Security Advisory

CVE-2022-26335: SCALANCE X-300 HTTP GET URI Crash

Last updated:
  • CVE-2022-26335

CVE-2022-26335 is a buffer overflow in the web server of Siemens SCALANCE X-300, X408 and XR-300 switches: a crafted URI in an HTTP GET request crashes the switch, and no login is needed. NVD scores it 7.5 as a denial of service; Siemens scores it 9.6. All 75 affected product entries are fixed in firmware V4.1.4.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-26335 · Source: NVD

Affected components

ComponentCPEVersion range
SCALANCE X302-7 EEC, X304-2FE, X306-1LD FE, X307-2 EEC, X307-3, X307-3LD, X308-2 (incl. LD, LH, LH+, M, M PoE, M TS), X310, X310FE, X320-1 FE, X320-1-2LD FEcpe:2.3:o:siemens:scalance_x308-2_firmware:*:*:*:*:*:*:*:*All versions before V4.1.4; fixed in V4.1.4 (Siemens SSA-836527)
SCALANCE X408-2cpe:2.3:o:siemens:scalance_x408-2_firmware:*:*:*:*:*:*:*:*All versions before V4.1.4; fixed in V4.1.4 (Siemens SSA-836527)
SCALANCE XR324-12M, XR324-12M TS, XR324-4M EEC, XR324-4M PoE, XR324-4M PoE TScpe:2.3:o:siemens:scalance_xr324-4m_eec_firmware:*:*:*:*:*:*:*:*All versions before V4.1.4; fixed in V4.1.4 (Siemens SSA-836527)
SIPLUS NET SCALANCE X308-2cpe:2.3:o:siemens:siplus_net_scalance_x308-2_firmware:*:*:*:*:*:*:*:*All versions before V4.1.4; fixed in V4.1.4 (Siemens SSA-836527)

What does this mean for affected devices?

NVD carries the Siemens description for the SCALANCE X-300 family: affected devices "do not properly validate the URI of incoming HTTP GET requests. This could allow an unauthenticated remote attacker to crash affected devices." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), and NVD and the Siemens CNA both class it CWE-120 (classic buffer overflow). The record was published on 2022-04-12 (NVD, CVE record).

How severe is it, and why do the scores differ?

Siemens ProductCERT scores CVE-2022-26335 at CVSS v3.1 9.6 (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C) in SSA-836527, and CISA's ICSA-22-104-09 CSAF (version 2, 2025-05-06) uses the same vector. The two scorers disagree on reach and impact. NVD takes the description at its word, a remote crash, and scores availability only. Siemens restricts the attack to the adjacent network but rates confidentiality, integrity and availability high with a changed scope, and its advisory summary says the heap and buffer overflows in this set could "potentially impact the system by other means". No privileges and no user interaction are needed in either vector.

CVE-2022-26335 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01386, the 72.9th percentile, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).

Which switches are affected?

SSA-836527 lists 75 product entries, all fixed in firmware V4.1.4:

Group (Siemens wording) Affected Fixed
SCALANCE X302-7 EEC, X307-2 EEC (all power and coated variants) before V4.1.4 V4.1.4
SCALANCE X304-2FE, X306-1LD FE, X307-3, X307-3LD, X308-2, X308-2LD, X308-2LH, X308-2LH+, X308-2M, X308-2M PoE, X308-2M TS, X310, X310FE, X320-1 FE, X320-1-2LD FE before V4.1.4 V4.1.4
SCALANCE X408-2 before V4.1.4 V4.1.4
SCALANCE XR324-12M, XR324-12M TS, XR324-4M EEC, XR324-4M PoE, XR324-4M PoE TS (front and rear port variants) before V4.1.4 V4.1.4
SIPLUS NET SCALANCE X308-2 before V4.1.4 V4.1.4

The same advisory covers eight other X-300 flaws fixed by the same release, among them CVE-2022-26334 (another HTTP GET parameter overflow), CVE-2022-25752 (predictable session IDs) and CVE-2022-26380 (SNMP out-of-bounds read). NVD's 24 CPE entries end before 4.1.4, except the X308-2M PoE entry, which has no upper version (Siemens SSA-836527 CSAF).

How do you fix or mitigate it?

Update every X-300, X408 and XR-300 switch on the list to V4.1.4 or later. Where that has to wait, Siemens gives three workarounds: restrict access to the affected systems, especially to ports 22/tcp, 161/udp and 443/tcp, to trusted IP addresses only; disable the SNMP service if possible; and deactivate the web server if it is not required and the product supports deactivation. A crash interrupts the traffic the switch carries, so put the management interfaces on a separate VLAN that only engineering hosts can reach. Our SCALANCE and RUGGEDCOM guide covers the web management attack surface, and the memory corruption fix guide explains the class. Other web server flaws in SCALANCE X switches include CVE-2021-25668 and CVE-2021-25669 (X-200 heap and stack overflows) and CVE-2019-13933; the X-300 family also carries CVE-2020-28395 (reused private key).

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • NVD (read 2026-11-22): status Modified; published 2022-04-12; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 7.8; CWE-120 (NVD and Siemens); 24 vulnerable CPE entries before 4.1.4, except scalance_x308-2m_poe_firmware without version limit; reference SSA-836527. — NVD
  • Siemens SSA-836527 CSAF version 1 (2022-04-12), read 2026-11-22: CVE-2022-26335 CWE-120, CVSS v3.1 9.6 CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C; 75 known-affected entries, all fixed in V4.1.4; workarounds: restrict access especially to 22/tcp, 161/udp and 443/tcp to trusted IP addresses, disable SNMP if possible, deactivate the webserver if not required and supported; advisory also covers CVE-2022-25751 to CVE-2022-25756, CVE-2022-26334 and CVE-2022-26380; summary says the heap and buffer overflows could potentially impact the system by other means. — Siemens ProductCERT SSA-836527 (CSAF)
  • CISA ICSA-22-104-09 CSAF version 2 (initial 2022-04-12, current 2025-05-06), read 2026-11-22: Siemens SCALANCE X-300 Switches; CVE-2022-26335 CWE-120, CVSS v3.1 9.6. — CISA CSAF ICSA-22-104-09
  • CVE record (checked 2026-11-22): state PUBLISHED, CNA Siemens, published 2022-04-12; CWE-120; 75 affected entries. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-22. — CISA KEV
  • EPSS 0.01386, percentile 0.72916, dataset 2026-11-21, read 2026-11-22. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-836527: Multiple Vulnerabilities in SCALANCE X-300 Switch Family Devices
  3. Siemens ProductCERT SSA-836527 (CSAF)
  4. CISA CSAF: ICSA-22-104-09 Siemens SCALANCE X-300 Switches (machine-readable advisory)
  5. CVE.org record CVE-2022-26335 (CNA: Siemens)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2022-26335?

Firmware V4.1.4 for all 75 affected SCALANCE X-300, X408, XR-300 and SIPLUS NET X308-2 entries, per Siemens SSA-836527. The same release fixes the eight other X-300 flaws in that advisory.

Does an attacker need credentials?

No. Both NVD and Siemens describe an unauthenticated attacker, and both vectors need no privileges and no user interaction. Siemens limits the attack vector to the adjacent network; NVD scores it as reachable over the network.

Why does Siemens score 9.6 when NVD scores 7.5?

NVD scores the crash described in the record, availability only (7.5). Siemens rates confidentiality, integrity and availability high with a changed scope (9.6), and its advisory summary says the overflows in this set could potentially impact the system by other means.

What can I do if I cannot update now?

Siemens recommends restricting access, especially to ports 22/tcp, 161/udp and 443/tcp, to trusted IP addresses; disabling SNMP if possible; and deactivating the web server if it is not required and the product supports it (per SSA-836527).