Security Advisory

CVE-2021-33541: Phoenix ILC 1x0/1x1 Network DoS

Last updated:
  • CVE-2021-33541

CVE-2021-33541 is a denial-of-service flaw (CWE-770) in Phoenix Contact ILC 1x0 and ILC 1x1 classic line controllers: an unauthenticated remote attacker sends crafted IP packets and the PLC's network module stops all communication until someone restarts it, while the control program keeps running. All versions are affected and there is no firmware fix. NVD scores it 7.5.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-33541 · Source: NVD

Affected components

ComponentCPEVersion range
Phoenix Contact ILC 1x0 classic line controllerscpe:2.3:o:phoenixcontact:ilc1x0_firmware:*:*:*:*:*:*:*:*all versions and variants (NVD, CERT@VDE VDE-2021-019); no fix, mitigations only
Phoenix Contact ILC 1x1 classic line controllerscpe:2.3:o:phoenixcontact:ilc1x1_firmware:*:*:*:*:*:*:*:*all versions and variants (NVD, CERT@VDE VDE-2021-019); no fix, mitigations only

What does this mean for affected devices?

NVD's description: "Phoenix Contact Classic Line Controllers ILC1x0 and ILC1x1 in all versions/variants are affected by a Denial-of-Service vulnerability. The communication protocols and device access do not feature authentication measures. Remote attackers can use specially crafted IP packets to cause a denial of service on the PLC's network communication module." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same as CERT@VDE's as CNA, which assigns CWE-770 (allocation of resources without limits or throttling). NVD's CPEs cover all ILC1x0 and ILC1x1 firmware, and the record was published on 2021-06-25 (NVD).

What happens to the controller during an attack?

Per CERT@VDE VDE-2021-019, released on 23 June 2021: "A successful attack stops all network communication. To restore the network connectivity the device needs to be restarted. The automation task is not affected." The program keeps running on its local I/O, but the controller drops off the network: no HMI values, no engineering access, no Ethernet-based fieldbus traffic, and no remote way to recover. Someone has to power-cycle it on site. The Industrial Control Security Laboratory of Qi An Xin Technology Group found and reported it (CERT@VDE CSAF).

The same ILC families carry the unauthenticated port 1962 protocol, CVE-2019-9201, and accept unsigned logic, CVE-2022-31800. PLCnext Control had its own network denial of service, CVE-2021-34570, which did get a firmware fix.

How do you mitigate CVE-2021-33541?

There is no fixed firmware. Phoenix Contact recommends operating the controllers in closed networks or protected by a suitable firewall, and refers to its application note on measures to protect network-capable devices with an Ethernet connection. In practice that means a cell firewall that admits only the HMI and engineering hosts that need the PLC, no route from the office network, and a plan for an on-site restart. Our Phoenix Contact PLCnext and classic line security guide covers zone design for the classic line and when to migrate to PLCnext. CVE-2020-12519 shows the PLCnext side of the same vendor's fixes.

Is CVE-2021-33541 exploited?

CVE-2021-33541 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01493, the 75th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Resource exhaustion. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.

Evidence

  • NVD: ILC1x0 and ILC1x1 all versions/variants, crafted IP packets cause DoS on the network communication module, all network communication stops, restart needed, automation task not affected; NVD Primary and CERT@VDE CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-770 (CERT@VDE); published 2021-06-25. — NVD
  • VDE-2021-019 CSAF (2021-06-23): firmware all versions on ILC1x0 and ILC1x1 affected; CWE-770; CVSS 7.5; mitigation closed networks or suitable firewall, application note; discovered and reported by the Industrial Control Security Laboratory of Qi An Xin Technology Group. — CERT@VDE VDE-2021-019 (CSAF)
  • Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18; the catalog has no Phoenix Contact entry. — CISA KEV
  • EPSS 0.01493, percentile 0.74595, dataset 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CERT@VDE VDE-2021-019: Phoenix Contact security advisory for ILC1x1 industrial controllers
  3. CERT@VDE CSAF: VDE-2021-019 (machine-readable advisory)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Does CVE-2021-33541 stop the PLC program?

No. Per Phoenix Contact, a successful attack stops all network communication on the ILC 1x0 or ILC 1x1, but the automation task is not affected. Network connectivity only returns after the device is restarted (per CERT@VDE VDE-2021-019).

Is there a firmware fix for CVE-2021-33541?

No. CERT@VDE lists all firmware versions of ILC 1x0 and ILC 1x1 as affected and gives only mitigations: operate the controllers in closed networks or behind a suitable firewall (per VDE-2021-019 and NVD).

Does the attacker need a login?

No. Phoenix Contact states that the communication protocols and device access of these controllers do not feature authentication, and the CVSS vector requires no privileges and no user interaction (per VDE-2021-019 and NVD).

Is CVE-2021-33541 in the CISA KEV catalog?

No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.01493, the 75th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).