CVE-2014-2375 is a flaw in the CSV export feature of Ecava IntegraXor SCADA Server, a SCADA server that Ecava now markets as IGX Web SCADA. A remote attacker can use it to read or write arbitrary files on the server, expose sensitive data or fill the disk. NVD scores it 9.0 and CISA 8.3. Ecava released a patch, build 4.2.4458, that fixes it and three sibling flaws.
Vulnerability summary
CVSS base score
9
Critical severity
EPSS score (FIRST)
2.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2014-2375 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Ecava IntegraXor SCADA Server (stable) | cpe:2.3:a:ecava:integraxor:*:*:*:*:*:*:*:* | 4.1.4360 and earlier (NVD: up to and including 4.1.4360; CISA ICSA-14-224-01) |
| Ecava IntegraXor SCADA Server (pre-release builds) | — | Pre-release 4.1.4392 and earlier (NVD and CISA); patch build 4.2.4458 |
What does this mean for affected devices?
The CVE record says Ecava IntegraXor SCADA Server stable builds 4.1.4360 and earlier and pre-release builds 4.1.4392 and earlier allow remote attackers "to read or write to arbitrary files, and obtain sensitive information or cause a denial of service (disk consumption), via the CSV export feature." CISA, which assigned the CVE, files it under CWE-73, external control of file name or path; NVD's entry uses the older CWE-264 (NVD, CVE record).
Why do NVD and CISA scores differ?
NVD's Primary score is CVSS v2 9.0, AV:N/AC:L/Au:N/C:P/I:P/A:C. CISA scores 8.3, AV:N/AC:M/Au:N/C:P/I:P/A:C. The only difference is access complexity: NVD rates the attack as low complexity, CISA as medium. NVD has no CVSS v3 score. Either way no login is needed. CISA's ICSA-14-224-01 says an attacker could reach logs, reports, configuration data and restricted database tables, cause a denial of service, and "write malicious files that can be leveraged to further attack a system." CISA rates it as low skill.
Which versions are affected and what fixes it?
IntegraXor SCADA Server stable builds 4.1.4360 and earlier and pre-release builds 4.1.4392 and earlier. CISA says the product is used in 38 countries, with the largest installations in the United Kingdom, United States, Australia, Poland, Canada and Estonia, in factory and process automation. Ecava produced one patch, build 4.2.4458, that addresses all four flaws in the advisory: this one, an SQL injection (CVE-2014-2376), full path disclosure through an application tag (CVE-2014-2377) and cleartext administrator credentials readable through the guest role (CVE-2014-0786). Install it, keep the SCADA server off the internet, and put a firewall and VPN in front of any remote access, as CISA recommends. Ecava's IGX Web SCADA site says the first IntegraXor version was deployed in 2003; check the current release there rather than relying on the 2014 patch alone.
The path traversal fix guide covers how to keep user input out of file paths, and the OT security guide for small manufacturers covers segmenting HMI servers. Related pages: CVE-2014-0780, a directory traversal in the InduSoft Web Studio web server, and CVE-2014-0754, a traversal in the SchneiderWEB server of Modicon modules.
Is CVE-2014-2375 exploited?
CVE-2014-2375 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit targeting it. FIRST EPSS gives it 0.02304, the 84.05th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2014-09-15; NVD Primary CVSS v2 9.0 AV:N/AC:L/Au:N/C:P/I:P/A:C; CNA (ICS-CERT) CVSS v2 8.3 AV:N/AC:M/Au:N/C:P/I:P/A:C; no CVSS v3; NVD CWE-264, CNA CWE-73; CPE ecava:integraxor up to and including 4.1.4360, pre-release CPE up to and including 4.1.4392. — NVD
- CISA ICSA-14-224-01 CSAF (read 2026-11-27): IntegraXor SCADA Server <=4.1.4360 and <=4.1.4392; CVE-2014-2375 CWE-73 CVSS v2 8.3; siblings 2376 (SQL injection), 2377, 0786; one patch (rc.msi build 4.2.4458) addresses all four. — CISA ICSA-14-224-01
- CISA advisory page (read 2026-11-27 via a page fetch): impact (logs, reports, configuration, restricted tables, DoS, write malicious files); 38 countries, largest in UK, US, Australia, Poland, Canada, Estonia; factory and process automation; low skill; no known public exploits. — CISA
- Ecava site (read 2026-11-27): product now titled "Ecava IGX Web SCADA"; first IntegraXor version deployed in 2003. — Ecava
- CVE.org record via the CVE Services API (read 2026-11-27): CNA ICS-CERT; CVSS v2 8.3 AV:N/AC:M/Au:N/C:P/I:P/A:C; CWE-73; product IntegraXor SCADA Server. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.02304, percentile 0.84047, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which IntegraXor build fixes CVE-2014-2375?
Ecava's patch build 4.2.4458, linked from CISA ICSA-14-224-01. It fixes all four flaws in that advisory: CVE-2014-2375, CVE-2014-2376, CVE-2014-2377 and CVE-2014-0786.
Does the attacker need an account?
No. Both NVD and CISA score it with no authentication required (Au:N). The attack goes through the CSV export feature over the network.
Why is it 9.0 on NVD and 8.3 at CISA?
NVD rates access complexity as low (AC:L), CISA as medium (AC:M). The impact ratings are the same: partial confidentiality and integrity, complete availability.
Is CVE-2014-2375 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02304 (84.05th percentile) in the 2026-11-26 dataset.
Questions about this page?