Security Advisory

CVE-2020-27736: Nucleus NET DNS Label Parsing Over-Read

Last updated:
  • CVE-2020-27736

CVE-2020-27736 is a NAME:WRECK flaw in the DNS client of Siemens' Nucleus RTOS network stack: a malformed DNS response with a bad null-terminated name makes the parser read past its buffer, crashing the device or leaking memory. NVD scores it 6.5, and Siemens lists fixes for Nucleus ReadyStart, SIMOTICS CONNECT 400 and APOGEE/TALON field panels.

Vulnerability summary

CVSS base score

6.5

Medium severity

EPSS score (FIRST)

4.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-27736 · Source: NVD

Affected components

ComponentCPEVersion range
Nucleus NETcpe:2.3:a:siemens:nucleus_net:*:*:*:*:*:*:*:*all versions; Siemens lists no fix and recommends moving to Nucleus ReadyStart V3 or V4 (SSA-705111)
Nucleus ReadyStart V3 and V4cpe:2.3:a:siemens:nucleus_readystart_v3:*:*:*:*:*:*:*:*V3 before V2017.02.3; V4 before V4.1.0 (SSA-705111)
Siemens SIMOTICS CONNECT 400—before V0.5.0.0 (SSA-669158, CISA ICSA-21-103-13)
Siemens APOGEE PXC Compact/Modular and TALON TC Compact/Modular field panels—BACnet before V3.5.5; APOGEE P2 Ethernet before V2.8.20 (SSA-180579, CISA ICSA-22-349-16)

What does this mean for affected devices?

Siemens ProductCERT's SSA-705111 (CSAF), first published 2021-04-13 and last updated 2022-01-11, covers the NAME:WRECK vulnerabilities in the DNS module of Nucleus RTOS. For this CVE it says "the DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses", that parsing a malformed response "could result in a read past the end of an allocated structure", and that "an attacker with a privileged position in the network" could cause a denial of service or leak the read memory. Siemens classifies it as CWE-170 (improper null termination); NVD records CWE-125 (out-of-bounds read) and scores it 6.5, vector CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H, the same score Siemens gives (NVD).

For the stack itself, Siemens tells users to update Nucleus ReadyStart V3 to V2017.02.3 or later and V4 to V4.1.0 or later, and to contact customer support for patches to Nucleus source code that includes the affected DNS modules. For the standalone Nucleus NET product it lists no fix, recommends moving to ReadyStart V3 or V4, and gives one workaround for all of them: "Avoid using DNS client of affected versions".

Nucleus is built into Siemens' own devices, which carry their own advisories. SSA-669158 (CSAF), republished by CISA as ICSA-21-103-13, says SIMOTICS CONNECT 400, a motor-monitoring sensor box, is affected before V0.5.0.0 and fixed in V0.5.0.0. SSA-180579 (CSAF), republished as ICSA-22-349-16, lists APOGEE PXC Compact and Modular and TALON TC Compact and Modular building-automation field panels: fixed in V3.5.5 for BACnet firmware and V2.8.20 for APOGEE P2 Ethernet firmware.

The CVE is not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). FIRST EPSS gives it 0.0396, the 90.6th percentile, in the 2026-11-15 dataset (CISA KEV, FIRST EPSS).

Device makers on Nucleus should confirm whether the DNS client is compiled in and used, then move to the fixed ReadyStart release or get the source patch from Siemens. Our embedded TCP/IP stack vulnerabilities guide lists the four Nucleus NAME:WRECK CVEs and the triage steps, and our BACnet security guide covers the field-panel networks where APOGEE and TALON devices sit. The weak transaction-ID flaw from the same Siemens advisory is CVE-2021-25677.

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • DNS label parsing does not validate null-terminated name; read past end of structure; DoS or memory leak; CWE-170; fixes ReadyStart V3 V2017.02.3 and V4 V4.1.0; Nucleus NET no fix, avoid DNS client. — Siemens ProductCERT SSA-705111
  • NVD CVSS v3.1 6.5 (AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H), CWE-125. — NVD
  • SIMOTICS CONNECT 400 affected before V0.5.0.0; update to V0.5.0.0. — Siemens ProductCERT SSA-669158
  • CISA republished SSA-669158 on 2021-04-13. — CISA ICSA-21-103-13 (CSAF)
  • APOGEE PXC / TALON TC field panels: BACnet before V3.5.5, P2 Ethernet before V2.8.20. — Siemens ProductCERT SSA-180579
  • CISA republished SSA-180579 on 2022-12-13. — CISA ICSA-22-349-16 (CSAF)
  • Not in the CISA KEV catalog as of 2026-11-16 (catalog version 2026.11.13). — CISA KEV
  • EPSS 0.0396 (90.6th percentile), dataset 2026-11-15, read 2026-11-16. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-705111: NAME:WRECK vulnerabilities in the DNS module of Nucleus RTOS (CSAF)
  3. Siemens ProductCERT SSA-669158: DNS client vulnerabilities in SIMOTICS CONNECT 400 (CSAF)
  4. CISA ICSA-21-103-13: Siemens SIMOTICS CONNECT 400 (CSAF)
  5. Siemens ProductCERT SSA-180579: APOGEE/TALON field panels (CSAF)
  6. CISA ICSA-22-349-16: Siemens APOGEE and TALON (CSAF)
  7. CISA KEV
  8. FIRST EPSS

Frequently asked questions

Which Nucleus versions fix CVE-2020-27736?

Nucleus ReadyStart V3 V2017.02.3 and V4 V4.1.0. For Nucleus source code with the affected DNS modules, Siemens says to contact customer support for patches; for standalone Nucleus NET it lists no fix and recommends moving to ReadyStart V3 or V4 (per Siemens SSA-705111).

Which Siemens devices are affected by CVE-2020-27736?

SIMOTICS CONNECT 400 before V0.5.0.0, and APOGEE PXC Compact and Modular and TALON TC Compact and Modular field panels with BACnet firmware before V3.5.5 or APOGEE P2 Ethernet firmware before V2.8.20 (per Siemens SSA-669158 and SSA-180579).

What does an attacker need to exploit CVE-2020-27736?

A malformed DNS response delivered to the device's DNS client. Siemens describes the attacker as having "a privileged position in the network", and NVD's vector has high attack complexity; the result is a denial of service or a memory leak (per Siemens SSA-705111 and NVD).

Is there a workaround if the firmware cannot be updated?

Siemens' workaround for all affected Nucleus products is "Avoid using DNS client of affected versions", and its device advisories recommend protecting network access to the devices (per Siemens SSA-705111 and SSA-669158).