CVE-2025-59301 is a denial-of-service flaw in the Delta Electronics DVP15MC11T. The firmware does not properly validate Modbus/TCP packets, so crafted traffic to the Modbus port can stop it. NVD scores it 7.5 and Delta 4.0. Firmware before v1.16.0 is affected, and Delta fixes it in v1.16.0, published in its December 2025 advisory.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2025-59301 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Delta Electronics DVP15MC11T | cpe:2.3:o:deltaww:dvp15mc11t_firmware:*:*:*:*:*:*:*:* | before v1.16.0; fixed in v1.16.0 (Delta-PCSA-2025-00020; NVD before 1.16.0) |
What does this mean for affected devices?
NVD carries Delta's description: "Delta Electronics DVP15MC11T lacks proper validation of the modbus/tcp packets and can lead to denial of service." The CWE is CWE-20, improper input validation. The record was published on 2025-12-22 (NVD, CVE record).
Why do NVD and Delta score it so differently?
NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H): any host that reaches the Modbus/TCP port can stop the device. Delta, the CNA, scores it 4.0 (CVSS:3.1/AV:A/AC:H/PR:H/UI:R/S:U/C:N/I:N/A:H), assuming an adjacent attacker with high privileges, high complexity and user interaction. Delta's advisory gives no reason for those conditions, and Modbus/TCP itself has no login, as the Modbus protocol guide explains. Plan as if NVD's reading applies on any flat control network.
What does Delta's advisory say?
Delta's Delta-PCSA-2025-00020, first published on 2025-12-22, lists the DVP15MC11T prior to v1.16.0 as affected, rates the flaw Medium and states no workaround. The fix is firmware v1.16.0 or later. The CVE record credits CNVD. NVD's CPE data matches: DVP15MC11T firmware before 1.16.0.
What should operators do?
Upgrade the DVP15MC11T firmware to v1.16.0 or later. Until then, limit who can reach its Modbus/TCP port: put the device behind a firewall, allow only the HMI and SCADA hosts that need it, keep it off the internet and the business network, and use a VPN for remote access, as Delta's general recommendations say. The Delta Electronics guide covers Delta's other PLC firmware flaws, including the AS320T denial of service CVE-2026-1952, and the input handling fix guide explains the packet validation that closes this class.
CVE-2025-59301 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00236, the 14.8th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Analyzed; published 2025-12-22; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; Delta (CNA) Secondary v3.1 4.0 CVSS:3.1/AV:A/AC:H/PR:H/UI:R/S:U/C:N/I:N/A:H; CWE-20 (Delta); CPE deltaww dvp15mc11t_firmware before 1.16.0 on dvp15mc11t hardware. — NVD
- Delta-PCSA-2025-00020 (first published and last updated 2025-12-22): DVP15MC11T Modbus/TCP DoS; DVP15MC11T prior to v1.16.0; CWE-20, Medium, CVSS v3 4.0; workaround No; fix upgrade to v1.16.0 or later. — Delta Electronics
- CVE record (checked 2026-11-23): state PUBLISHED, CNA Deltaww, published 2025-12-22, affected < 1.16.0, solution upgrade firmware to v1.16.0 or later, credit CNVD. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.00236, percentile 0.14752, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which DVP15MC11T firmware fixes CVE-2025-59301?
Firmware v1.16.0 or later (Delta-PCSA-2025-00020). Every version before v1.16.0 is affected.
Why does NVD score it 7.5 when Delta scores 4.0?
NVD assumes a network attacker with no privileges or user interaction. Delta's vector assumes an adjacent attacker with high privileges, high complexity and user interaction, which lowers the score to 4.0.
How can I reduce exposure before upgrading?
Restrict the Modbus/TCP port to the HMI and SCADA hosts that need it with a firewall, keep the device off the internet and the business network, and use a VPN for remote access, in line with Delta's general recommendations.
Is CVE-2025-59301 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00236 (14.8th percentile) in the 2026-11-22 dataset.