CVE-2015-0979 is a heap-based buffer overflow (CWE-122) in the SOAP web interface of SCADA Engine BACnet OPC Server, a Windows service that serves BACnet data to OPC clients. A remote attacker can run code with one crafted packet. NVD scores it 9.0 (CVSS v2), CISA 8.3. Version 2.1.371.24 removes the interface.
Vulnerability summary
CVSS base score
9
Critical severity
EPSS score (FIRST)
4.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2015-0979 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| SCADA Engine BACnet OPC Server | cpe:2.3:a:scadaengine:bacnet_opc_server:*:*:*:*:*:*:*:* | Versions up to and including 2.1.359.22 (CISA and NVD CPE); fixed in 2.1.371.24 |
What does this mean for affected devices?
The CVE record says: "Heap-based buffer overflow in the SOAP web interface in SCADA Engine BACnet OPC Server before 2.1.371.24 allows remote attackers to execute arbitrary code via a crafted packet." CISA classifies it as CWE-122, heap-based buffer overflow; NVD uses the parent CWE-119 (NVD; the CVE.org record carries the same text).
How severe is it?
NVD's Primary score is CVSS v2 9.0, AV:N/AC:L/Au:N/C:P/I:P/A:C. CISA's advisory scores 8.3 with AV:N/AC:M/Au:N/C:P/I:P/A:C; the only difference is attack complexity. The CVE record itself carries no CNA score, and NVD has no CVSS v3 score for this 2015 record. CISA notes that an attacker with low skill could exploit it remotely and that no public exploit was known at release.
Which versions are affected and what is the fix?
CISA's ICSA-15-069-03, released on 2015-03-10, covers BACnet OPC Server up to and including 2.1.359.22 and credits independent researcher Josep Pi Rodriguez. SCADA Engine estimated that the product is deployed worldwide. The same advisory lists two sibling flaws in the same SOAP interface: CVE-2015-0980, a format string flaw (CISA CVSS v2 7.8), and CVE-2015-0981, an authentication bypass that allows reading or writing arbitrary database fields (CISA 10.0). SCADA Engine fixed all three in version 2.1.371.24, which removes the SOAP web interface from the Windows service, replaces it with a proprietary protocol and blocks requests from other computers (CSAF). Install 2.1.371.24 or later; until then, restrict network access to the server to the hosts that need it.
The server sits between BACnet building automation networks and OPC clients, so keep it inside the building-control zone, never on the internet. The BACnet protocol security guide covers zoning for building networks, and the memory corruption fix guide covers the coding fix. Related building automation pages: CVE-2016-4494 (KMC BAC-5051E BACnet router) and CVE-2015-7906 (LOYTEC router).
Is CVE-2015-0979 exploited?
It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.04564, the 92.38th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): published 2015-03-14, status Modified; NVD Primary CVSS v2 9.0 AV:N/AC:L/Au:N/C:P/I:P/A:C; CWE-119; CPE scadaengine bacnet_opc_server up to and including 2.1.359.22. — NVD
- CISA ICSA-15-069-03 CSAF (read 2026-11-27): SCADA Engine OPC Server <=2.1.359.22; CVE-2015-0979 CWE-122 CVSS v2 8.3 AV:N/AC:M/Au:N/C:P/I:P/A:C; CVE-2015-0980 CWE-20 7.8; CVE-2015-0981 CWE-287 10.0; version 2.1.371.24 removes the SOAP web interface in the Windows service, replaces it with a proprietary protocol, blocks requests from other PCs. — CISA ICSA-15-069-03
- CISA advisory page (read 2026-11-27 via a page fetch): released 2015-03-10, last revised 2018-08-27; researcher Josep Pi Rodriguez; deployed globally per SCADA Engine; remotely exploitable; no known public exploits; low skill. — CISA
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.04564, percentile 0.92375, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2015-0979?
BACnet OPC Server 2.1.371.24. Per CISA ICSA-15-069-03 it removes the SOAP web interface from the Windows service, replaces it with a proprietary protocol and blocks requests from other computers. Versions up to and including 2.1.359.22 are affected.
Does the same update fix the other SOAP flaws?
Yes. CISA lists CVE-2015-0980 (format string, CVSS v2 7.8) and CVE-2015-0981 (authentication bypass to read or write database fields, 10.0) in the same advisory, all fixed by 2.1.371.24 because the SOAP interface is removed.
Why do NVD and CISA scores differ?
NVD rates attack complexity low (CVSS v2 9.0); CISA rates it medium (8.3). Both rate partial confidentiality and integrity impact and complete availability impact with no authentication.
Is CVE-2015-0979 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.04564, the 92.38th percentile, in the 2026-11-26 dataset.
Questions about this page?