Security Advisory

CVE-2010-4740: SCADA Engine BACnet OPC Client Overflow

Last updated:
  • CVE-2010-4740

CVE-2010-4740 is a stack buffer overflow in SCADA Engine BACnet OPC Client 1.0.24 and earlier, a Windows tool used with SCADA Engine's BACnet OPC Server in building automation: opening a crafted .csv file overflows a buffer in WTclient.dll while a status log message is built, which can run attacker code. NVD scores it 9.3 (CVSS v2). Version 1.0.25 fixes it.

Vulnerability summary

CVSS base score

9.3

Critical severity

EPSS score (FIRST)

41.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2010-4740 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
SCADA Engine BACnet OPC Clientcpe:2.3:a:scadaengine:bacnet_opc_client:*:*:*:*:*:*:*:*CISA ICSA-10-264-01: 1.0.24 confirmed, older versions may be affected (NVD: up to and including 1.0.24); fixed in 1.0.25

What does this mean for affected devices?

NVD's description reads: "Stack-based buffer overflow in WTclient.dll in SCADA Engine BACnet OPC Client before 1.0.25 allows user-assisted remote attackers to execute arbitrary code via a crafted .csv file, related to a status log message." NVD's Primary score is CVSS v2 9.3 (AV:N/AC:M/Au:N/C:C/I:C/A:C) with CWE-119; there is no NVD v3 score. MITRE assigned the record with vendor and product n/a and no CNA score; NVD published it on 2011-02-16 (NVD, CVE record).

What does CISA say?

CISA's advisory ICSA-10-264-01, "SCADA Engine BACnet OPC Client Buffer Overflow Vulnerability", confirms version 1.0.24 as vulnerable and warns that "older versions may also be affected." It explains that "a boundary error exists in WTclient.dll when preparing a status log message", exploitable "when the client opens a specially crafted malicious file (e.g., *.csv file)." CISA credits security researcher Jeremy Brown. The advisory carries no CVSS score, and CISA has no machine-readable CSAF file for it, so NVD's 9.3 is the only published score. CERT/CC's VU#660688 quotes SCADA Engine's description of the companion BACnet OPC Server as a bridge for data access, alarms and events and historical data between OPC clients and BACnet devices, the protocol used by HVAC, lighting and access control controllers.

How do I fix it?

CISA states that a software update is available from the SCADA Engine download page and that version 1.0.25 "effectively mitigates the vulnerability." CERT/CC adds: do not open .csv files from untrusted sources, since the flaw needs a user to load the file. The SCADA Engine website rejected automated requests (HTTP 406) when checked on 2026-11-28, so contact the vendor directly for current client builds. Run the OPC client on an engineering workstation that is not used for email or web browsing, and keep the building automation network separated from office networks.

CVE-2015-0979 is a later overflow in SCADA Engine's BACnet OPC Server, and CVE-2017-9946 (Siemens APOGEE PXC) is a BACnet-era building controller flaw. The BACnet protocol security guide covers building automation networks, and the memory corruption guide explains stack overflows.

CVE-2010-4740 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.4162, a percentile of 99.0, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2011-02-16; NVD Primary CVSS v2 9.3 AV:N/AC:M/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPE scadaengine bacnet_opc_client up to and including 1.0.24; references ICSA-10-264-01 and VU#660688. — NVD
  • CISA ICSA-10-264-01 web page (read 2026-11-28): BACnet OPC Client 1.0.24 confirmed, older versions may be affected; boundary error in WTclient.dll preparing a status log message; triggered when the client opens a crafted file (e.g. .csv); researcher Jeremy Brown; update to 1.0.25 from the SCADA Engine download page; no CVSS. No CSAF file for ICSA-10-264-01 in the cisagov/CSAF 2010 directory (checked 2026-11-28). — CISA ICSA-10-264-01
  • CERT/CC VU#660688 (read 2026-11-28): BACnet OPC Server provides DA, AE and HDA between OPC clients and BACnet-compliant devices; client stack overflow parsing .csv files in WTclient.dll; upgrade to 1.0.25; do not access .csv files from untrusted sources. www.scadaengine.com returned HTTP 406 on 2026-11-28. — CERT/CC VU#660688
  • CVE record (read 2026-11-28): state PUBLISHED, assigner mitre, vendor/product n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.41619, percentile 0.99004, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-10-264-01: SCADA Engine BACnet OPC Client Buffer Overflow Vulnerability
  3. CERT/CC VU#660688: SCADA Engine BACnet OPC Client buffer overflow
  4. CVE record CVE-2010-4740 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which BACnet OPC Client versions are affected by CVE-2010-4740?

CISA confirms version 1.0.24 and says older versions may also be affected; NVD's range covers everything up to 1.0.24. Version 1.0.25 is the fixed release.

Can it be exploited over the network without a user?

No. A user has to open a crafted .csv file in the client, which is why NVD scores it user-assisted. Treat .csv files from outside sources as untrusted on engineering workstations.

Why is there no CISA CVSS score or CSAF file?

ICSA-10-264-01 was published in 2010 without a CVSS score, and CISA's machine-readable CSAF set has no file for it. NVD's Primary CVSS v2 9.3 is the published score.

Is CVE-2010-4740 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.4162 (percentile 99.0) in the 2026-11-27 dataset.