwide; no known public exploits. — CISA
  • GE Vernova ML800 software page (read 2026-11-27): MultiLink Firmware 5.5.0 dated 2016-06-07, 6.0.0 dated 2019-06-20; ML810 and ML3000 pages list 6.0.0 and 7.0.1 (2022-07-12). — GE Vernova
  • CVE record (read 2026-11-27): CNA ICS-CERT; no CNA CVSS in the record. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.03219, percentile 0.88977, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-16-154-01: GE MultiLink Series Hard-coded Credential Vulnerability (CSAF)
  3. CISA ICSA-16-154-01 advisory page
  4. GE Vernova: ML800 software downloads
  5. CVE.org record CVE-2016-2310
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2016-2310?

Firmware 5.5.0 for the MultiLink ML800, ML1200, ML1600 and ML2400, and firmware 5.5.0k for the ML810, ML3000 and ML3100 (CISA ICSA-16-154-01). GE Vernova's download pages also list later 6.0.0 and 7.0.1 releases.

What can an attacker do with the hard-coded password?

Per the CVE record and CISA, a remote attacker can change the switch configuration through its web interface. For a switch that carries control traffic, that can mean changed ports, VLANs or management settings.

Why do NVD and CISA give different scores?

Both rate the attack as network-based with no privileges or user interaction and high impact. CISA adds a changed scope (10.0) because the switch sits in front of other control equipment; NVD keeps scope unchanged (9.8).

Is CVE-2016-2310 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.03219 (88.98th percentile) in the 2026-11-26 dataset.