Security Advisory

CVE-2024-34171: Fuji Electric V-SFT Stack Overflow

Last updated:
  • CVE-2024-34171

CVE-2024-34171 is a stack-based buffer overflow (CWE-121) in Fuji Electric Monitouch V-SFT, the configuration software for Monitouch HMI panels, before version 6.2.3.0. It could let an attacker execute arbitrary code. NVD scores it 9.8; CISA, the CNA, rates it 7.8 because exploitation needs a local user action. Fuji Electric fixed it in V-SFT 6.2.3.0.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

0.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-34171 · Source: NVD

Affected components

ComponentCPEVersion range
Fuji Electric Monitouch V-SFTcpe:2.3:a:fujielectric:monitouch_v-sft:*:*:*:*:*:*:*:*Versions before 6.2.3.0 (CISA ICSA-24-151-02, CVE record, NVD CPE); fixed in V-SFT 6.2.3.0

What does this mean for affected devices?

NVD describes CVE-2024-34171 as follows: "Fuji Electric Monitouch V-SFT is vulnerable to a stack-based buffer overflow, which could allow an attacker to execute arbitrary code." CISA ICS, the CNA, classifies it as CWE-121 and scores it 7.8 (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H) and 8.5 in CVSS v4. NVD's own Primary CVSS v3.1 score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), with a network vector and no user interaction; NVD lists no weakness of its own. NVD's CPE configuration covers V-SFT before 6.2.3.0 (NVD, CVE record).

Why do NVD and CISA disagree on the score?

CISA advisory ICSA-24-151-02 of 2024-05-30 states that these vulnerabilities are not exploitable remotely, and its vector is local with user interaction required. NVD's vector assumes network access and no user interaction. Both rate the impact on confidentiality, integrity and availability as high, so the code execution outcome is the same either way. Fuji Electric describes Monitouch V-SFT as configuration software with screen configuration tools for its HMI displays, compatible with all Fuji Electric HMIs; CISA lists the Critical Manufacturing and Energy sectors, worldwide deployment and a vendor based in Japan. The advisory, updated on 2024-06-04 (Update A), has three CVEs found by kimiya working with Trend Micro Zero Day Initiative: CVE-2024-5271 and CVE-2024-5597 (type confusion, CWE-843) and this stack overflow. NVD also scores CVE-2024-5597 9.8.

How do you fix CVE-2024-34171?

Fuji Electric recommends updating to Monitouch V-SFT 6.2.3.0; CISA links Fuji Electric's technical document library for it (CSAF file). Until engineering workstations are updated, CISA's general advice applies: keep control system networks off the internet, behind firewalls and separated from business networks, and use an up-to-date VPN for remote access. The memory corruption fix guide covers stack overflows in parsers like this, and the OT security guide for small manufacturers covers how to manage engineering workstations. A similar HMI design software flaw on this site is the Delta DIAScreen stack overflow CVE-2024-7502.

Is CVE-2024-34171 exploited?

It is absent from the CISA KEV catalog as of 2026-11-26 (catalog version 2026.11.25), and CISA reported no known public exploitation at publication. FIRST EPSS gives 0.00788, the 52.73rd percentile, in the 2026-11-25 dataset (FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • NVD: Analyzed; Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CISA ICS Secondary v3.1 7.8 AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H and v4 8.5; CWE-121 from CISA only; CPE fujielectric monitouch_v-sft before 6.2.3.0; published 2024-05-30; CVE-2024-5597 NVD Primary 9.8; read 2026-11-26. — NVD
  • CVE record: PUBLISHED by CISA ICS 2024-05-30, title Fuji Electric Monitouch V-SFT Stack-Based Buffer Overflow; affected less than 6.2.3.0; CVSS v3.1 7.8, v4 8.5; credit kimiya working with Trend Micro Zero Day Initiative. — CVE.org
  • ICSA-24-151-02 (2024-05-30, Update A 2024-06-04, CWE revision 2025-07-18): V-SFT < 6.2.3.0; CVE-2024-5271 and CVE-2024-5597 CWE-843, CVE-2024-34171 CWE-121; Critical Manufacturing, Energy; HQ Japan; fix V-SFT 6.2.3.0; not exploitable remotely; no known public exploitation reported. — CISA ICS advisory
  • Fuji Electric product page: Monitouch V-SFT Configuration Software offers screen configuration tools for HMI displays; compatible with all Fuji Electric HMIs; read 2026-11-26. — Fuji Electric
  • Not in the KEV catalog, version 2026.11.25, checked 2026-11-26. — CISA KEV
  • EPSS 0.00788, percentile 0.52731, dataset 2026-11-25. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CVE.org record CVE-2024-34171 (CNA: CISA ICS)
  3. CISA ICS advisory ICSA-24-151-02
  4. CISA CSAF file ICSA-24-151-02
  5. Fuji Electric Corp. of America: V-SFT Configuration Software
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which Monitouch V-SFT versions are affected by CVE-2024-34171?

All versions before 6.2.3.0 (per CISA ICSA-24-151-02, the CVE record and NVD's CPE).

Can CVE-2024-34171 be exploited over the network?

CISA says the vulnerabilities in its advisory are not exploitable remotely and scores this one with a local vector that needs user interaction (7.8). NVD's own score of 9.8 uses a network vector (per CISA ICSA-24-151-02 and NVD).

How do I fix CVE-2024-34171?

Update Monitouch V-SFT to version 6.2.3.0, which CISA links in Fuji Electric's technical document library, and keep engineering workstations off the internet and away from business networks (per CISA ICSA-24-151-02).

Is CVE-2024-34171 in the CISA KEV catalog?

No. It is absent from KEV catalog version 2026.11.25 as of 2026-11-26, and FIRST EPSS gives 0.00788 (52.73rd percentile) in the 2026-11-25 dataset (per CISA KEV and FIRST EPSS).