CVE-2020-27738: Nucleus DNS Compression Pointer Over-Read

Last updated:
  • CVE-2020-27738

CVE-2020-27738 is a NAME:WRECK flaw in the DNS client of Siemens' Nucleus RTOS network stack: compression pointer offsets in DNS names are not validated, so a malformed response makes the parser read past its buffer and can crash the device. NVD scores it 7.4 and Siemens 6.5; Siemens lists fixes for Nucleus ReadyStart, SIMOTICS CONNECT 400 and APOGEE/TALON field panels.

Vulnerability summary

CVSS base score

7.4

High severity

EPSS score (FIRST)

4.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-27738 · Source: NVD

Affected components

ComponentCPEVersion range
Nucleus NETcpe:2.3:a:siemens:nucleus_net:*:*:*:*:*:*:*:*all versions; Siemens offers no fix and recommends moving to Nucleus ReadyStart V3 or V4 (SSA-705111)
Nucleus ReadyStart V3 and V4cpe:2.3:a:siemens:nucleus_readystart_v3:*:*:*:*:*:*:*:*V3 before V2017.02.3; V4 before V4.1.0 (SSA-705111)
Nucleus Source Code (versions including the affected DNS modules)cpe:2.3:a:siemens:nucleus_source_code:-:*:*:*:*:*:*:*versions including the affected DNS modules; patch from Siemens customer support (SSA-705111)
Siemens SIMOTICS CONNECT 400cpe:2.3:o:siemens:simotics_connect_400_firmware:*:*:*:*:*:*:*:*before V0.5.0.0 (SSA-669158, CISA ICSA-21-103-13)
Siemens APOGEE PXC Compact/Modular and TALON TC Compact/Modular field panels—BACnet before V3.5.5; APOGEE P2 Ethernet before V2.8.20 (SSA-180579, CISA ICSA-22-349-16)

What does this mean for affected devices?

Siemens ProductCERT's SSA-705111 (CSAF), first published 2021-04-13 and last updated 2022-01-11, covers the NAME:WRECK vulnerabilities in the DNS module of Nucleus RTOS. For this CVE it says "the DNS domain name record decompression functionality does not properly validate the pointer offset values", so parsing a malformed response "could result in a read access past the end of an allocated structure", and that "an attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition". Siemens classifies it as CWE-788 (access of memory location after end of buffer) and scores it 6.5 with low confidentiality impact; NVD records CWE-119 (improper restriction of operations within the bounds of a memory buffer) and scores it 7.4, vector CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:H, rating the confidentiality impact high (NVD).

DNS compression lets a name end in a pointer to an earlier position in the message, and a parser that follows that offset without a bounds check reads wherever the attacker points it.

For the stack, Siemens tells users to update Nucleus ReadyStart V3 to V2017.02.3 or later and V4 to V4.1.0 or later, and to contact customer support for patches to Nucleus source code that includes the affected DNS modules. For the standalone Nucleus NET product it offers no fix, recommends moving to ReadyStart V3 or V4, and gives one workaround for every affected product: "Avoid using DNS client of affected versions".

Nucleus runs inside Siemens' own devices, which carry their own advisories. SSA-669158 (CSAF), republished by CISA as ICSA-21-103-13, lists SIMOTICS CONNECT 400, a motor-monitoring sensor box, as affected before V0.5.0.0 and fixed in V0.5.0.0. SSA-180579 (CSAF), republished as ICSA-22-349-16, lists APOGEE PXC Compact and Modular and TALON TC Compact and Modular building-automation field panels: fixed in V3.5.5 for BACnet firmware and V2.8.20 for APOGEE P2 Ethernet firmware.

The CVE is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.04055, the 90.8th percentile, in the 2026-11-16 dataset (CISA KEV, FIRST EPSS).

Device makers on Nucleus should check whether the DNS client is compiled in and used, then move to the fixed ReadyStart release or get the source patch from Siemens; operators of the Siemens devices above should apply the listed firmware. Our embedded TCP/IP stack vulnerabilities guide lists the four Nucleus NAME:WRECK CVEs with their fixes, and our BACnet security guide covers the field-panel networks where APOGEE and TALON devices sit. The other DNS flaws from the same Siemens advisory are CVE-2020-27736 (label parsing), CVE-2020-27737 (record lengths and counts) and CVE-2021-25677 (weak transaction IDs).

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • CVE-2020-27738: DNS module flaw in Nucleus; privileged network position; DoS; fixes ReadyStart V3 V2017.02.3 and V4 V4.1.0; Nucleus NET no fix, move to ReadyStart; workaround: avoid using DNS client; first published 2021-04-13, updated 2022-01-11. — Siemens ProductCERT SSA-705111
  • NVD CVSS v3.1 7.4 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:H). — NVD
  • SIMOTICS CONNECT 400 affected before V0.5.0.0; update to V0.5.0.0 or later. — Siemens ProductCERT SSA-669158
  • CISA republication of SSA-669158. — CISA ICSA-21-103-13 (CSAF)
  • APOGEE PXC / TALON TC field panels: BACnet before V3.5.5, P2 Ethernet before V2.8.20. — Siemens ProductCERT SSA-180579
  • CISA republication of SSA-180579. — CISA ICSA-22-349-16 (CSAF)
  • Not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). — CISA KEV
  • EPSS 0.04055 (90.8th percentile), dataset 2026-11-16, read 2026-11-16. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-705111: NAME:WRECK vulnerabilities in the DNS module of Nucleus RTOS (CSAF)
  3. Siemens ProductCERT SSA-669158: DNS client vulnerabilities in SIMOTICS CONNECT 400 (CSAF)
  4. CISA ICSA-21-103-13: Siemens SIMOTICS CONNECT 400 (CSAF)
  5. Siemens ProductCERT SSA-180579: APOGEE/TALON field panels (CSAF)
  6. CISA ICSA-22-349-16: Siemens APOGEE and TALON (CSAF)
  7. CISA KEV
  8. FIRST EPSS

Frequently asked questions

Which Nucleus versions fix CVE-2020-27738?

Nucleus ReadyStart V3 V2017.02.3 and V4 V4.1.0. For Nucleus source code with the affected DNS modules, Siemens says to contact customer support for patches; for standalone Nucleus NET it offers no fix and recommends moving to ReadyStart V3 or V4 (per Siemens SSA-705111).

Which Siemens devices are affected by CVE-2020-27738?

SIMOTICS CONNECT 400 before V0.5.0.0, and APOGEE PXC Compact and Modular and TALON TC Compact and Modular field panels with BACnet firmware before V3.5.5 or APOGEE P2 Ethernet firmware before V2.8.20 (per Siemens SSA-669158 and SSA-180579).

What does an attacker need to exploit CVE-2020-27738?

A malformed DNS response whose compression pointers point outside the message, delivered to the device's DNS client. Siemens describes the attacker as having "a privileged position in the network" and lists a denial of service as the result; NVD's vector has high attack complexity (per Siemens SSA-705111 and NVD).

Is there a workaround if the firmware cannot be updated?

Siemens' workaround for all affected Nucleus products is "Avoid using DNS client of affected versions", and its general recommendation is to protect network access to the devices with appropriate mechanisms (per Siemens SSA-705111).