Security Advisory

CVE-2014-0755: RSLogix 5000 Project Password Weakness

Last updated:
  • CVE-2014-0755

CVE-2014-0755 is a weakness in how Rockwell Automation RSLogix 5000 V7 through V20.01 and V21.0 protects passwords in project (.ACD) files. Someone with a copy of a project can recover the passwords that guard protected routines and read or change that logic. NVD scores it CVSS v2 6.9 and CISA 6.3. RSLogix 5000 V20.03 and V21.03 fix it.

Vulnerability summary

CVSS base score

6.9

Medium severity

EPSS score (FIRST)

0.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2014-0755 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation RSLogix 5000 design and configuration softwarecpe:2.3:a:rockwellautomation:rslogix_5000_design_and_configuration_software:21.0:*:*:*:*:*:*:*V7 through V20.01 and V21.0 (CISA ICSA-14-021-01); fixed in V20.03 and V21.03; resave and redownload protected projects

What does this mean for affected devices?

NVD says RSLogix 5000 7 through 20.01, and 21.0, "does not properly implement password protection for .ACD files (aka project files), which allows local users to obtain sensitive information or modify data via unspecified vectors." CISA classifies it as CWE-522, insufficiently protected credentials; NVD maps it to CWE-255. The record was assigned by ICS-CERT and published on 2014-02-05 (NVD, CVE record).

How severe is CVE-2014-0755?

NVD's Primary score is CVSS v2 6.9, AV:L/AC:M/Au:N/C:C/I:C/A:C. The CNA score from ICS-CERT is 6.3, AV:L/AC:M/Au:N/C:C/I:C/A:N; the two differ only on availability. CISA's ICSA-14-021-01, released on 2014-01-21, says exploitation could expose user-created content but would not directly disrupt controller operations, that it is not remotely exploitable, needs local access to the project file and user interaction, and that no public exploit was known. The real risk is to intellectual property and to protected logic that someone could change and download to a Logix controller.

Which RSLogix 5000 versions are affected and what fixes it?

Project files created with RSLogix 5000 V7 through V20.01 and V21.0 that contain password-protected content. CISA credits independent researcher Stephen Dunlap and lists use in chemical, critical manufacturing, food and agriculture, and water and wastewater. The advisory CSAF records that V20.03 and V21.03 include mitigations that strengthen password protection. CISA's advisory adds the steps that matter after upgrading: open, resave and redownload projects created in earlier versions; track who creates and receives protected files; archive and transmit them securely, encrypted where possible; restrict physical and network access to controllers holding protected content; and use unique, complex, regularly changed passwords for each protected routine. The Rockwell Logix controller guide covers this controller family, and the OT security guide for small manufacturers covers engineering-file handling. Related Logix pages: CVE-2022-1161 (hidden code change) and CVE-2021-22681 (Logix controller key bypass).

Is CVE-2014-0755 exploited?

CVE-2014-0755 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00563, the 40.53rd percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2014-02-05; NVD Primary CVSS v2 6.9 AV:L/AC:M/Au:N/C:C/I:C/A:C; ICS-CERT Secondary 6.3 AV:L/AC:M/Au:N/C:C/I:C/A:N; CWE-255 (NVD), CWE-522 (ICS-CERT); CPEs rslogix_5000_design_and_configuration_software 7.0, 18.0, 20.01, 21.0 with logix_5000_controller. — NVD
  • CISA ICSA-14-021-01 CSAF (read 2026-11-27): RSLogix 5000 >=V7 <=V20.01 and V21.0; CWE-522; CVSS v2 6.3; V20.03 and V21.03 released with mitigations that enhance password protection. — CISA ICSA-14-021-01
  • CISA advisory page (read 2026-11-27 via a page fetch): released January 21, 2014; Stephen Dunlap; unauthorized disclosure of user-created content, no direct disruption of controller operations; chemical, critical manufacturing, food and agriculture, water and wastewater; not remotely exploitable, local access and user interaction; no known public exploits; resave/redownload, track, archive, encrypt, restrict access, unique complex passwords changed periodically. — CISA
  • CVE record (read 2026-11-27): CNA ICS-CERT; title Rockwell RSLogix 5000 Insufficiently Protected Credentials; CNA CVSS v2 6.3. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.00563, percentile 0.40533, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-14-021-01: Rockwell RSLogix 5000 Password Vulnerability (CSAF)
  3. CISA ICSA-14-021-01 advisory page
  4. CVE.org record CVE-2014-0755 (CVE Services JSON, CNA: ICS-CERT)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which RSLogix 5000 versions fix CVE-2014-0755?

V20.03 and V21.03. CISA ICSA-14-021-01 says these releases include mitigations that strengthen password protection for project files.

Is upgrading RSLogix 5000 enough?

No. Projects saved with earlier versions keep the weak protection, so CISA advises opening, resaving and redownloading them with the fixed version, and changing the passwords on protected routines.

Can CVE-2014-0755 be exploited over the network?

Not directly. CISA says it needs local access to the .ACD project file and user interaction. Anyone who obtains a copy of the project, for example from a shared drive or email, is in a position to exploit it.

Is CVE-2014-0755 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00563 (40.53rd percentile) in the 2026-11-26 dataset.