CVE-2014-0755 is a weakness in how Rockwell Automation RSLogix 5000 V7 through V20.01 and V21.0 protects passwords in project (.ACD) files. Someone with a copy of a project can recover the passwords that guard protected routines and read or change that logic. NVD scores it CVSS v2 6.9 and CISA 6.3. RSLogix 5000 V20.03 and V21.03 fix it.
Vulnerability summary
CVSS base score
6.9
Medium severity
EPSS score (FIRST)
0.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2014-0755 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation RSLogix 5000 design and configuration software | cpe:2.3:a:rockwellautomation:rslogix_5000_design_and_configuration_software:21.0:*:*:*:*:*:*:* | V7 through V20.01 and V21.0 (CISA ICSA-14-021-01); fixed in V20.03 and V21.03; resave and redownload protected projects |
What does this mean for affected devices?
NVD says RSLogix 5000 7 through 20.01, and 21.0, "does not properly implement password protection for .ACD files (aka project files), which allows local users to obtain sensitive information or modify data via unspecified vectors." CISA classifies it as CWE-522, insufficiently protected credentials; NVD maps it to CWE-255. The record was assigned by ICS-CERT and published on 2014-02-05 (NVD, CVE record).
How severe is CVE-2014-0755?
NVD's Primary score is CVSS v2 6.9, AV:L/AC:M/Au:N/C:C/I:C/A:C. The CNA score from ICS-CERT is 6.3, AV:L/AC:M/Au:N/C:C/I:C/A:N; the two differ only on availability. CISA's ICSA-14-021-01, released on 2014-01-21, says exploitation could expose user-created content but would not directly disrupt controller operations, that it is not remotely exploitable, needs local access to the project file and user interaction, and that no public exploit was known. The real risk is to intellectual property and to protected logic that someone could change and download to a Logix controller.
Which RSLogix 5000 versions are affected and what fixes it?
Project files created with RSLogix 5000 V7 through V20.01 and V21.0 that contain password-protected content. CISA credits independent researcher Stephen Dunlap and lists use in chemical, critical manufacturing, food and agriculture, and water and wastewater. The advisory CSAF records that V20.03 and V21.03 include mitigations that strengthen password protection. CISA's advisory adds the steps that matter after upgrading: open, resave and redownload projects created in earlier versions; track who creates and receives protected files; archive and transmit them securely, encrypted where possible; restrict physical and network access to controllers holding protected content; and use unique, complex, regularly changed passwords for each protected routine. The Rockwell Logix controller guide covers this controller family, and the OT security guide for small manufacturers covers engineering-file handling. Related Logix pages: CVE-2022-1161 (hidden code change) and CVE-2021-22681 (Logix controller key bypass).
Is CVE-2014-0755 exploited?
CVE-2014-0755 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00563, the 40.53rd percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2014-02-05; NVD Primary CVSS v2 6.9 AV:L/AC:M/Au:N/C:C/I:C/A:C; ICS-CERT Secondary 6.3 AV:L/AC:M/Au:N/C:C/I:C/A:N; CWE-255 (NVD), CWE-522 (ICS-CERT); CPEs rslogix_5000_design_and_configuration_software 7.0, 18.0, 20.01, 21.0 with logix_5000_controller. — NVD
- CISA ICSA-14-021-01 CSAF (read 2026-11-27): RSLogix 5000 >=V7 <=V20.01 and V21.0; CWE-522; CVSS v2 6.3; V20.03 and V21.03 released with mitigations that enhance password protection. — CISA ICSA-14-021-01
- CISA advisory page (read 2026-11-27 via a page fetch): released January 21, 2014; Stephen Dunlap; unauthorized disclosure of user-created content, no direct disruption of controller operations; chemical, critical manufacturing, food and agriculture, water and wastewater; not remotely exploitable, local access and user interaction; no known public exploits; resave/redownload, track, archive, encrypt, restrict access, unique complex passwords changed periodically. — CISA
- CVE record (read 2026-11-27): CNA ICS-CERT; title Rockwell RSLogix 5000 Insufficiently Protected Credentials; CNA CVSS v2 6.3. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.00563, percentile 0.40533, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which RSLogix 5000 versions fix CVE-2014-0755?
V20.03 and V21.03. CISA ICSA-14-021-01 says these releases include mitigations that strengthen password protection for project files.
Is upgrading RSLogix 5000 enough?
No. Projects saved with earlier versions keep the weak protection, so CISA advises opening, resaving and redownloading them with the fixed version, and changing the passwords on protected routines.
Can CVE-2014-0755 be exploited over the network?
Not directly. CISA says it needs local access to the .ACD project file and user interaction. Anyone who obtains a copy of the project, for example from a shared drive or email, is in a position to exploit it.
Is CVE-2014-0755 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00563 (40.53rd percentile) in the 2026-11-26 dataset.
Questions about this page?