CVE-2021-34570 is an input validation flaw (CWE-20) in Phoenix Contact PLCnext Control firmware before 2021.0.5 LTS: a device on the same network that sends a crafted JSON request to the /auth/access-token endpoint makes the controller restart, and a script can repeat it to hold the PLC down. It is fixed in firmware 2021.0.5 LTS. NVD scores it 7.5.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
1.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-34570 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Phoenix Contact AXC F 1152 (1151412), AXC F 2152 (2404267), AXC F 3152 (1069208) | cpe:2.3:o:phoenixcontact:axc_f_2152_firmware:*:*:*:*:lts:*:*:* | firmware before 2021.0.5 LTS (NVD, CERT@VDE VDE-2021-029); fixed in 2021.0.5 LTS |
| Phoenix Contact RFC 4072S (1051328) | cpe:2.3:o:phoenixcontact:rfc_4072s_firmware:*:*:*:*:lts:*:*:* | firmware before 2021.0.5 LTS (NVD, VDE-2021-029); fixed in 2021.0.5 LTS |
| Phoenix Contact AXC F 2152 Starterkit (1046568) and PLCnext Technology Starterkit (1188165) | cpe:2.3:o:phoenixcontact:axc_f_2152_starterkit_firmware:*:*:*:*:lts:*:*:* | firmware before 2021.0.5 LTS (NVD, VDE-2021-029); fixed in 2021.0.5 LTS |
What does this mean for affected devices?
NVD's description: "Multiple Phoenix Contact PLCnext control devices in versions prior to 2021.0.5 LTS are prone to a DoS attack through special crafted JSON requests." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same as CERT@VDE's as CNA, which assigns CWE-20 (improper input validation). NVD's CPEs cover the AXC F 1152, 2152 and 3152, the RFC 4072S and both starter kits with LTS firmware before 2021.0.5, and the record was published on 2021-09-27 (NVD).
How does the JSON request crash the controller?
CERT@VDE VDE-2021-029, released on 4 August 2021: "A device on the same network as the controller sending a special crafted JSON request to the /auth/access-token endpoint may cause the controller to restart." The endpoint is the one that issues login tokens, so it answers before any authentication, and the advisory notes that "an attacker could potentially script this request and create a denial of service attack condition". A restarting PLC stops its control program each time. Oliver Carrigan of Dionach discovered it (CERT@VDE CSAF).
Update A of the advisory, dated 9 November 2021, says the score was raised from 7.7 to 9.1 under CVSS 3.0 with an integrity impact added. The vulnerability entry in the same CSAF document, and the CERT@VDE record on NVD, still carry 7.5 with availability impact only; this page uses NVD's Primary 7.5.
Which firmware fixes CVE-2021-34570?
Phoenix Contact's remedy is firmware 2021.0.5 LTS or higher for the AXC F 1152 (1151412), AXC F 2152 (2404267), AXC F 3152 (1069208), RFC 4072S (1051328), AXC F 2152 Starterkit (1046568) and PLCnext Technology Starterkit (1188165). Firmware 2021.0 LTS, which fixed the root shell flaw CVE-2020-12519, is still affected by this one. Until the update, Phoenix Contact recommends closed networks or a suitable firewall, which here means only engineering and HMI hosts reach the controller's web interface. The classic line has a comparable network denial of service with no fix, CVE-2021-33541, alongside CVE-2019-9201. Our Phoenix Contact PLCnext and classic line security guide lists current PLCnext firmware fixes.
Is CVE-2021-34570 exploited?
CVE-2021-34570 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.00978, the 63rd percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: PLCnext control devices prior to 2021.0.5 LTS prone to DoS through crafted JSON requests; NVD Primary and CERT@VDE CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-20 (CERT@VDE); LTS firmware before 2021.0.5 on AXC F 1152/2152/3152, RFC 4072S, AXC F 2152 Starterkit, PLCnext Technology Starterkit; published 2021-09-27. — NVD
- VDE-2021-029 CSAF: initial 2021-08-04, Update A 2021-11-09; crafted JSON request to /auth/access-token may cause restart; attacker could script it for DoS; Update A note: score raised from 7.7 to 9.1 (CVSS 3.0); vulnerability score 7.5; fixed in 2021.0.5 LTS for article numbers 1151412, 2404267, 1069208, 1051328, 1046568, 1188165; discovered by Oliver Carrigan (Dionach). — CERT@VDE VDE-2021-029 (CSAF)
- Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18; the catalog has no Phoenix Contact entry. — CISA KEV
- EPSS 0.00978, percentile 0.62759, dataset 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which PLCnext firmware fixes CVE-2021-34570?
Firmware 2021.0.5 LTS or later for the AXC F 1152, AXC F 2152, AXC F 3152, RFC 4072S, AXC F 2152 Starterkit and PLCnext Technology Starterkit. Firmware 2021.0 LTS is still affected (per CERT@VDE VDE-2021-029 and NVD).
Does an attacker need credentials to exploit CVE-2021-34570?
No. The crafted request goes to /auth/access-token, the endpoint that issues login tokens, from any device on the same network, and the CVSS vector requires no privileges. Repeating the request can keep the controller restarting (per VDE-2021-029 and NVD).
Why does the advisory mention a score of 9.1?
Update A of VDE-2021-029 (9 November 2021) says the score was raised from 7.7 to 9.1 under CVSS 3.0. The vulnerability entry in the CSAF and the CERT@VDE record on NVD carry 7.5, and NVD's own Primary score is 7.5 (per VDE-2021-029 and NVD).
Is CVE-2021-34570 in the CISA KEV catalog?
No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.00978, the 63rd percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?