CVE-2020-25159 is a stack-based buffer overflow in Real Time Automation's 499ES EtherNet/IP adapter stack before version 2.28. An unauthenticated attacker who can reach TCP port 44818 sends a crafted forward-open request and can crash the device or possibly run code. NVD and CISA score it 9.8. The stack ships inside other vendors' firmware, so the fix comes from each device maker.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
3.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-25159 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Real Time Automation 499ES EtherNet/IP (ENIP) Adaptor Source Code | cpe:2.3:o:rtautomation:499es_ethernet\/ip_adaptor_firmware:*:*:*:*:*:*:*:* | All versions prior to 2.28 (CISA ICSA-20-324-03, NVD CPE). Version 2.28, released 21 November 2012, no longer contains the vulnerable code per RTA via Claroty Team82 |
| Devices from other vendors that embed the RTA 499ES stack | — | Depends on the stack version built into the firmware; Claroty found 11 devices from six unnamed vendors using the RTA stack. No downstream vendor advisory is referenced by CISA or NVD as of 2026-11-19 |
What does this mean for affected devices?
NVD carries CISA's description: "499ES EtherNet/IP (ENIP) Adaptor Source Code is vulnerable to a stack-based buffer overflow, which may allow an attacker to send a specially crafted packet that may result in a denial-of-service condition or code execution." NVD's Primary score is CVSS v3.1 9.8 (critical), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CVSS v2 7.5. NVD classes it CWE-787 (out-of-bounds write); CISA, the CNA, uses CWE-121 (stack-based buffer overflow). NVD's CPE covers 499ES EtherNet/IP Adaptor firmware before 2.28. The record was published on 2020-11-24 and the CVE.org record is PUBLISHED with CISA ICS as CNA (NVD, CVE record).
Why does a source-code stack matter for device owners?
Real Time Automation (RTA) sells the 499ES stack as source code that device makers compile into their own firmware. CISA's ICSA-20-324-03 (17 November 2020) lists "499ES EtherNet/IP Adaptor Source Code, a TCP/IP stack", all versions prior to 2.28, scores it CVSS v3.0 9.8 and credits Sharon Brizinov of Claroty. Claroty Team82's write-up says RTA confirmed the flaw is present in every 499ES version before v2.28, released on 21 November 2012, and that vendors may have bought older versions and integrated them into firmware that is still in use. Claroty scanned 290 EtherNet/IP devices, found 32 distinct stacks, and identified 11 devices from six vendors running the RTA stack; RTA contacted all of them. Neither CISA nor Claroty names those vendors, and NVD lists no downstream vendor advisory as of 2026-11-19, so the product name on a nameplate will not tell you whether a device is affected.
How is it triggered?
According to Claroty, an attacker sends a crafted EtherNet/IP forward-open request to TCP port 44818. The stack stores the connection CIP path in a fixed array of 32 16-bit values but accepts a path of up to 255 values, so a path longer than 32 entries writes past the array on the stack. That normally crashes the device; whether it leads to code execution depends on the firmware. CISA rates the flaw remotely exploitable with low skill and reported no known public exploits targeting it.
How do you fix or mitigate it?
Device makers should move to a 499ES release of 2.28 or later and ship new firmware; CISA's only remediation entry is to contact RTA support. Asset owners need a firmware update from the device maker, so ask suppliers of EtherNet/IP adapters, gateways and drives whether they embed the RTA stack and which version. Until then, follow CISA's advice: keep devices off the internet, put control networks behind firewalls, and use a VPN for remote access. Blocking or filtering 44818/tcp from untrusted zones removes the path to the bug.
Our EtherNet/IP and CIP security guide compares this stack with OpENer and other licensed stacks, and the memory corruption fix guide covers bounds checks on length fields. Related CIP flaws are CVE-2023-3595 and CVE-2023-3596 in Rockwell ControlLogix communication modules; Claroty compares the case with Ripple20, for example CVE-2020-11896 in the Treck TCP/IP stack.
CVE-2020-25159 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.03026, the 87.7th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-19): status Modified; published 2020-11-24; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 7.5; CWE-787 (NVD), CWE-121 (CISA ICS, secondary); CPE rtautomation 499es_ethernet/ip_adaptor_firmware before 2.28; sole reference ICSA-20-324-03. — NVD
- CISA ICSA-20-324-03 web page and CSAF (released 2020-11-17), read 2026-11-19: 499ES EtherNet/IP Adaptor Source Code, a TCP/IP stack, all versions prior to 2.28; CWE-121; CVSS v3.0 9.8; remotely exploitable with low skill; no known public exploits; Critical Manufacturing, deployed worldwide; credit Sharon Brizinov (Claroty); remediation: contact Real Time Automation; no downstream products named. — CISA ICSA-20-324-03
- Claroty Team82, read 2026-11-19: overflow in the forward-open connection CIP path parsing (array of 32 16-bit values, path up to 255 values) over TCP 44818; RTA confirms all 499ES versions before v2.28 (released 2012-11-21) are affected; 290 devices scanned, 32 stacks, 11 devices from six vendors run the RTA stack, all contacted by RTA; more than 8,000 internet-facing ENIP devices per Shodan. — Claroty Team82
- CVE record (checked 2026-11-19): state PUBLISHED, CNA CISA ICS (icscert), published 2020-11-24; affected 499ES EtherNet/IP (ENIP) Adaptor Source Code less than 2.28; CWE-121; no CNA CVSS metric. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-19. — CISA KEV
- EPSS 0.03026, percentile 0.87733, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD: CVE-2020-25159
- CVE.org record CVE-2020-25159 (CNA: CISA ICS)
- CISA ICS Advisory ICSA-20-324-03: Real Time Automation EtherNet/IP
- CISA CSAF record for ICSA-20-324-03
- Claroty Team82: ENIP Stack Vulnerability Causes Crashes or Leads to Code Execution
- Real Time Automation support
- CISA Known Exploited Vulnerabilities catalog
- FIRST EPSS score for CVE-2020-25159
Frequently asked questions
Which version fixes CVE-2020-25159?
499ES EtherNet/IP Adaptor Source Code 2.28 and later. CISA lists all versions prior to 2.28 as affected, and RTA told Claroty that v2.28, released 21 November 2012, no longer contains the vulnerable code (per CISA ICSA-20-324-03 and Claroty Team82).
How do I know whether my device is affected?
Ask the device maker whether its firmware embeds the RTA 499ES stack and which version. Claroty found 11 devices from six vendors using the stack but did not name them, and CISA and NVD reference no downstream vendor advisory as of 2026-11-19 (per Claroty Team82, CISA ICSA-20-324-03 and NVD).
What can I do if no firmware update exists?
Minimize network exposure, keep devices unreachable from the internet, isolate control networks behind firewalls and use a VPN for remote access, and contact Real Time Automation for details (per CISA ICSA-20-324-03). Filtering TCP 44818 from untrusted zones blocks the forward-open path the bug uses (per Claroty Team82).
Why does NVD list CWE-787 and CISA CWE-121?
Both describe the same bug: CISA uses the specific class, a stack-based buffer overflow, and NVD the parent class, an out-of-bounds write. Both score it 9.8 with network access, no privileges and full impact (per NVD and CISA ICSA-20-324-03).
Is CVE-2020-25159 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18), and CISA reported no known public exploits at release. FIRST EPSS gives it 0.03026, the 87.7th percentile, in the 2026-11-18 dataset (per CISA KEV, CISA ICSA-20-324-03 and FIRST EPSS).
Questions about this page?