CVE-2021-32986 is an authorization flaw in AutomationDirect CLICK PLC C0-1x CPU modules with firmware before v3.00: once an authorized user unlocks the PLC, the unlocked state never times out. If the programming software is interrupted, later programming connections are accepted without a password until a power cycle. NVD and CISA score it 9.8; firmware v3.00 fixes it.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-32986 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| AutomationDirect CLICK PLC C0-1x CPU modules (20 part numbers, C0-10 to C0-12) | cpe:2.3:o:automationdirect:c0-10dd1e-d_firmware:*:*:*:*:*:*:*:* | Firmware before v3.00 (CISA ICSA-21-166-02, NVD CPE, CVE record); fix: firmware and CLICK programming software v3.00 or later |
What does this mean for affected devices?
The CVE record from CISA says that after a CLICK PLC CPU module with firmware before v3.00 "is unlocked by an authorized user, the unlocked state does not timeout." If the programming software is interrupted, the PLC stays unlocked and "all subsequent programming connections are allowed without authorization"; only a power cycle or a clean disconnect of the programming software locks it again. NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-863, incorrect authorization; CISA, the CNA, also scores it 9.8 but maps it to CWE-288, authentication bypass using an alternate path or channel. NVD published the record on 2022-04-04, ten months after CISA's advisory (NVD, CVE record).
Which CLICK PLC modules are affected?
CISA's ICSA-21-166-02, released on 2021-06-15, covers CLICK PLC CPU modules, C0-1x CPUs, on all firmware before v3.00. NVD's configuration lists 20 CPU part numbers: C0-10DD1E-D, C0-10DD2E-D, C0-10DRE-D, C0-10ARE-D, C0-11DD1E-D, C0-11DD2E-D, C0-11DRE-D, C0-11ARE-D, C0-12DD1E-D, C0-12DD2E-D, C0-12DRE-D, C0-12ARE-D, C0-12DD1E-1-D, C0-12DD2E-1-D, C0-12DRE-1-D, C0-12ARE-1-D, C0-12DD1E-2-D, C0-12DD2E-2-D, C0-12DRE-2-D and C0-12ARE-2-D, each with firmware below 3.00. CISA lists the sectors as Commercial Facilities, Critical Manufacturing and Information Technology, deployed worldwide; AutomationDirect is headquartered in the United States.
What else is in the same advisory?
ICSA-21-166-02 groups five CVEs that together weaken the CLICK password lock:
- CVE-2021-32980 (9.8): the firmware accepts an extra programming connection while one is already active;
- CVE-2021-32984 (9.8): every programming connection gets the same unlocked privileges, so while the PLC is unlocked another client can read the project;
- CVE-2021-32982 (7.5): passwords cross the network in plaintext during unlock and project transfer;
- CVE-2021-32978 (7.5): the programming protocol lets the previously entered password and lock state be read back.
CISA's risk summary is that an attacker could log in as a current or previous authenticated user or discover passwords of valid users. Irfan Ahmed and Adeen Ayub (Virginia Commonwealth University) and Hyunguk Yoo (University of New Orleans) reported the flaws to AutomationDirect (CISA advisory page).
How do you fix CVE-2021-32986?
AutomationDirect reports that all five vulnerabilities are mitigated by version 3.00 and recommends updating both the CLICK programming software and the PLC firmware to the latest version. It also points users to its security guidelines, Appendix A of the CLICK PLC Hardware User Manual, which recommends defence in depth: control networks behind firewalls, isolated from business networks, with VPNs for remote access and no direct internet exposure. Until a unit is updated:
- keep the PLC's programming port reachable only from the engineering workstation's network segment;
- power-cycle the PLC after a programming session that ended abnormally, since that relocks it;
- treat the CLICK password as exposed if it was ever used over a shared network, and change it after the update.
For how vendors tie privileges to a session and expire it, see the authentication bypass fix guide; for small plants running compact PLCs, the OT security guide for small manufacturers covers segmentation on a budget. Similar controller lock weaknesses appear in CVE-2018-7842 (Modicon UMAS session brute force) and CVE-2019-9013 (CODESYS V3 credentials in transit).
Is CVE-2021-32986 exploited?
CVE-2021-32986 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01113, the 65.64th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting these vulnerabilities at publication.


Evidence
- NVD (read 2026-11-27): status Modified; published 2022-04-04; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, ICS-CERT Secondary 9.8; NVD CWE-863, ICS-CERT CWE-288; CPE 20 AutomationDirect C0-10/C0-11/C0-12 CPU firmware versions before 3.00. — NVD
- CISA ICSA-21-166-02 CSAF (released 2021-06-15, read 2026-11-27): CLICK PLC CPU Modules below v3.00; CWE-288 9.8; siblings CVE-2021-32980 (9.8), CVE-2021-32984 (9.8), CVE-2021-32982 (7.5), CVE-2021-32978 (7.5); all mitigated by version 3.00; sectors Commercial Facilities, Critical Manufacturing, Information Technology; reported by Irfan Ahmed, Adeen Ayub (VCU) and Hyunguk Yoo (University of New Orleans); no known public exploits. — CISA ICSA-21-166-02
- CISA advisory page ICSA-21-166-02 (read 2026-11-27): C0-1x CPUs with firmware prior to v3.00, five CVEs, update to v3.00, VPN and firewall guidance. — CISA
- CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2022-04-04, CNA CVSS 9.8; affected CLICK PLC CPU Modules C0-1x CPUs below 3.00; solution: version 3.00 and AutomationDirect security guidelines. — CVE.org
- AutomationDirect CLICK PLC Hardware User Manual Appendix A, Security Considerations for Control Systems Networks (read 2026-11-27): defence in depth, firewalls, isolation from business networks, VPN remote access, no direct internet exposure. — AutomationDirect
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.01113, percentile 0.65637, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2021-32986?
Version 3.00. AutomationDirect reports that v3.00 mitigates all five CLICK PLC vulnerabilities in ICSA-21-166-02 and recommends updating both the programming software and the PLC firmware to the latest version.
Which CLICK PLC models are affected?
The C0-1x CPU modules on firmware before v3.00. NVD lists 20 part numbers from C0-10DD1E-D through C0-12ARE-2-D.
How do I relock a CLICK PLC left unlocked?
Per the CVE description, the PLC relocks only after a power cycle or when the programming software disconnects correctly. Until v3.00 is installed, power-cycle after any interrupted programming session and keep the programming port off shared networks.
Is CVE-2021-32986 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01113 (65.64th percentile) in the 2026-11-26 dataset.
Questions about this page?