CVE-2025-3395 is a user management bypass in ABB Automation Builder for projects that contain AC500 V2 or SM560-S devices: the device application files inside the project can be modified to overrule Automation Builder's user management. NVD scores it 5.5; ABB scores it 7.1. ABB's workaround is to set the project's Security option to "Encryption".
Vulnerability summary
CVSS base score
5.5
Medium severity
EPSS score (FIRST)
0.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2025-3395 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| ABB Automation Builder | cpe:2.3:a:abb:automation_builder:*:*:*:*:*:*:*:* | through 2.8.0 (ABB: all versions; set Security to 'Encryption'); CISA ICSA-25-133-04 lists 2.8.1 and later as fixed; NVD up to and including 2.8.0 |
What does this mean for affected devices?
NVD carries ABB's description: "Incorrect Permission Assignment for Critical Resource, Cleartext Storage of Sensitive Information vulnerability in ABB Automation Builder. This issue affects Automation Builder: through 2.8.0." NVD's Primary score is CVSS v3.1 5.5 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N), integrity impact only. ABB, the CNA, scores it 7.1 (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N) and 8.4 in CVSS v4.0, adding high confidentiality impact. ABB names CWE-732 and CWE-312. The record was published on 2025-04-30 (NVD, CVE record).
What can be changed?
ABB's advisory 3ADR011407 (revision B, 2025-07-25): "Automation Builder projects including AC500 V2 or SM560-S devices contain the application files for these devices. An attacker could try to modify parts of these files so that the project can be changed by overruling the Automation Builder user management." The attack needs access to the project at file level. Jiho Shin of Sungkyunkwan University reported it; ABB knew of no exploitation.
How is it closed?
ABB says all Automation Builder versions are affected. The workaround is the project setting under "Project" → "Project Settings…" → "Security": set "Encryption". This stops unauthorized users from opening the project, but ABB notes that "Authorized users can open the project and with that exploit the vulnerability." ABB ties the 2.8.1 default "Integrity check" only to the sibling CVE-2025-3394, while CISA's ICSA-25-133-04 (Update A, 2026-05-21) lists Automation Builder 2.8.0 and earlier as affected and 2.8.1 and later as fixed for both CVEs. NVD's CPE covers versions up to and including 2.8.0. Since the vendor text and CISA's status differ, set "Encryption" on AC500 V2 and SM560-S projects even on 2.8.1 or later, and keep the list of authorized project users short.
Cleartext secrets in OT engineering files also appear in CVE-2022-2513, where PCM600 backups expose relay passwords. See the ABB AC500, RTU500 and Relion guide and the weak cryptography fix guide.
CVE-2025-3395 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00099, the 0.8th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Analyzed; published 2025-04-30; NVD Primary CVSS v3.1 5.5 AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N; ABB Secondary v3.1 7.1 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N and v4.0 8.4; CWE-312 (ABB, NVD weakness list); CPE abb:automation_builder up to and including 2.8.0. — NVD
- ABB 3ADR011407 rev B 2025-07-25 (initial 2025-04-30), PDF read 2026-11-23: all Automation Builder versions affected by CVE-2025-3394 and CVE-2025-3395; workarounds: project setting 'Security' = 'Integrity check' (3394), 'Encryption' (3395, authorized users can still open the project and exploit it); from 2.8.1 the default is 'Integrity check', which prevents CVE-2025-3394; exploitation needs file-level access to the project; responsible disclosure, no exploitation known; Automation Builder is the programming tool mainly for AC500 PLCs and CP600 panels. — ABB 3ADR011407
- CISA ICSA-25-133-04 Update A (2025-05-13, updated 2026-05-21), CSAF read 2026-11-23: known_affected Automation Builder <= 2.8.0, fixed >= 2.8.1 for both CVEs; CWE-732; CVSS v3.1 7.8 (3394) and 7.1 (3395). — CISA ICSA-25-133-04
- CVE record (checked 2026-11-23): state PUBLISHED, CNA ABB, published 2025-04-30; Automation Builder through 2.8.0; CWE-732 and CWE-312; credit Jiho Shin, Sungkyunkwan University; CNA CVSS v4.0 8.4, v3.1 7.1. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.00099, percentile 0.00785, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
How do I protect Automation Builder projects against CVE-2025-3395?
Set "Project" → "Project Settings…" → "Security" to "Encryption" for projects with AC500 V2 or SM560-S devices. Unauthorized users can then no longer open the project; authorized users still can (ABB 3ADR011407).
Does Automation Builder 2.8.1 fix CVE-2025-3395?
CISA ICSA-25-133-04 lists 2.8.1 and later as fixed. ABB's own advisory links the new 2.8.1 default only to CVE-2025-3394 and keeps "Encryption" as the workaround for CVE-2025-3395.
Which devices are involved?
Projects that include AC500 V2 PLCs or SM560-S devices, because they contain the application files for these devices.
Is CVE-2025-3395 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00099 (0.8th percentile) in the 2026-11-22 dataset.
Questions about this page?