CVE-2022-35870 is a Java deserialization flaw in the com.inductiveautomation.metro.impl code of Inductive Automation Ignition, shown at Pwn2Own Miami 2022. ZDI says authentication is required but the existing mechanism can be bypassed, and the code then runs as SYSTEM on the Gateway host. NVD scores it 7.8 and ZDI 8.8. Ignition 8.1.17 and 7.9.20 carry the vendor fix.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
44.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-35870 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Inductive Automation Ignition Gateway | cpe:2.3:a:inductiveautomation:ignition:8.1.15:*:*:*:*:*:*:* | 8.1.15 (b2022030114) per NVD and ZDI; fixed in 8.1.17 and 7.9.20 (Inductive Automation release notes, "Fixed vulnerabilities disclosed at Pwn2Own") |
What does this mean for affected devices?
NVD's Primary score is CVSS v3.1 7.8 (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). ZDI, the CNA, scores it CVSS v3.0 8.8 (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), a network attack with low privileges. That rating fits ZDI's own text better than NVD's local, user-interaction vector. NVD and ZDI both give the weakness as CWE-502 (deserialization of untrusted data). The record was published on 2022-07-25 (NVD, CVE record).
What does ZDI say about it?
ZDI-22-1017 (ZDI-CAN-17265) is tagged Pwn2Own and credited to @_s_n_t of @pentestltd. The flaw "exists within com.inductiveautomation.metro.impl", where user-supplied data is not validated before deserialization. "Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed", and the attacker can "execute code in the context of SYSTEM". It was reported to the vendor on 2022-05-09 and published on 2022-07-15. The same entrant's authentication bypass in the Gateway web pages is CVE-2022-35869.
Which Ignition versions are affected and fixed?
NVD and ZDI name Ignition 8.1.15 (build b2022030114), and NVD's CPE configuration lists only that version, so a CPE match misses other releases. The 8.1.17 release notes and 7.9.20 release notes, both released May 12, 2022, list "Fixed vulnerabilities disclosed at Pwn2Own" without naming CVEs. Run 8.1.17 or later on the 8.1 line, or 7.9.20 or later on 7.9, and keep the Gateway's web and client ports reachable only from the engineering and HMI hosts that need them.
An older Gateway deserialization flaw is CVE-2020-12000. The Ignition vulnerabilities guide lists all five Pwn2Own 2022 CVEs, and the input handling fix guide covers safe deserialization.
CVE-2022-35870 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.44285, the 98.8th percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-24): status Modified; published 2022-07-25; NVD Primary CVSS v3.1 7.8 CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H; ZDI Secondary CVSS v3.0 8.8 CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; CWE-502 (NVD and ZDI); CPE cpe:2.3:a:inductiveautomation:ignition:8.1.15:*:*:*:*:*:*:* only. — NVD
- ZDI-22-1017 (ZDI-CAN-17265, Pwn2Own, read 2026-11-24): flaw in com.inductiveautomation.metro.impl; authentication required but bypassable; code runs as SYSTEM; reported 2022-05-09, published 2022-07-15; credit @_s_n_t of @pentestltd; vendor has issued an update. — Zero Day Initiative
- Ignition 8.1.17 release notes (released May 12, 2022, read 2026-11-24): "Fixed vulnerabilities disclosed at Pwn2Own"; no CVE ids named. — Inductive Automation
- Ignition 7.9.20 release notes (released May 12, 2022, read 2026-11-24): "Fixed vulnerabilities disclosed at Pwn2Own"; no CVE ids named. — Inductive Automation
- CVE record (checked 2026-11-24): state PUBLISHED, CNA ZDI, published 2022-07-25, affected Ignition 8.1.15 (b2022030114), CNA CVSS v3.0 8.8, CWE-502. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24; the catalog has no Inductive Automation entry. — CISA KEV
- EPSS 0.44285, percentile 0.9879, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Ignition version fixes CVE-2022-35870?
Inductive Automation's 8.1.17 and 7.9.20 release notes, both dated May 12, 2022, list "Fixed vulnerabilities disclosed at Pwn2Own". NVD and ZDI name 8.1.15 as the affected build, so treat any earlier 8.1 or 7.9 release as exposed and run 8.1.17 or 7.9.20 or later.
Does CVE-2022-35870 need a login?
ZDI says authentication is required but the existing authentication mechanism can be bypassed, so in practice an unauthenticated attacker who reaches the Gateway can use it. Code then runs as SYSTEM.
Why do NVD and ZDI score CVE-2022-35870 differently?
NVD's Primary CVSS v3.1 score is 7.8 with a local attack vector and user interaction. ZDI, the CNA, scores it CVSS v3.0 8.8 as a network attack needing low privileges and no user interaction, which matches its description of a remote flaw with a bypassable login.
Is CVE-2022-35870 actively exploited?
It is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23). FIRST EPSS rates it 0.44285, the 98.8th percentile, in the 2026-11-23 dataset, which is high for an ICS product.