Security Advisory

CVE-2011-2214: 7T IGSS ODBC Server Heap Corruption

Last updated:
  • CVE-2011-2214

CVE-2011-2214 is a memory corruption flaw in the ODBC server of 7-Technologies IGSS 8 and 9, a Danish SCADA package: a crafted packet to TCP port 20222 can crash the server or possibly let a remote attacker run code. NVD scores it 10.0 (CVSS v2), CISA's CSAF 9.8 (CVSS v3.0). 7T released a patch, delivered from its website or through the IGSS update feature.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

4.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2011-2214 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
7-Technologies IGSS (Interactive Graphical SCADA System)cpe:2.3:a:7t:igss:*:*:*:*:*:*:*:*CISA ICSA-11-018-02: IGSS 8 and 9; NVD: before 9.0.0.11143 (CPE up to and including 9.0.0.11129); fixed by the 7T patch or the in-application update

What does this mean for affected devices?

NVD's description reads: "Unspecified vulnerability in the Open Database Connectivity (ODBC) component in 7T Interactive Graphical SCADA System (IGSS) before 9.0.0.11143 allows remote attackers to execute arbitrary code via a crafted packet to TCP port 20222, which triggers memory corruption related to an "invalid structure being used."" NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with NVD-CWE-noinfo; there is no NVD v3 score. MITRE assigned the record with vendor and product n/a and no CNA score; NVD published it on 2011-05-31 (NVD, CVE record).

What does CISA say?

CISA's advisory ICSA-11-018-02 (CSAF), "7-Technologies IGSS 8 ODBC Server Remote Heap Corruption", states that the flaw "affects only IGSS Versions 8 and 9" and that a crafted packet to port 20222/TCP "can crash the server (DoS) or possibly allow the attacker to execute arbitrary code." CISA credits independent researcher Jeremy Brown. The CSAF version maps the flaw to CWE-241 (improper handling of unexpected data type) with a CVSS v3.0 score of 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Other 2011 IGSS flaws were covered separately: NVD ties CVE-2011-1565 to CVE-2011-1568 (directory traversal, stack overflows and a format string bug in IGSSdataServer.exe and dc.exe) to ICS-CERT alert ICS-ALERT-11-080-03.

How do I fix it?

CISA reports that "7T has created a patch for this vulnerability" and recommends downloading the latest patch from the 7T website or using the "update" feature inside IGSS; NVD places the fix at build 9.0.0.11143. The 7T site address named in the advisory, igss.com, now redirects to igss.schneider-electric.com (checked 2026-11-28), so current IGSS releases come from Schneider Electric. Block port 20222/TCP from anything outside the SCADA network, keep the IGSS server behind a firewall away from business networks, and use a VPN for remote access.

CVE-2013-0657 is a later IGSS stack overflow, and CVE-2011-0406 (WellinTech KingView) is another 2011 SCADA server overflow reachable without a login. The memory corruption guide explains heap corruption, and the OT/ICS security guide for small manufacturers covers SCADA server segmentation.

CVE-2011-2214 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0468, a percentile of 92.6, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2011-05-31; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; NVD-CWE-noinfo; CPEs 7t igss up to and including 9.0.0.11129, igss 8, igss 9; description: before 9.0.0.11143. CVE-2011-1565..1568 reference ICS-ALERT-11-080-03. — NVD
  • CISA ICSA-11-018-02 web page (read 2026-11-28): affects only IGSS 8 and 9; crafted packets to 20222/TCP crash the server or possibly execute code; researcher Jeremy Brown; 7T patch on website or via update feature; contact 7T at igss.com. — CISA ICSA-11-018-02
  • CISA ICSA-11-018-02 CSAF (read 2026-11-28): CVE-2011-2214 CWE-241, CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; IGSS 8|9; 7T patch, download from 7T website or use update feature. — CISA ICSA-11-018-02
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, vendor/product n/a; no CNA CVSS. www.igss.com redirected to igss.schneider-electric.com on 2026-11-28. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.04676, percentile 0.92551, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-11-018-02: 7-Technologies IGSS 8 ODBC Server Remote Heap Corruption
  3. CISA ICSA-11-018-02 CSAF (machine-readable advisory)
  4. CVE record CVE-2011-2214 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which IGSS versions are affected by CVE-2011-2214?

CISA says only IGSS 8 and 9 are affected. NVD gives the fix point as build 9.0.0.11143, so IGSS 9 builds before that and all IGSS 8 installations need the 7T patch.

How is the patch delivered?

CISA says 7T published the patch on its website and that existing users can also apply it with the update feature inside IGSS. The IGSS product site now redirects to Schneider Electric, which supplies current releases.

What can I do if I cannot patch an old IGSS server right away?

Block TCP port 20222 at the firewall so only hosts that need ODBC access can reach it, keep the server off business networks and the internet, and use a VPN for remote engineering access.

Is CVE-2011-2214 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0468 (percentile 92.6) in the 2026-11-27 dataset.