CVE-2021-38406 is an out-of-bounds write in Delta Electronics DOPSoft 2, the Windows tool used to build screens for Delta DOP HMI panels. A crafted project file can run code on the engineering workstation when a user opens it. It is the only Delta CVE in CISA's KEV catalog as of 2026-11-23, and DOPSoft 2 will get no fix.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
76.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
Yes
Listed as known exploited
Published
Vulnerability ID: CVE-2021-38406 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Delta Electronics DOPSoft 2 (HMI configuration software) | cpe:2.3:a:deltaww:dopsoft:*:*:*:*:*:*:*:* | 2.00 through 2.00.07 (NVD); 2.00.07 and prior, end-of-life with no fix (CISA ICSA-21-252-02) |
What does this mean for affected devices?
NVD carries the CISA description: DOPSoft 2 version 2.00.07 and prior "lacks proper validation of user-supplied data when parsing specific project files", which "could result in multiple out-of-bounds write instances" and lets an attacker "execute code in the context of the current process". NVD's Primary score is CVSS v3.1 7.8 (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H) and its CVSS v2 score is 6.8; CISA, the CNA, also scores 7.8 and maps the flaw to CWE-787. NVD's CPE covers DOPSoft 2.00 through 2.00.07 (NVD, CVE record).
What does CISA say about DOPSoft 2?
CISA's ICSA-21-252-02 of 2021-09-09 covers three file-parsing flaws in DOPSoft 2: this out-of-bounds write, the heap-based overflow CVE-2021-38404 and the stack-based overflow CVE-2021-38402, all scored 7.8. CISA notes the flaws are not exploitable remotely; the attack needs a user to open a malicious project file. DOPSoft 2 "will not receive an update" because it is end-of-life. Delta recommends moving HMI devices to the DOP-100 family and the software to DIAScreen in DIAStudio v1.1.2 or later.
Why is it in the KEV catalog?
CISA added CVE-2021-38406 to the KEV catalog on 2022-08-25 with a due date of 2022-09-15. The required action is that "the impacted product is end-of-life and should be disconnected if still in use"; known ransomware use is marked Unknown. KEV names it an improper input validation flaw that results in the out-of-bounds write. FIRST EPSS gives it 0.76428, the 99.5th percentile, in the 2026-11-22 dataset (FIRST EPSS).
What should operators do?
Find every laptop that still has DOPSoft 2 installed, migrate the panel projects to DIAScreen and remove DOPSoft 2. Until then, open only project files from a known source, and keep the workstation off the internet and away from email. The Delta Electronics guide lists the later DOPSoft and DIAScreen file-parsing CVEs, and the memory corruption fix guide explains this class of bug. Similar engineering-file attacks: CVE-2022-45788 in Modicon project files and CVE-2019-10996 in Red Lion Crimson.
Evidence
- NVD (read 2026-11-23): status Analyzed; published 2021-09-17; NVD Primary CVSS v3.1 7.8 AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H and CVSS v2 6.8 AV:N/AC:M/Au:N/C:P/I:P/A:P; ICS-CERT Secondary 7.8; CWE-787 (ICS-CERT); CPE deltaww dopsoft 2.00 to 2.00.07 inclusive. — NVD
- CISA ICSA-21-252-02 CSAF (released 2021-09-09), read 2026-11-23: DOPSoft 2 version 2.00.07 and prior; CVE-2021-38402 (CWE-121), CVE-2021-38406 (CWE-787), CVE-2021-38404 (CWE-122), each CVSS v3 7.8; not exploitable remotely; end-of-life, no update; switch HMI to DOP-100 family and software to DIAScreen in DIAStudio v1.1.2 or later. — CISA ICSA-21-252-02
- CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT (icscert), published 2021-09-17, CNA CVSS v3.1 7.8, CWE-787. — CVE.org
- In the CISA KEV catalog (catalog version 2026.11.20, 1,790 entries, checked 2026-11-23): dateAdded 2022-08-25, dueDate 2022-09-15, required action 'The impacted product is end-of-life and should be disconnected if still in use.', knownRansomwareCampaignUse Unknown. — CISA KEV
- EPSS 0.76428, percentile 0.99549, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Is there a patch for CVE-2021-38406?
No. CISA's ICSA-21-252-02 says DOPSoft 2 is end-of-life and will not receive an update. Delta recommends moving HMI devices to the DOP-100 family and the software to DIAScreen in DIAStudio v1.1.2 or later.
What does CISA KEV require for CVE-2021-38406?
CISA added it on 2022-08-25 with a due date of 2022-09-15 and the action that the end-of-life product should be disconnected if still in use. Ransomware use is marked Unknown (catalog version 2026.11.20, checked 2026-11-23).
Can it be exploited over the network?
Not directly. CISA says the DOPSoft 2 flaws are not exploitable remotely; an attacker has to get a user to open a crafted project file, for example one sent by email or copied from a shared drive.
Does it affect the DOP HMI panel itself?
The advisories name the DOPSoft 2 software on the engineering workstation, not panel firmware. The code runs on the PC where the project is opened, which is often the PC that later downloads projects to panels.
Questions about this page?