CVE-2011-4536 is a heap-based buffer overflow in the HistoryServer service of WellinTech KingView 6.53, an HMI/SCADA package. A crafted network packet to the service overflows a heap buffer in nettransdll.dll and can run code as Local System. NVD scores it 10.0 (CVSS v2). WellinTech released a patch in December 2011.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

8.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2011-4536 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
WellinTech KingView HMI/SCADA, HistoryServer service (HistorySvr.exe / nettransdll.dll)cpe:2.3:a:wellintech:kingview:6.53:*:*:*:*:*:*:*NVD: KingView 6.53 and 65.30.2010.18018; CISA ICSA-11-355-02: Kingview HistoryServer 65.30.2010.18018. Fix: WellinTech patch

What does this mean for affected devices?

NVD's description reads: "Heap-based buffer overflow in nettransdll.dll in HistorySvr.exe (aka HistoryServer.exe) in WellinTech KingView 6.53 and 65.30.2010.18018 allows remote attackers to execute arbitrary code via a crafted op-code 3 packet." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119. NVD published the record on 2011-12-27; CERT/CC assigned it with no CNA score (NVD, CVE record).

What did ZDI and CISA publish?

The Zero Day Initiative advisory ZDI-11-351 (2011-12-22) scores it CVSS v2 10.0, says no authentication is needed, names HistoryServer.exe as the parent service listening on port 777, and says code runs "in the context of the service (Local System)". It credits Luigi Auriemma and records that the flaw was reported to the vendor on 2011-11-09. CISA advisory ICSA-11-355-02 (CSAF), "WellinTech KingView History Server Buffer Overflow", lists Kingview HistoryServer 65.30.2010.18018 and scores it CVSS v2 10.0 with CWE-119.

How do I fix it?

WellinTech created a patch and installation instructions and published them on its website, per CISA; ZDI also records a vendor update. The 2011 WellinTech and KingView news pages that carried the download are no longer reachable, so get a current KingView build from WellinTech support. Until the history server is updated, block port 777 at the plant boundary, allow it only from the KingView clients that need historical data, and keep the SCADA host off the internet.

CVE-2012-4711 is a later KingView overflow, and CVE-2014-0787 covers WellinTech KingSCADA. The memory corruption guide explains this class of bug, and the KEV and EPSS prioritization guide shows how to rank old ICS CVEs.

CVE-2011-4536 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0853, a percentile of 95.8, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2011-12-27; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE-119; CPEs wellintech kingview 6.53 and 65.30.2010.18018. — NVD
  • CISA ICSA-11-355-02 CSAF (read 2026-11-28): CWE-119 CVSS v2 10.0; Kingview HistoryServer 65.30.2010.18018; WellinTech patch and installation instructions on its website. — CISA ICSA-11-355-02
  • ZDI-11-351 (read 2026-11-28): published 2011-12-22; CVSS 10.0; HistoryServer.exe on port 777; code runs as Local System; reported 2011-11-09; credit Luigi Auriemma; vendor update. — Zero Day Initiative ZDI-11-351
  • en.wellintech.com/news/detail.aspx?contentid=166 no response and www.kingview.com/news/detail.aspx?contentid=587 HTTP 404 (checked 2026-11-28). — WellinTech
  • CVE record (read 2026-11-28): state PUBLISHED, assigner certcc; affected n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.08527, percentile 0.95806, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-11-355-02: WellinTech KingView History Server Buffer Overflow
  3. CISA ICSA-11-355-02 CSAF (machine-readable advisory)
  4. Zero Day Initiative ZDI-11-351: WellinTech KingView HistoryServer.exe
  5. CVE record CVE-2011-4536 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which KingView versions have CVE-2011-4536?

NVD lists KingView 6.53 and build 65.30.2010.18018; CISA ICSA-11-355-02 names the Kingview HistoryServer 65.30.2010.18018.

Is there a patch?

Yes. WellinTech published a patch with installation instructions in December 2011, per CISA and ZDI-11-351. The original download pages are offline, so ask WellinTech support for a current KingView build.

How do I reduce exposure before patching?

Block the HistoryServer port (777, per ZDI) at the plant boundary, allow it only from the KingView clients that read history, and keep the SCADA host off the internet. The service runs as Local System, so a compromise gives full control of the host.

Is CVE-2011-4536 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0853 (percentile 95.8) in the 2026-11-27 dataset.