Security Advisory

CVE-2020-25197: GE Reason RT43X GNSS Clock Code Injection

Last updated:
  • CVE-2020-25197

CVE-2020-25197 is a code injection flaw (CWE-94) in a web page of GE Reason RT430, RT431 and RT434 GNSS clocks with firmware before 08A06. An authenticated remote attacker could run arbitrary code on the clock. NVD scores it 8.8 and CISA 9.8. GE's fix is firmware 08A06 or later; until then, block web access to the clock.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

3.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-25197 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
GE Reason RT430 GNSS clockcpe:2.3:o:ge:rt430_firmware:*:*:*:*:*:*:*:*Firmware before 08A06 (CISA ICSA-21-005-03, NVD CPE, CVE record); fix: firmware 08A06 or later
GE Reason RT431 GNSS clockcpe:2.3:o:ge:rt431_firmware:*:*:*:*:*:*:*:*Firmware before 08A06 (CISA ICSA-21-005-03, NVD CPE, CVE record); fix: firmware 08A06 or later
GE Reason RT434 GNSS clockcpe:2.3:o:ge:rt434_firmware:*:*:*:*:*:*:*:*Firmware before 08A06 (CISA ICSA-21-005-03, NVD CPE, CVE record); fix: firmware 08A06 or later

What does this mean for affected devices?

The CVE record from CISA describes "a code injection vulnerability" in "one of the webpages" of GE Reason RT430, RT431 and RT434 GNSS clocks with firmware before 08A06 that "could allow an authenticated remote attacker to execute arbitrary code on the system." Both NVD and CISA map it to CWE-94, improper control of generation of code. The scores differ on privileges: NVD's Primary score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), which reflects the authenticated attacker in the description, while CISA, the CNA, scores it 9.8 with no privileges required (PR:N). NVD published the record on 2022-03-18 and lists RT430, RT431 and RT434 firmware below 08A06 (NVD, CVE record).

Why does a clock flaw matter in a substation?

Reason RT43X units are GNSS clocks: they take time from satellite receivers and hand it to the devices around them. CISA lists the deployment sectors as Communications, Critical Manufacturing, Energy, Healthcare and Public Health, Transportation Systems, and Water and Wastewater Systems, worldwide. Code execution on the clock would put an attacker on the same network as the equipment that takes its time from it. The time sync vulnerabilities guide explains why wrong time breaks logs and certificate checks, and the IEC 62351 guide covers securing substation communications.

What does ICSA-21-005-03 cover?

CISA's ICSA-21-005-03, released on 2021-01-05, covers the RT430, RT431 and RT434 on all firmware before 08A06. It has one sibling CVE: CVE-2020-25193, a hard-coded cryptographic key (CWE-321, CVSS 5.3) that would let an attacker intercept and decrypt HTTPS traffic to the clock. Tom Westenberg of Thales UK reported both flaws to GE, and CISA noted no known public exploits targeting them (CISA advisory page).

How do you fix CVE-2020-25197?

GE strongly recommends updating Reason RT43X units to firmware 08A06 or later, which fixes both CVEs as described in the Reason RT43X 08A06 release notes. GE's detailed notice, GES-2020-006, requires a login. Until a clock is updated, GE and CISA list these measures:

  • block TCP ports 80 and 443 to the clock's web interface, with an access control list on the switch port where the clock connects so other web services are not affected;
  • use strong network and physical security so attackers cannot reach the clock's local network;
  • keep control system devices off the internet and behind firewalls, with VPNs for any remote access;
  • analyze security events to spot unexpected traffic to or from the clock.

Since NVD's description names an authenticated attacker, restricting who holds web credentials for the clocks also narrows exposure. The command injection fix guide covers how firmware should handle input that reaches an interpreter. Other GE grid flaws on this site include CVE-2021-27428 (UR relay firmware upload) and CVE-2018-5475 (D60 line distance relay).

Is CVE-2020-25197 exploited?

CVE-2020-25197 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.03172, the 88.79th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Command injection. Our practical guide covers how to detect, fix, verify and disclose it: How to fix command injection in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2022-03-18; NVD Primary CVSS v3.1 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, ICS-CERT Secondary 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CWE-94 (NVD and CISA); CPE ge rt430, rt431, rt434 firmware before 08a06. — NVD
  • CISA ICSA-21-005-03 CSAF (released 2021-01-05, read 2026-11-27): RT430, RT431 & RT434 below 08A06; CWE-94 9.8; sibling CVE-2020-25193 CWE-321 5.3; fix firmware 08A06 or greater; block TCP 80/443 with ACL on the clock's port; GES-2020-006 login required; sectors Communications, Critical Manufacturing, Energy, Healthcare, Transportation, Water; reported by Tom Westenberg (Thales UK); no known public exploits. — CISA ICSA-21-005-03
  • CISA advisory page ICSA-21-005-03 (read 2026-11-27): GE Reason RT43X Clocks, released January 5, 2021; update to 08A06; block ports 80 and 443; firewalls and VPNs. — CISA
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2022-03-18, CNA CVSS 9.8; affected Reason RT43X Clocks below 08A06; solution firmware 08A06 or greater. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.03172, percentile 0.88787, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-21-005-03: GE Reason RT43X Clocks (CSAF)
  3. CISA ICSA-21-005-03 advisory page
  4. CVE.org record CVE-2020-25197
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2020-25197?

Firmware 08A06 or later for the Reason RT430, RT431 and RT434. GE states that 08A06 fixes both CVE-2020-25197 and CVE-2020-25193 (ICSA-21-005-03).

Why do NVD and CISA give different scores?

NVD scores 8.8 with low privileges required, matching the description's authenticated attacker. CISA scores 9.8 with no privileges required. Both use network attack vector and high impact on confidentiality, integrity and availability.

What can I do if the clock cannot be updated right away?

Block TCP ports 80 and 443 to the clock's web interface with an ACL on its switch port, keep it off the internet and behind firewalls, use VPNs for remote access, and watch for unexpected traffic, as GE and CISA recommend.

Is CVE-2020-25197 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.03172 (88.79th percentile) in the 2026-11-26 dataset.