CVE-2012-0238 is a stack-based buffer overflow in the opcImg.asp page of Advantech/BroadWin WebAccess, a web-based HMI and SCADA package, in versions before 7.0. A remote attacker can use it to run code on the WebAccess server. NVD scores it 10.0 (CVSS v2). Advantech fixed it, with 17 related flaws, in WebAccess 7.0.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
4.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2012-0238 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Advantech/BroadWin WebAccess | cpe:2.3:a:advantech:advantech_webaccess:*:*:*:*:*:*:*:* | NVD: up to and including 6.0 (plus 5.0 entry); CISA ICSA-12-047-01A: versions before 7.0; fixed in WebAccess 7.0 |
What does this mean for affected devices?
NVD's description reads: "Stack-based buffer overflow in opcImg.asp in Advantech/BroadWin WebAccess before 7.0 allows remote attackers to execute arbitrary code via unspecified vectors." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119; there is no NVD v3 score. NVD's CPE data marks WebAccess up to and including 6.0 as vulnerable. CERT/CC assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-02-21 (NVD, CVE record).
What does CISA say?
CISA's advisory 12-047-01A (CSAF), "Advantech WebAccess Vulnerabilities", covers 18 CVEs in BroadWin WebAccess before 7.0 and scores CVE-2012-0238 CVSS v2 10.0 with CWE-119. Six siblings carry the same 10.0 score: CVE-2012-0240 (authentication, CWE-287), CVE-2011-4524, CVE-2011-4526 and CVE-2012-0243 (buffer overflows), CVE-2011-4525 (access control) and CVE-2012-0242 (format string, CWE-134). The rest are SQL injection, cross-site scripting, cross-site request forgery and information disclosure flaws scored 4.3 to 7.5. WebAccess runs the HMI as web pages served to operator browsers, so the server is often reachable from many workstations.
How do I fix it?
Advantech released WebAccess 7.0, which addresses all the listed vulnerabilities. Advantech recommends installing the new version over the existing installation; if the old version is uninstalled first, the computer must be rebooted before WebAccess is reinstalled. Advantech also points customers to the security considerations in the WebAccess installation manual. Any later WebAccess release also contains the fix. Keep the WebAccess server off the internet, behind a firewall that admits only operator workstations, and use a VPN for remote access.
Later WebAccess flaws include CVE-2016-0859, a kernel integer overflow. The memory corruption guide explains stack overflows, and the Advantech industrial networking and SCADA guide groups the vendor's advisories.
CVE-2012-0238 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0412, a percentile of 91.6, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2012-02-21; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPE advantech_webaccess up to and including 6.0 plus 5.0. — NVD
- CISA ICSA-12-047-01A CSAF (read 2026-11-28): 18 CVEs, product BroadWin WebAccess <7.0; CVE-2012-0238 CWE-119 CVSS v2 10.0; 10.0 siblings CVE-2012-0240 (CWE-287), CVE-2011-4524/4526, CVE-2012-0243 (CWE-119), CVE-2011-4525 (CWE-284), CVE-2012-0242 (CWE-134); others 4.3-7.5; fix WebAccess 7.0, install over existing version, reboot before reinstalling if uninstalled; refer to installation manual security considerations. — CISA ICSA-12-047-01A
- CVE record (read 2026-11-28): state PUBLISHED, assigner certcc, vendor and product n/a, no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.04123, percentile 0.91580, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which WebAccess versions are affected?
All Advantech/BroadWin WebAccess versions before 7.0. NVD's CPE data lists versions up to and including 6.0. WebAccess 7.0 and later contain the fix.
How should WebAccess 7.0 be installed?
Advantech recommends installing 7.0 over the existing installation. If you uninstall the old version first, reboot the computer before reinstalling WebAccess.
Does the same advisory cover other flaws?
Yes. CISA ICSA-12-047-01A lists 18 CVEs in WebAccess before 7.0, including six more scored CVSS v2 10.0, plus SQL injection, cross-site scripting and CSRF issues. Upgrading to 7.0 addresses all of them.
Is CVE-2012-0238 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0412 (percentile 91.6) in the 2026-11-27 dataset.
Questions about this page?