CVE-2024-6077 is a denial-of-service flaw in the CIP Security object of Rockwell Automation ControlLogix and GuardLogix 5580, CompactLogix and Compact GuardLogix 5380, CompactLogix 5480 controllers and the 1756-EN4 module: crafted packets, sent without credentials, make the device unavailable until it is factory reset. NVD scores it 7.5. Fixed controller firmware is v33.017, v34.014, v35.013 or v36.011 and later; the 1756-EN4 fix is v6.001.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2024-6077 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation CompactLogix 5380 | cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:32.011:*:*:*:*:*:*:* | First known affected v32.011; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). NVD CPE lists only firmware 32.011 |
| Rockwell Automation CompactLogix 5380 Process | — | First known affected v33.011; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). No NVD CPE entry |
| Rockwell Automation Compact GuardLogix 5380 SIL 2 | cpe:2.3:o:rockwellautomation:compact_guardlogix_5380_sil_2_firmware:32.013:*:*:*:*:*:*:* | First known affected v32.013; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). NVD CPE lists only firmware 32.013 |
| Rockwell Automation Compact GuardLogix 5380 SIL 3 | cpe:2.3:o:rockwellautomation:compact_guardlogix_5380_sil_3_firmware:32.011:*:*:*:*:*:*:* | First known affected v32.011; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). NVD CPE lists only firmware 32.011 |
| Rockwell Automation CompactLogix 5480 | cpe:2.3:o:rockwellautomation:compactlogix_5480_firmware:32.011:*:*:*:*:*:*:* | First known affected v32.011; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). NVD CPE lists only firmware 32.011 |
| Rockwell Automation ControlLogix 5580 | cpe:2.3:o:rockwellautomation:controllogix_5580_firmware:33.011:*:*:*:*:*:*:* | First known affected v32.011; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). NVD CPE lists only firmware 33.011, not the v32.011 that Rockwell and CISA name |
| Rockwell Automation ControlLogix 5580 Process | — | First known affected v33.011; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). No NVD CPE entry |
| Rockwell Automation GuardLogix 5580 | cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:32.011:*:*:*:*:*:*:* | First known affected v32.011; corrected in v33.017, v34.014, v35.013, v36.011 and later (Rockwell CNA record, CISA ICSA-24-256-18). NVD CPE lists only firmware 32.011 |
| Rockwell Automation 1756-EN4 communication module | cpe:2.3:o:rockwellautomation:1756-en4_firmware:2.001:*:*:*:*:*:*:* | First known affected v2.001; corrected in v6.001 and later (Rockwell CNA record, CISA ICSA-24-256-18). NVD CPE lists only firmware 2.001 |
What does this mean for affected devices?
NVD carries the Rockwell description: "A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover." Rockwell Automation is the CNA and classes it CWE-20 (improper input validation); NVD's own weakness entry is NVD-CWE-noinfo. Rockwell's record names its advisory SD1963 and says the issue was found internally. The record was published on 2024-09-12 (NVD, CVE record).
How severe is it, and who scored it?
NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), and CISA's ICSA-24-256-18 CSAF file gives the same v3.1 vector and 7.5. Rockwell, as CNA, scores it CVSS v4.0 8.7 (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N). Both versions describe the same attack: reachable over the network, low complexity, no privileges, no user interaction, and an availability impact only. CISA's SSVC entry on the CVE record reads exploitation none, automatable yes, technical impact partial.
Why is a factory reset worse than a fault?
Other Logix CIP flaws, such as CVE-2022-3157 and CVE-2026-11317, end in a major nonrecoverable fault; for CVE-2026-11317 NVD says a program download is required to recover. Here CISA's risk evaluation says exploitation "may cause the device to become unavailable and require a factory reset to recover." A factory reset returns the device to its out-of-box state, so recovery means someone restoring the project and settings, which makes an outage from this flaw longer than a plain fault. The flaw sits in the CIP Security object, the part of the firmware that implements ODVA's secure EtherNet/IP transport, so any host that can reach the device on EtherNet/IP is a possible source. CISA's advisory states that no known public exploitation specifically targeting this vulnerability had been reported to it.
Which devices and firmware versions are affected?
| Product | First known affected | Corrected in |
|---|---|---|
| CompactLogix 5380 | v32.011 | v33.017, v34.014, v35.013, v36.011 and later |
| CompactLogix 5380 Process | v33.011 | v33.017, v34.014, v35.013, v36.011 and later |
| Compact GuardLogix 5380 SIL 2 | v32.013 | v33.017, v34.014, v35.013, v36.011 and later |
| Compact GuardLogix 5380 SIL 3 | v32.011 | v33.017, v34.014, v35.013, v36.011 and later |
| CompactLogix 5480 | v32.011 | v33.017, v34.014, v35.013, v36.011 and later |
| ControlLogix 5580 | v32.011 | v33.017, v34.014, v35.013, v36.011 and later |
| ControlLogix 5580 Process | v33.011 | v33.017, v34.014, v35.013, v36.011 and later |
| GuardLogix 5580 | v32.011 | v33.017, v34.014, v35.013, v36.011 and later |
| 1756-EN4 | v2.001 | v6.001 and later |
The table follows the Rockwell CNA record and ICSA-24-256-18 (released 2024-09-12). Rockwell's own notice is SD1963. The middle column is the first version known to be affected, not the only one: a controller on v33.011 or v34.011 is affected until it reaches the fixed revision for its major release.
NVD's CPE configuration does not match that reading. It lists one exact firmware version per family (32.011, 32.013 for the SIL 2 controller, 2.001 for the 1756-EN4), gives ControlLogix 5580 as 33.011 instead of v32.011, and has no entry for the two Process variants. A CPE-only scanner will therefore miss most affected revisions; match on the CISA CSAF product tree and the corrected versions instead.
How do you fix or mitigate it?
Update the controller to v33.017, v34.014, v35.013 or v36.011 or later, and the 1756-EN4 to v6.001 or later. Record the revision as major.minor, because a 33.x controller below 33.017 is still affected. Where an update has to wait, Rockwell's mitigation is for users who do not want CIP Security to disable the feature per device, as described in "Disable CIP Security" in chapter 2 of its publication SECURE-AT001. Rockwell also points to its security best practices page, and CISA repeats its general advice to keep control system devices off the internet and behind firewalls, isolated from business networks.
Our Rockwell Logix controller guide covers how to read controller revisions and the other Logix CVE families, the EtherNet/IP and CIP security guide explains what CIP Security adds, and the input handling fix guide covers the weakness class. Related Logix advisories: CVE-2022-3157 (malformed CIP request, older 5370/5570 controllers), CVE-2021-22681, the transport gap CIP Security is meant to close, and CVE-2022-1161.
CVE-2024-6077 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00558, the 47.4th percentile, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-22): status Analyzed, published 2024-09-12, last modified 2026-06-17; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; Rockwell CVSS v4.0 8.7 Secondary; CWE-20 (Rockwell), NVD-CWE-noinfo (NVD); vulnerable CPEs are exact versions only: compactlogix_5380 32.011, compact_guardlogix_5380_sil_2 32.013, compact_guardlogix_5380_sil_3 32.011, compactlogix_5480 32.011, controllogix_5580 33.011, guardlogix_5580 32.011, 1756-en4 2.001; reference SD1963. — NVD
- NVD CVE-2026-11317 description (read 2026-11-22): a crafted CIP message can result in a major nonrecoverable fault (MNRF); a program download is required to recover. — NVD
- CVE record (checked 2026-11-22): state PUBLISHED, CNA Rockwell, published 2024-09-12; source advisory SD1963, discovery INTERNAL; CWE-20; CVSS v4.0 8.7; nine affected products with first-known versions (CompactLogix 5380 v.32.011, 5380 Process v.33.011, Compact GuardLogix 5380 SIL 2 v.32.013, SIL 3 v.32.011, CompactLogix 5480 v.32.011, ControlLogix 5580 v.32.011, 5580 Process v.33.011, GuardLogix 5580 v.32.011, 1756-EN4 v2.001); corrected in v33.017, v34.014, v35.013, v36.011 and later (1756-EN4 v6.001); mitigation: disable CIP Security per device per SECURE-AT001 chapter 2; CISA-ADP SSVC exploitation none, automatable yes, technical impact partial. — CVE.org
- CISA CSAF ICSA-24-256-18 version 1 (2024-09-12), read 2026-11-22: CWE-20, CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; risk evaluation 'may cause the device to become unavailable and require a factory reset to recover'; same nine products and vendor_fix versions; no known public exploitation specifically targeting this vulnerability reported to CISA. — CISA CSAF ICSA-24-256-18
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-22. — CISA KEV
- EPSS 0.00558, percentile 0.47353, dataset 2026-11-21, read 2026-11-22. — FIRST EPSS

Related advisories
Sources
- NVD
- CISA CSAF: ICSA-24-256-18 Rockwell Automation ControlLogix/GuardLogix 5580 and CompactLogix/Compact GuardLogix 5380 (machine-readable advisory)
- Rockwell Automation security advisory SD1963
- Rockwell Automation security best practices (linked from the CNA record)
- CVE.org record CVE-2024-6077 (CNA: Rockwell)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which firmware fixes CVE-2024-6077?
For ControlLogix 5580, ControlLogix 5580 Process, GuardLogix 5580, CompactLogix 5380, CompactLogix 5380 Process, Compact GuardLogix 5380 SIL 2 and SIL 3, and CompactLogix 5480, update to v33.017, v34.014, v35.013, v36.011 or later. For the 1756-EN4 module, update to v6.001 or later (per the Rockwell CNA record and CISA ICSA-24-256-18).
What if I cannot update the controller right away?
Rockwell's mitigation is for users who do not need CIP Security to disable the feature per device, following 'Disable CIP Security' in chapter 2 of publication SECURE-AT001. CISA also advises keeping control system devices off the internet and behind firewalls, isolated from business networks.
How does recovery differ from other Logix denial-of-service flaws?
CISA's risk evaluation says an exploited device becomes unavailable and requires a factory reset to recover. Other Logix CIP flaws, such as CVE-2022-3157 and CVE-2026-11317, end in a major nonrecoverable fault instead. A factory reset returns the device to its out-of-box state, so its project and settings have to be restored afterwards.
Will a CPE-based scanner find every affected controller?
Probably not. As of 2026-11-22, NVD lists one exact firmware version per product family, gives ControlLogix 5580 as 33.011 rather than the v32.011 Rockwell names, and has no entry for the 5380 and 5580 Process variants. Match on the CISA CSAF product tree and the corrected versions instead.
Is CVE-2024-6077 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries), CISA's advisory reports no known public exploitation specifically targeting it, and its EPSS score is 0.00558 (47.4th percentile) in the 2026-11-21 dataset.
Questions about this page?