CVE-2014-0750 is a path traversal in gefebt.exe, part of the WebView web components of GE Proficy HMI/SCADA CIMPLICITY 4.01 to 8.2. A crafted HTTP request can upload and run code on the server without logging in. NVD and CISA score it CVSS v2 7.5, and its FIRST EPSS score of 0.698 is very high. GE's fix is to remove web-reachable copies of gefebt.exe.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
69.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2014-0750 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| GE Intelligent Platforms Proficy HMI/SCADA CIMPLICITY | cpe:2.3:a:ge:intelligent_platforms_proficy_hmi\/scada_cimplicity:8.2:*:*:*:*:*:*:* | CIMPLICITY 4.01 to 8.2 (CISA ICSA-14-023-01); NVD CPEs 4.01, 7.5, 8.0, 8.1, 8.2 and up to 8.2 SIM 24; fix: delete or move web-reachable copies of gefebt.exe (GE GEIP13-05) |
| GE Proficy Process Systems with CIMPLICITY | cpe:2.3:a:ge:intelligent_platforms_proficy_process_systems_with_cimplicity:-:*:*:*:*:*:*:* | All versions (CISA ICSA-14-023-01) |
What does this mean for affected devices?
NVD's description reads: "Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622." NVD's Primary score is CVSS v2 7.5 (AV:N/AC:L/Au:N/C:P/I:P/A:P) with CWE-22, and CISA's ICS team, the CNA, gives the same score. NVD's CPEs cover CIMPLICITY 4.01, 7.5, 8.0, 8.1 and 8.2 up to SIM 24, while the CNA record lists 4.01 up to 8.2 (NVD, CVE record).
Which CIMPLICITY installations are affected?
CISA advisory ICSA-14-023-01 (CSAF), released on 2014-01-23 and last revised on 2018-09-06, lists CIMPLICITY 4.01 to 8.2 and Proficy Process Systems with CIMPLICITY. It also covers CVE-2014-0751, a CimWebServer path traversal scored 6.8. The researchers ZombiE and amisto0x07 reported both through the Zero Day Initiative; ZDI-14-015, published on 2014-02-13, says the gefebt.exe flaw lets an unauthenticated attacker upload and run a file on the server. CISA reported no known public exploits at release.
How do I fix CVE-2014-0750?
GE's advisory GEIP13-05, quoted by CISA, says: "All copies of the gefebt.exe files that are accessible from a Web client must be deleted or moved, so they are inaccessible." CIMPLICITY 8.2 SIM 24 (GEIP13-06) fixes the companion flaw CVE-2014-0751, and NVD counts 8.2 SIM 24 as still affected by this one, so the file removal is needed even on a patched node. Also:
- search every CIMPLICITY server, including WebView document folders, for gefebt.exe and remove the web-reachable copies;
- block HTTP to CIMPLICITY servers from outside the control network and leave WebView off where it is not used;
- move nodes on CIMPLICITY 8.2 or older to a supported release.
Earlier web server flaws in the same product are CVE-2013-0654 and CVE-2013-2785. The GE Proficy, CIMPLICITY and Historian guide ranks this as the GE CVE with the highest EPSS score, and the path traversal fix guide explains the class.
Is CVE-2014-0750 exploited?
CVE-2014-0750 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.698, the 99.55th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS). A score this high means FIRST's model estimates a high chance of exploitation activity, so treat any internet-facing CIMPLICITY web server as urgent even without a KEV entry; the KEV and EPSS prioritization guide explains how to weigh the two.


Evidence
- NVD (read 2026-11-28): status Modified; published 2014-01-25; NVD Primary CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; ICS-CERT Secondary 7.5 same vector; CWE-22; CPE CIMPLICITY up to (including) 8.2 sim24, 4.01, 7.5, 8.0, 8.1, 8.2, Proficy Process Systems with CIMPLICITY. — NVD
- CISA ICSA-14-023-01 (released 2014-01-23, revised 2018-09-06, read 2026-11-28): CIMPLICITY 4.01 to 8.2, Proficy Process Systems with CIMPLICITY; CVE-2014-0750 CWE-22 CVSS v2 7.5; CVE-2014-0751 6.8; reported by Amisto0x07 and Z0mb1E of ZDI; no known public exploits; GEIP13-05: delete or move web-accessible gefebt.exe; GEIP13-06: CIMPLICITY 8.2 SIM 24. — CISA ICSA-14-023-01
- ZDI-14-015 (ZDI-CAN-1622, read 2026-11-28): CVE-2014-0750, gefebt.exe insufficient parameter validation on an HTTP request allows upload and execution of an arbitrary file, no authentication required; reported 2013-02-22, published 2014-02-13; credit ZombiE and amisto0x07. — Zero Day Initiative
- CVE record (read 2026-11-28): state PUBLISHED, assigner icscert, published 2014-01-25; affected Proficy HMI/SCADA - CIMPLICITY 4.01 less than 8.2, Proficy Process Systems with CIMPLICITY all versions; CNA CVSS v2 7.5; CWE-22. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.698, percentile 0.99547, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Does CIMPLICITY 8.2 SIM 24 fix CVE-2014-0750?
Not on its own. SIM 24 addresses the companion flaw CVE-2014-0751, and NVD lists CIMPLICITY through 8.2 SIM 24 as affected by CVE-2014-0750. GE's fix for this flaw, per CISA ICSA-14-023-01, is to delete or move every copy of gefebt.exe that a web client can reach.
Why is the EPSS score so high?
FIRST EPSS rates CVE-2014-0750 at 0.698, the 99.55th percentile, in the 2026-11-27 dataset. EPSS estimates the probability of exploitation activity in the next 30 days, which is high for an old, unauthenticated, network-reachable flaw.
Do attackers need credentials?
No. NVD, CISA and ZDI all describe a remote attack with no authentication, using a crafted HTTP request to the WebView components.
Is CVE-2014-0750 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries).