Security Advisory

CVE-2022-1704: Ignition Backup Restore XXE

Last updated:
  • CVE-2022-1704

CVE-2022-1704 is an XML external entity (XXE) flaw in the backup and restore function of Inductive Automation Ignition. The software parses XML in a restored backup without XML security flags, so a crafted backup can expose file contents. NVD scores it 9.8 and CISA 7.6. CISA names Ignition 8.1.9 and 7.9.21 as the fixed versions.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-1704 · Source: NVD

Affected components

ComponentCPEVersion range
Inductive Automation Ignition 7.9cpe:2.3:a:inductiveautomation:ignition:*:*:*:*:*:*:*:*7.9 before 7.9.21; fixed in 7.9.21 (CISA ICSA-22-207-01, NVD 7.9.0 to before 7.9.21)
Inductive Automation Ignition 8.1cpe:2.3:a:inductiveautomation:ignition:*:*:*:*:*:*:*:*8.1 before 8.1.8 (CISA, NVD); CISA names 8.1.9 or later as the fix

What does this mean for affected devices?

NVD carries the CISA description: "Due to an XML external entity reference, the software parses XML in the backup/restore functionality without XML security flags, which may lead to a XXE attack while restoring the backup." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). CISA, the CNA, scores it CVSS v3.1 7.6 (AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:N/A:L), with high privileges required, and assigns CWE-611. The record was published on 2022-08-05 (NVD, CVE record).

Which versions are affected and fixed?

CISA's ICSA-22-207-01, released on 2022-07-26 and updated on 2022-08-04, lists Ignition 7.9 before 7.9.21 and 8.1 before 8.1.8, and says exploitation "could allow an attacker to obtain file contents". Its fixes are 8.1.9 or later and 7.9.21 or later. NVD's CPE ranges copy the affected list (7.9.0 to before 7.9.21, 8.1.0 to before 8.1.8), so 8.1.8 sits in a gap. The 8.1.9 release notes, dated August 7, 2021, say "Fixed multiple potential XXE and SSRF vulnerabilities", and the 7.9.21 notes, dated July 26, 2022, "Back-ported fixes from 8.1 for potential XXE and SSRF vulnerabilities". Treat 8.1.8 as affected and install 8.1.9 or later. Keval Shah reported the flaw.

What should operators do?

Upgrade, and restore only backups from a trusted source until then. CISA's vector assumes high privileges, so limiting who holds Gateway configuration rights narrows who can trigger it. The path traversal CVE-2022-1264 is the other privileged-user web configuration flaw from 2022, and CVE-2020-10644 shows the earlier unauthenticated input handling bugs. See the Ignition SCADA guide and the input handling fix guide.

CVE-2022-1704 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.01034, the 64.7th percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-24): status Modified; published 2022-08-05; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 7.6 AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:N/A:L; CWE-611 (ICS-CERT only); CPE ignition 7.9.0 to before 7.9.21 and 8.1.0 to before 8.1.8. — NVD
  • CISA ICSA-22-207-01 CSAF (released 2022-07-26, updated 2022-08-04), read 2026-11-24: Ignition >= 7.9 < 7.9.21 and >= 8.1 < 8.1.8; CWE-611; CVSS v3.0 7.6; attacker could obtain file contents; vendor fix 8.1.9 or later and 7.9.21 or later; credit Keval Shah. — CISA ICSA-22-207-01
  • Release notes: 8.1.9 Released August 7, 2021, 'Fixed multiple potential XXE and SSRF vulnerabilities'; 7.9.21 Released July 26, 2022, 'Back-ported fixes from 8.1 for potential XXE and SSRF vulnerabilities'. — Inductive Automation
  • CVE record (checked 2026-11-24): state PUBLISHED, CNA icscert, published 2022-08-05, CNA CVSS v3.1 7.6. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
  • EPSS 0.01034, percentile 0.64702, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-22-207-01 Inductive Automation Ignition (CSAF)
  3. Inductive Automation: Ignition 8.1.9 release notes
  4. Inductive Automation: Ignition 7.9.21 release notes
  5. CVE.org record CVE-2022-1704
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which Ignition versions fix CVE-2022-1704?

CISA names 8.1.9 or later and 7.9.21 or later. The 8.1.9 and 7.9.21 release notes both list XXE fixes.

Is Ignition 8.1.8 affected by CVE-2022-1704?

CISA's and NVD's affected ranges end before 8.1.8, but CISA's fix and the XXE release note are in 8.1.9. Treat 8.1.8 as affected and upgrade to 8.1.9 or later.

What can an attacker get from CVE-2022-1704?

CISA says successful exploitation could let an attacker obtain file contents, triggered when a crafted backup is restored.

Is CVE-2022-1704 in the CISA KEV catalog?

No, not as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS rates it 0.01034 (64.7th percentile) in the 2026-11-23 dataset.