CVE-2023-1133 is a deserialization flaw in Delta Electronics InfraSuite Device Master before version 1.0.5. Its Device-status service listens on UDP port 10100 by default and deserializes whatever packets arrive, so an attacker with no login can run code on the server. NVD and CISA score it 9.8; Delta's fix is a reinstall of version 1.0.5.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
50.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-1133 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Delta Electronics InfraSuite Device Master | cpe:2.3:a:deltaww:infrasuite_device_master:*:*:*:*:*:*:*:* | versions prior to 1.0.5; fixed by uninstalling and reinstalling 1.0.5 (CISA ICSA-23-080-02, NVD before 1.0.5); later advisory ICSA-23-331-01 names 1.0.10 for flaws in 1.0.7 |
What does this mean for affected devices?
NVD carries the CISA description: InfraSuite Device Master versions prior to 1.0.5 "contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), the same as CISA's. NVD assigns CWE-502; the CVE record names none. NVD's CPE covers all versions before 1.0.5 (NVD, CVE record).
What does CISA's advisory cover?
CISA's ICSA-23-080-02 of 2023-03-29 lists 13 flaws in InfraSuite Device Master versions prior to 1.0.5, numbered CVE-2023-1133 to CVE-2023-1145, reported by Piotr Bazydlo of Trend Micro and an anonymous researcher through Trend Micro's Zero Day Initiative. Besides this one they include pre-authentication deserialization in the Device-gateway and Device-DataCollect services (CVE-2023-1139 and CVE-2023-1145), token forgery that bypasses authentication (CVE-2023-1136, 9.8), command injection and path traversal. Delta's fix is to uninstall the old version and reinstall version 1.0.5 with the installer, which CISA links from Delta's UPS software download area. CISA reported no known public exploits targeting these flaws when it published.
How likely is exploitation?
FIRST EPSS gives CVE-2023-1133 0.50050, the 98.9th percentile, in the 2026-11-22 dataset (FIRST EPSS). It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries, CISA KEV). NVD's reference list also includes a Packet Storm entry for this deserialization flaw. A single UDP port with no authentication is easy to probe, so block UDP 10100 at the network boundary and allow it only from hosts that need the Device-status service.
What should operators do?
Reinstall a fixed version and restrict which networks can reach the server's service ports. Version 1.0.5 is not the end of the story: CISA's later advisories found CVE-2023-47207 in 1.0.7, fixed in 1.0.10, so install the newest release Delta offers. The Delta Electronics guide lists the InfraSuite advisories in order with their fixed versions. Related: CVE-2023-1140, the unauthenticated administrator code execution in the same release, and CVE-2023-1437, untrusted RPC input in Advantech WebAccess/SCADA.
Evidence
- NVD (read 2026-11-23): status Modified; published 2023-03-27; NVD Primary CVSS v3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, ICS-CERT Secondary 9.8; CWE-502 (NVD Primary); CPE deltaww infrasuite_device_master before 1.0.5; references CISA ICSA-23-080-02 and Packet Storm file 172799. — NVD
- CISA ICSA-23-080-02 CSAF (released 2023-03-29), read 2026-11-23: InfraSuite Device Master versions prior to 1.0.5; 13 CVEs CVE-2023-1133 to CVE-2023-1145; CVE-2023-1133 CWE-502 9.8 Device-status service UDP 10100; CVE-2023-1140 CWE-306 9.8 unauthenticated RCE as administrator; CVE-2023-1139 and CVE-2023-1145 deserialization in Device-gateway and Device-DataCollect; remediation uninstall old versions and reinstall 1.0.5; no known public exploits; reported by Piotr Bazydlo (Trend Micro) and an anonymous researcher via Trend Micro ZDI. — CISA ICSA-23-080-02
- CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT (icscert), published 2023-03-27, CNA CVSS v3.1 9.8, no CWE in the CNA record, affected versions before 1.0.5. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.50050, percentile 0.98932, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
How do I fix CVE-2023-1133?
Uninstall the old InfraSuite Device Master and reinstall version 1.0.5 or later with the installer (CISA ICSA-23-080-02). CISA's later ICSA-23-331-01 recommends 1.0.10 or later for flaws found in 1.0.7, so use the newest release.
Which port does CVE-2023-1133 use?
UDP port 10100, where the Device-status service listens by default (CISA ICSA-23-080-02 and the CVE record). The service deserializes packets without verifying them.
Does the attacker need credentials?
No. NVD and CISA score it with no privileges and no user interaction; CISA describes the attacker as unauthenticated.
Is CVE-2023-1133 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.50050 (98.9th percentile) in the 2026-11-22 dataset.