Security Advisory

CVE-2014-0754: SchneiderWEB Modicon Module Traversal

Last updated:
  • CVE-2014-0754

CVE-2014-0754 is a directory traversal in SchneiderWEB, the web server built into many Schneider Electric Modicon PLC CPUs and Ethernet modules. A crafted HTTP request gets past the web server's basic authentication and gives an unauthenticated attacker administrative access and control over the device. NVD and CISA score it 10.0. Schneider released firmware fixes per module and listed network workarounds.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

9.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-0754 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric Modicon 140CPU65x CPU (SchneiderWEB)—Exec before 5.5 (CVE record); NVD CPEs carry no version numbers
Schneider Electric Modicon 140NOC78x and 140NOE77x Ethernet modules—140NOC78x Exec before 1.62; 140NOE77x Exec before 6.2 (CVE record)
Schneider Electric Modicon M340 BMXNOC0401, BMXNOE0100 and BMXNOE0110x Ethernet modulescpe:2.3:o:schneider-electric:modicon_m340_bmxnoe0100_firmware:-:*:*:*:*:*:*:*BMXNOC0401 before 2.05; BMXNOE0100 before 2.9; BMXNOE0110x Exec before 6.0 (CVE record)
Schneider Electric Modicon TSXETC101, TSXETY4103x and TSXETY5103x Ethernet modulescpe:2.3:o:schneider-electric:tsxety4103_firmware:-:*:*:*:*:*:*:*TSXETC101 Exec before 2.04; TSXETY4103x Exec before 5.7; TSXETY5103x Exec before 5.9 (CVE record)
Schneider Electric Modicon TSXP57x CPUs (ETYPort and Ethernet Copro)cpe:2.3:o:schneider-electric:tsxp574634m_firmware:-:*:*:*:*:*:*:*ETYPort Exec before 5.7; Ethernet Copro Exec before 5.5 (CVE record)

What does this mean for affected devices?

The CVE record describes a "directory traversal vulnerability in SchneiderWEB on Schneider Electric Modicon PLC Ethernet modules" that "allows remote attackers to visit arbitrary resources via a crafted HTTP request." It lists the fixed firmware per module: 140CPU65x Exec 5.5, 140NOC78x Exec 1.62, 140NOE77x Exec 6.2, BMXNOC0401 2.05, BMXNOE0100 2.9, BMXNOE0110x Exec 6.0, TSXETC101 Exec 2.04, TSXETY4103x Exec 5.7, TSXETY5103x Exec 5.9, TSXP57x ETYPort Exec 5.7 and TSXP57x Ethernet Copro Exec 5.5. NVD files it under CWE-22, path traversal (NVD, CVE record).

Why is a web server bug rated 10.0?

NVD's Primary score is CVSS v2 10.0, AV:N/AC:L/Au:N/C:C/I:C/A:C, identical to CISA's score in the CVE record; NVD has no CVSS v3 score for it. CISA's ICSA-14-273-01 explains the impact: the flaw "allows an attacker to bypass the basic authentication on the web server, which would allow unauthenticated administrative access and control over the device." On a PLC communication module that means the web pages used to configure and monitor the controller. CISA credits independent researcher Billy Rios and rates the attack as low skill.

Which modules are affected and what fixes it?

CISA counts twenty-two products with sixty-six part numbers across the Modicon M340, Quantum and Premium ranges, used worldwide in the communications, critical manufacturing, energy, and water and wastewater sectors. The complete part-number list and the firmware releases are in Schneider Electric's notification SEVD-2014-260-01, which CISA points to. For modules without a firmware update, Schneider recommends a deep packet inspection firewall that drops HTTP requests containing traversal sequences in the URL, disabling port 80 (HTTP) on modules where that is possible, and blocking port 80 to these devices for all but trusted hosts. Note that NVD's configuration lists 73 per-part firmware CPEs with no version numbers, so a scanner matching on NVD CPEs alone flags fixed and unfixed modules alike; check the module firmware against the versions above.

The path traversal fix guide covers how this class is fixed in embedded web servers, and the OT security guide for small manufacturers covers keeping controller web interfaces off shared networks. Related Modicon pages: CVE-2015-7937, a buffer overflow in the Modicon M340 web server, and CVE-2017-6034, Modbus command replay on Modicon controllers.

Is CVE-2014-0754 exploited?

CVE-2014-0754 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit targeting it. FIRST EPSS gives it 0.09513, the 96.18th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Path traversal. Our practical guide covers how to detect, fix, verify and disclose it: How to fix path traversal in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2014-10-03; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no CVSS v3; CWE-22; 73 vulnerable per-part firmware CPEs (e.g. modicon_m340_bmxnoe0100_firmware, tsxety4103_firmware) with version "-". — NVD
  • CISA ICSA-14-273-01 CSAF (read 2026-11-27): SchneiderWEB web HMI, 66 part numbers; CWE-22; CVSS v2 10.0; see SEVD-2014-260-01 for part numbers and firmware; DPI firewall, disable port 80, block port 80 except trusted devices. — CISA ICSA-14-273-01
  • CISA advisory page (read 2026-11-27 via a page fetch): researcher Billy Rios; 22 products with 66 part numbers; bypass of basic authentication gives unauthenticated administrative access; sectors communications, critical manufacturing, energy, water and wastewater; low skill; no known public exploits. — CISA
  • CVE.org record via the CVE Services API (read 2026-11-27): CNA ICS-CERT; CVSS v2 10.0; product "Ethernet modules for M340, Quantum and Premium PLC ranges"; fixed firmware per module in the description. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.09513, percentile 0.96182, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-14-273-01: SchneiderWEB Server Directory Traversal Vulnerability (CSAF)
  3. CISA ICSA-14-273-01 advisory page
  4. CVE.org record CVE-2014-0754
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2014-0754?

It depends on the module: 140NOE77x Exec 6.2, 140NOC78x 1.62, 140CPU65x 5.5, BMXNOC0401 2.05, BMXNOE0100 2.9, BMXNOE0110x 6.0, TSXETC101 2.04, TSXETY4103x 5.7, TSXETY5103x 5.9, TSXP57x ETYPort 5.7 and Ethernet Copro 5.5 (CVE record). Schneider's SEVD-2014-260-01 has the full list.

What if a module has no firmware update?

Schneider recommends filtering HTTP requests with traversal sequences at a deep packet inspection firewall, disabling port 80 where the module allows it, and blocking port 80 to the device for all but trusted hosts (CISA ICSA-14-273-01).

What does an attacker gain?

CISA says the traversal bypasses the web server's basic authentication and allows unauthenticated administrative access and control over the device through its web interface.

Is CVE-2014-0754 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.09513 (96.18th percentile) in the 2026-11-26 dataset.