CVE-2020-10644 is an unauthenticated Java deserialization flaw in how the Inductive Automation Ignition Gateway handles project diffs. It was one half of a Pwn2Own Miami 2020 exploit chain. NVD scores it 7.5, while CISA and the Zero Day Initiative score it 9.8 because it leads to code execution as SYSTEM. Ignition 8.0.10 and 7.9.14 fix it.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
20.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-10644 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Inductive Automation Ignition 7 Gateway | cpe:2.3:a:inductiveautomation:ignition_gateway:*:*:*:*:*:*:*:* | before 7.9.14; fixed in 7.9.14 (CISA ICSA-20-147-01, NVD 7.2.4.48 to before 7.9.14) |
| Inductive Automation Ignition 8 Gateway | cpe:2.3:a:inductiveautomation:ignition_gateway:*:*:*:*:*:*:*:* | before 8.0.10; fixed in 8.0.10 (CISA ICSA-20-147-01, NVD 8.0 to before 8.0.10) |
What does this mean for affected devices?
NVD's description says the product "lacks proper validation of user-supplied data, which can result in deserialization of untrusted data", letting an attacker "obtain sensitive information". NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N) and NVD CVSS v2 5.0, with CWE-502. CISA's advisory and the Zero Day Initiative both give CVSS v3.0 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The record was published on 2020-06-09 (NVD, CVE record).
How was it exploited at Pwn2Own?
ZDI-20-686, published on 2020-06-01, says the flaw "exists with the handling of project diffs" and lets an attacker "execute code in the context of SYSTEM" with no authentication. Team FLASHBACK (Pedro Ribeiro and Radek Domanski) reported it to the vendor on 2020-01-30. The same team's CVE-2020-12004, a missing authentication check on the getDiffs method, is the way in; CVE-2020-12000 is the Incite Team's separate deserialization bug in the same advisory.
Which versions are affected and fixed?
CISA's ICSA-20-147-01 (first released 2020-05-26, Update B 2020-06-30) lists the Ignition 8 Gateway before 8.0.10 and the Ignition 7 Gateway before 7.9.14, and recommends upgrading to 8.0.10 or 7.9.14. NVD's CPE ranges match, starting at 7.2.4.48 for the 7.x line. Until the upgrade, allow only the engineering hosts that need the Gateway's web ports to reach them.
The Ignition SCADA guide puts this chain beside later deserialization bugs, and the input handling fix guide covers untrusted serialized data.
CVE-2020-10644 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.20208, the 97.5th percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-24): status Modified; published 2020-06-09; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N and NVD CVSS v2 5.0; CWE-502; CPE ignition_gateway 7.2.4.48 to before 7.9.14 and 8.0 to before 8.0.10. — NVD
- CISA ICSA-20-147-01 CSAF (released 2020-05-26, Update A 2020-06-02, Update B 2020-06-30), read 2026-11-24: Ignition 8 Gateway < 8.0.10 and Ignition 7 Gateway < 7.9.14; upgrade to 8.0.10 or 7.9.14; credit Pedro Ribeiro, Radek Domanski, Chris Anastasio, Steven Seeley via Trend Micro ZDI. CVE-2020-10644: CWE-502, CVSS v3.0 9.8. — CISA ICSA-20-147-01
- ZDI-20-686 (ZDI-CAN-10276), published 2020-06-01: getDiffs deserialization of project diffs, unauthenticated, code execution as SYSTEM, CVSS 9.8; reported 2020-01-30; credit Team FLASHBACK: Pedro Ribeiro and Radek Domanski. — Zero Day Initiative
- Release notes: 8.0.10 Released March 19, 2020; 7.9.14 Released April 28, 2020. — Inductive Automation
- CVE record (checked 2026-11-24): state PUBLISHED, CNA icscert, published 2020-06-09. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
- EPSS 0.20208, percentile 0.97529, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Ignition versions fix CVE-2020-10644?
Ignition 8.0.10 for the 8.0 line and 7.9.14 for the 7.9 line, per CISA ICSA-20-147-01.
Does CVE-2020-10644 need a login?
No. ZDI-20-686 says authentication is not required and that the attacker can run code as SYSTEM.
Why is the NVD score lower than CISA's?
NVD's Primary vector rates only confidentiality impact (7.5), following the record's "obtain sensitive information" wording. CISA and ZDI rate full code execution (9.8).
Is CVE-2020-10644 in the CISA KEV catalog?
No, not as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS rates it 0.20208 (97.5th percentile) in the 2026-11-23 dataset.