Security Advisory

CVE-2015-7930: Adcon A840 Gateway Hard-Coded Credentials

Last updated:
  • CVE-2015-7930

CVE-2015-7930 is a hard-coded credential in the Adcon Telemetry A840 Telemetry Gateway Base Station that gives a remote attacker administrative access. NVD scores it 10.0 under both CVSS v3.0 and v2. Adcon Telemetry told CISA the A840 is obsolete and that no patch or update will be created, so isolation or replacement is the only remedy.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

2.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2015-7930 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Adcon Telemetry A840 Telemetry Gateway Base Station firmwarecpe:2.3:o:adcon:a840_telemetry_gateway_base_station_firmware:*:*:*:*:*:*:*:*All versions (CISA ICSA-15-349-01; NVD CPE without a version bound); obsolete product, no fix will be released

What does this mean for affected devices?

NVD's description reads: "Adcon Telemetry A840 Telemetry Gateway Base Station has hardcoded credentials, which allows remote attackers to obtain administrative access via unspecified vectors." NVD's Primary score is CVSS v3.0 10.0 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H) and CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C); NVD records the weakness as NVD-CWE-Other. ICS-CERT assigned the record with vendor and product n/a and no CNA score; it was published on 2015-12-24 (NVD, CVE record).

What does CISA's advisory add?

CISA's advisory ICSA-15-349-01 (CSAF) maps the flaw to CWE-798, use of hard-coded credentials, and also scores it CVSS v3.0 10.0, with a vector that has no availability impact (S:C/C:H/I:H/A:N). The same advisory lists three sibling findings in that chain: CVE-2015-7931, where the Java client does not authenticate the station device (CWE-287), CVE-2015-7932, sensitive information readable by sniffing the network (CWE-319), and CVE-2015-7934, disclosure of log-file path names through the Java client (CWE-200). All versions of the base station are listed as affected.

Is there a fix for the A840?

No. CISA's remediation text quotes Adcon Telemetry: the A840 "is an obsolete product and is no longer supported", and "no patches or updates will be created for this product". A fixed credential cannot be changed by the operator, so anyone who learns it can log in to every unit with administrative rights. Plan the replacement of A840 base stations, and until then keep them off the internet, behind a firewall that only admits the hosts that collect telemetry, and reach them remotely only through a VPN, as CISA recommends.

The hard-coded credentials fix guide explains what vendors do instead of shared built-in accounts, and the OT security guide for small manufacturers covers inventory and segmentation for end-of-life field devices such as this one. CVE-2015-3964 is a similar built-in password case in a solar plant data logger.

CVE-2015-7930 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0252, a percentile of 85.6, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2015-12-24; NVD Primary CVSS v3.0 10.0 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H and CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE NVD-CWE-Other; CPE adcon a840_telemetry_gateway_base_station_firmware, no version bound. — NVD
  • CISA ICSA-15-349-01 CSAF (read 2026-11-27): CVE-2015-7930 CWE-798, CVSS v3.0 10.0 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:N; product A840 Telemetry Gateway Base Station, all versions; siblings CVE-2015-7931 (CWE-287), CVE-2015-7932 (CWE-319), CVE-2015-7934 (CWE-200); remediation: Adcon Telemetry has stated the A840 is an obsolete product and is no longer supported; no patches or updates will be created. — CISA ICSA-15-349-01
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA icscert; published 2015-12-24, affected n/a / n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.02521, percentile 0.8557, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-15-349-01: Adcon Telemetry A840 Vulnerabilities
  3. CISA ICSA-15-349-01 CSAF (machine-readable advisory)
  4. CVE.org record CVE-2015-7930
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Will Adcon release a firmware fix for CVE-2015-7930?

No. Adcon Telemetry stated in CISA's advisory that the A840 is an obsolete product, no longer supported, and that no patches or updates will be created. Replacement is the long-term remedy.

Can the operator change the hard-coded credential?

Neither NVD nor CISA describes a way to change it; a hard-coded credential is by definition built into the firmware. Treat every A840 as reachable by anyone who knows the credential and limit who can connect to it.

How should an A840 be protected until it is replaced?

Keep it off the internet, put it behind a firewall that admits only the hosts that collect telemetry, separate it from business networks, and use a VPN for any remote access, as CISA recommends for control system devices.

Is CVE-2015-7930 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0252 (percentile 85.6) in the 2026-11-26 dataset.