CVE-2017-9946 is an authentication bypass (CWE-287) in the integrated web server of Siemens APOGEE PXC and TALON TC building-automation field panels: anyone who reaches ports 80 or 443 can skip the login and download sensitive data. NVD scores it 7.5. BACnet models are fixed in V3.5; Siemens lists no fix for the P2 Ethernet models.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
25.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-9946 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens APOGEE PXC Compact (BACnet) and APOGEE PXC Modular (BACnet) | cpe:2.3:o:siemens:apogee_pxc_firmware:*:*:*:*:*:*:*:* | all versions before V3.5; fixed in V3.5 (Siemens ProductCERT SSA-148078) |
| Siemens TALON TC Compact (BACnet) and TALON TC Modular (BACnet) | cpe:2.3:o:siemens:talon_tc_modular_firmware:*:*:*:*:*:*:*:* | all versions before V3.5; fixed in V3.5 (Siemens ProductCERT SSA-148078) |
| Siemens APOGEE PXC Compact (P2 Ethernet) and APOGEE PXC Modular (P2 Ethernet) | — | all versions; no fix, disable the integrated web server (Siemens ProductCERT SSA-148078 V1.1) |
What does this mean for affected devices?
CVE-2017-9946 affects the web server built into Siemens APOGEE PXC and TALON TC field panels, the direct digital controllers that run HVAC and other building systems on BACnet networks. Siemens' description, which NVD reuses, says that "an attacker with network access to the integrated web server (80/tcp and 443/tcp) could bypass the authentication and download sensitive information from the device." Both Siemens and NVD record CWE-287, improper authentication, and NVD gives its own Primary CVSS v3.1 score of 7.5 (high), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N (NVD).
Siemens adds the temporal metrics E:P/RL:O/RC:C, meaning proof-of-concept exploit code exists and an official fix is available. CISA's SSVC entry in the CVE record, dated 2026-06-02, also lists exploitation as "poc" and the attack as automatable. Without a valid login, the attacker gets the same data the panel's web pages expose to its operators.
Which APOGEE and TALON panels are affected, and what fixes them?
Siemens ProductCERT SSA-148078 (V1.1, last updated 2022-06-14) lists six products, all "high-performance Direct Digital Control (DDC) devices" of the APOGEE and TALON automation systems:
- APOGEE PXC Compact (BACnet) and APOGEE PXC Modular (BACnet): all versions before V3.5; update to V3.5 or later.
- TALON TC Compact (BACnet) and TALON TC Modular (BACnet): all versions before V3.5; update to V3.5 or later.
- APOGEE PXC Compact (P2 Ethernet) and APOGEE PXC Modular (P2 Ethernet): all versions. Siemens lists no fix for these and says to disable the integrated web server. They were added in V1.1 after RoseSecurity reported the flaws on the P2 Ethernet variants.
For every product, Siemens recommends disabling the integrated web server when it is not in use and protecting network access to the panels. The V3.5 firmware is distributed through the Siemens partner portal. CISA republished the advisory as ICSA-17-285-05 (Update A), which lists the deployment as worldwide across multiple critical infrastructure sectors.
NVD's CPE configuration covers the BACnet variants only (APOGEE PXC, APOGEE PXC Modular, TALON TC Compact and TALON TC Modular firmware before 3.5). It has no entry for the P2 Ethernet panels, so a CPE-based scan will not flag them even though Siemens lists every version as affected. Check those panels by model, not by CPE.
How does it relate to CVE-2017-9947?
They are the same advisory and the same web server. CVE-2017-9947 is a path traversal that reveals the panel's file-system structure, and V3.5 fixes both on the BACnet models. Our BACnet protocol security guide lists this advisory next to KMC Controls' CVE-2016-4495, another unauthenticated read through a BACnet device's web interface. For the weakness class, see our authentication bypass fix guide.
CVE-2017-9946 is not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.25437, the 98th percentile, in the 2026-11-16 dataset, a high value for a building-automation flaw (CISA KEV, FIRST EPSS).
To fix it, update APOGEE PXC and TALON TC BACnet panels to V3.5 or later. On P2 Ethernet panels, and on any panel where the web pages are not needed, disable the integrated web server. In every case keep ports 80 and 443 on the panels reachable only from the building management network, never from business networks or the internet.
Evidence
- Attacker with network access to the integrated web server (80/tcp, 443/tcp) could bypass authentication and download sensitive information; APOGEE PXC and TALON TC before V3.5; NVD Primary CVSS v3.1 7.5; CWE-287; CPE configuration covers apogee_pxc, apogee_pxc_modular, talon_tc_compact, talon_tc_modular firmware before 3.5. — NVD
- Six affected products: PXC Compact/Modular (BACnet) and TALON TC Compact/Modular (BACnet) before V3.5, fixed in V3.5; PXC Compact/Modular (P2 Ethernet) all versions, no fix, disable the web server; V1.1 2022-06-14 added P2 Ethernet, reported by RoseSecurity; vector with E:P/RL:O/RC:C; products are DDC devices. — Siemens ProductCERT SSA-148078
- CISA Update A republishes SSA-148078; sectors Multiple, deployed worldwide. — CISA ICSA-17-285-05 (CSAF)
- CISA SSVC 2026-06-02: exploitation poc, automatable yes. — NVD (CVE record ADP data)
- Not in the CISA KEV catalog as of 2026-11-17 (catalog version 2026.11.13). — CISA KEV
- EPSS 0.25437 (98th percentile), dataset 2026-11-16, read 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Siemens panels does CVE-2017-9946 affect?
APOGEE PXC Compact and Modular and TALON TC Compact and Modular with BACnet before V3.5, plus every version of APOGEE PXC Compact and Modular (P2 Ethernet) (per Siemens ProductCERT SSA-148078).
Is there a fix for CVE-2017-9946 on P2 Ethernet panels?
No. Siemens lists no fix for the P2 Ethernet variants and recommends disabling the integrated web server on them. The BACnet variants are fixed in V3.5 (per Siemens ProductCERT SSA-148078).
Does a CPE scan find every panel affected by CVE-2017-9946?
No. NVD's CPE configuration lists only the BACnet variants before 3.5, so P2 Ethernet panels need to be checked by model (per NVD and Siemens ProductCERT SSA-148078).
Is CVE-2017-9946 in the CISA KEV catalog?
No, not as of 2026-11-17 (catalog version 2026.11.13). FIRST EPSS gives it 0.25437, the 98th percentile, in the 2026-11-16 dataset (per CISA KEV and FIRST EPSS).