CVE-2011-0406 is a heap buffer overflow in the HistorySvr history service of WellinTech KingView 6.53, a Chinese HMI/SCADA package used in power, water and building systems: a long request to TCP port 777 can crash the service or let an unauthenticated attacker run code. NVD scores it 10.0 (CVSS v2). WellinTech fixed it in KingView 6.53 (2010-12-15) with a patch.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
21.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2011-0406 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| WellinTech KingView (Chinese and English editions) | cpe:2.3:a:wellintech:kingview:6.53:*:*:*:*:*:*:* | CISA ICSA-11-017-01: KingView 6.53; fixed by upgrading to 6.53 (2010-12-15) and installing the patch (NVD: 6.53) |
What does this mean for affected devices?
NVD's description reads: "Heap-based buffer overflow in HistorySvr.exe in WellinTech KingView 6.53 allows remote attackers to execute arbitrary code via a long request to TCP port 777." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119; there is no NVD v3 score. MITRE assigned the record with vendor and product n/a and no CNA score; NVD published it on 2011-01-11 (NVD, CVE record).
What does CISA say?
CISA's advisory ICSA-11-017-01 (CSAF), "WellinTech Kingview 6.53 Remote Heap Overflow", states that the flaw "affects both the Chinese and English language versions of KingView V6.53" and that successful exploitation "can lead a remote unauthenticated attacker to cause a denial of service, or to execute arbitrary code." CISA credits independent researcher Dillon Beresford. The CSAF version adds a CVSS v3.0 score of 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), in line with NVD's v2 10.0. CERT/CC's VU#180119 describes KingView as visualization software used in power, water conservancy, buildings, coal mining and metallurgy, and notes that exploit code was publicly available in 2011.
How do I fix it?
CISA recommends upgrading to "the latest Version 6.53(2010-12-15)" and installing the patch, and restricting network access to port 777/TCP with network or host firewall rules. The 2011 download links named by CISA and NVD (en.wellintech.com and a kingview.com news page) did not resolve or returned 404 when checked on 2026-11-28, so obtain current KingView builds through WellinTech support. A KingView 6.53 station still in service should sit on an isolated HMI network with no route from business networks or the internet.
CVE-2012-4711 (KingView kingMess overflow) and CVE-2014-0787 (KingSCADA AEserver overflow) are later WellinTech memory flaws. The memory corruption guide explains heap overflows, and the OT/ICS security guide for small manufacturers covers HMI network isolation.
CVE-2011-0406 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.2132, a percentile of 98.1, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2011-01-11; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPE wellintech kingview 6.53. — NVD
- CISA ICSA-11-017-01 web page (read 2026-11-28): Chinese and English KingView V6.53; heap overflow in HistorySrv on 777/TCP; remote unauthenticated DoS or code execution; researcher Dillon Beresford; upgrade to 6.53(2010-12-15) and install patch; firewall port 777/TCP. — CISA ICSA-11-017-01
- CISA ICSA-11-017-01 CSAF (read 2026-11-28): CVE-2011-0406 CWE-119, CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; firewall port 777/TCP; upgrade to 6.53(2010-12-15) and install patch. — CISA ICSA-11-017-01
- CERT/CC VU#180119 (read 2026-11-28): KingView used in power, water conservancy, buildings, coalmine, metallurgy; HistorySrv on port 777; exploit code publicly available; patch version 6.53(2010-12-15); restrict port 777/tcp. — CERT/CC VU#180119
- CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, vendor/product n/a; no CNA CVSS. en.wellintech.com did not resolve and kingview.com news detail contentid=528 returned 404 on 2026-11-28. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.21315, percentile 0.98128, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which KingView versions are affected by CVE-2011-0406?
CISA and NVD name KingView 6.53, both the Chinese and English editions. WellinTech fixed it in the 6.53 build dated 2010-12-15 together with a patch.
Does an attacker need a login?
No. CISA describes the attacker as remote and unauthenticated; any host that can reach the history service on TCP port 777 can send the request, which is why firewalling that port is the first mitigation.
Why does the CSAF file show a CVSS v3.0 score?
The original 2011 advisory had no CVSS score. CISA's machine-readable CSAF version carries CVSS v3.0 9.8, while NVD's Primary score is CVSS v2 10.0. Both rate it critical.
Is CVE-2011-0406 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.2132 (percentile 98.1) in the 2026-11-27 dataset.