CVE-2013-0657 is a stack-based buffer overflow in Schneider Electric IGSS (Interactive Graphical SCADA System): data that does not follow the protocol, sent to TCP port 12397, overflows a buffer and lets a remote attacker run code with administrator privileges on IGSS 10 and earlier. NVD scores it 10.0 under CVSS v2. Schneider issued patches for IGSS V9 and V10.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
21.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2013-0657 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Interactive Graphical SCADA System (IGSS) | cpe:2.3:a:schneider-electric:interactive_graphical_scada_system:*:*:*:*:*:*:*:* | 10 and earlier (NVD: up to and including 10.0, plus 9.0); Schneider patches for V9 and V10, older versions must upgrade (CISA ICSA-13-018-01) |
What does this mean for affected devices?
NVD's description: "Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote attackers to execute arbitrary code by sending TCP port-12397 data that does not comply with a protocol." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119, and its CPE configuration covers IGSS up to and including 10.0 and version 9.0 (NVD). The CVE record, assigned by ICS-CERT and published on 2013-01-21, carries no CNA score.
What does CISA's advisory say?
CISA's ICSA-13-018-01, "Schneider Electric IGSS Buffer Overflow", was released on 2013-01-18 and last updated on 2013-05-06 for the commercial facilities and energy sectors, per the ICS Advisory Project index. CISA's CSAF record classifies it as CWE-121 (Stack-based Buffer Overflow) with the same CVSS v2 10.0 vector and states that, if unmitigated, "a remote attacker could cause a buffer overflow and allow malicious code to be executed with administrator privileges."
How do you fix CVE-2013-0657?
Per CISA, "the best mitigation for this vulnerability is applying the appropriate vendor-supplied patch": Schneider Electric issued two patches, one for IGSS V9 and one for V10, and Aaron Portnoy of Exodus Intelligence validated them. Users of older versions should upgrade or use other mitigations. At a minimum, CISA says, filter port 12397 so it accepts connections only from the IP addresses of the devices being controlled or monitored, and keep the SCADA network behind firewalls, away from business networks and the internet. The same class of memory bug in a SCADA communication process appears in Yokogawa CENTUM as CVE-2014-0781 and CVE-2015-5626. Our memory corruption fix guide covers how vendors remove this class of bug, and the KEV and EPSS prioritization guide explains why a CVE in the top EPSS percentiles deserves attention without a KEV listing.
CVE-2013-0657 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.21262, the 98th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD: stack-based buffer overflow in IGSS 10 and earlier via TCP port-12397 data that does not comply with a protocol; Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE-119; CPE IGSS up to and including 10.0 and 9.0; published 2013-01-21. — NVD
- CVE record: assigner icscert, published 2013-01-21, no CNA metrics. — CVE Services (CVE.org record)
- CISA ICSA-13-018-01 CSAF: IGSS application; CWE-121; CVSS v2 10.0; Schneider Electric issued two patches for V9 and V10; Aaron Portnoy of Exodus Intelligence validated the patches; older versions upgrade; filter port to specific IP addresses; code executed with administrator privileges. — CISA CSAF
- ICS Advisory Project: ICSA-13-018-01 released 1/18/2013, last updated 5/6/2013; sectors commercial facilities, energy; HQ France. — ICS Advisory Project
- CVE-2013-0657 is not in the CISA KEV catalog, version 2026.11.25 (1,805 entries), checked 2026-11-27. — CISA KEV
- EPSS 0.21262, percentile 0.98125, dataset 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which IGSS versions does CVE-2013-0657 affect?
IGSS 10 and earlier; NVD's CPEs cover versions up to and including 10.0 and 9.0. Schneider Electric issued patches for V9 and V10; older versions have to be upgraded (per NVD and CISA ICSA-13-018-01).
Does an attacker need a login to exploit CVE-2013-0657?
No. NVD's CVSS v2 vector has no authentication: sending malformed data to TCP port 12397 is enough, and CISA says the code runs with administrator privileges (per NVD and CISA ICSA-13-018-01).
What can you do if the IGSS server cannot be patched at once?
Filter TCP port 12397 so that only the IP addresses of the devices IGSS controls or monitors can connect, and keep the server behind firewalls away from business networks and the internet (per CISA ICSA-13-018-01).
Is CVE-2013-0657 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.21262, the 98th percentile, in the 2026-11-26 dataset, so it ranks above most CVEs for predicted exploitation even without a KEV listing (per CISA KEV and FIRST EPSS).