Security Advisory

CVE-2020-12004: Ignition getDiffs Missing Authentication

Last updated:
  • CVE-2020-12004

CVE-2020-12004 is a missing authentication check on the getDiffs method of the Inductive Automation Ignition Gateway, so anyone who reaches the Gateway can query project data. At Pwn2Own Miami 2020 it was the first step of a chain with CVE-2020-10644. NVD scores it 7.5, CISA and ZDI 5.3. Ignition 8.0.10 and 7.9.14 fix it.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

14.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-12004 · Source: NVD

Affected components

ComponentCPEVersion range
Inductive Automation Ignition 7 Gatewaycpe:2.3:a:inductiveautomation:ignition_gateway:*:*:*:*:*:*:*:*before 7.9.14; fixed in 7.9.14 (CISA ICSA-20-147-01, NVD 7.2.4.48 to before 7.9.14)
Inductive Automation Ignition 8 Gatewaycpe:2.3:a:inductiveautomation:ignition_gateway:*:*:*:*:*:*:*:*before 8.0.10; fixed in 8.0.10 (CISA ICSA-20-147-01, NVD 8.0 to before 8.0.10)

What does this mean for affected devices?

NVD's description says the product "lacks proper authentication required to query the server", letting an attacker "obtain sensitive information". NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N) and NVD CVSS v2 5.0, with CWE-306. CISA's advisory and the Zero Day Initiative score it lower, CVSS v3.0 5.3 (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). The record was published on 2020-06-09 (NVD, CVE record).

Where is the flaw?

ZDI-20-685, published on 2020-06-01, places it in "the getDiffs method of the com.inductiveautomation.ignition.gateway.servlets.gateway.functions.ProjectDownload class". ZDI adds that an attacker "can leverage this in conjunction with other vulnerabilities to execute code in the context of SYSTEM". Pedro Ribeiro and Radek Domanski reported it on 2020-02-04; their chain paired it with the deserialization flaw CVE-2020-10644. The 8.0.10 release notes include the line "Resolved information leak by required project download to require authentication".

Which versions are affected and fixed?

CISA's ICSA-20-147-01 lists the Ignition 8 Gateway before 8.0.10 and the Ignition 7 Gateway before 7.9.14, and recommends upgrading to 8.0.10 or 7.9.14. NVD's CPE ranges match, starting at 7.2.4.48 for the 7.x line. A related missing-authentication flaw, CVE-2020-14479, was added in Update B without a fix.

See the Ignition SCADA guide and the authentication bypass fix guide.

CVE-2020-12004 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.13968, the 96.6th percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD (read 2026-11-24): status Modified; published 2020-06-09; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N and NVD CVSS v2 5.0; CWE-306; CPE ignition_gateway 7.2.4.48 to before 7.9.14 and 8.0 to before 8.0.10. — NVD
  • CISA ICSA-20-147-01 CSAF (released 2020-05-26, Update A 2020-06-02, Update B 2020-06-30), read 2026-11-24: Ignition 8 Gateway < 8.0.10 and Ignition 7 Gateway < 7.9.14; upgrade to 8.0.10 or 7.9.14; credit Pedro Ribeiro, Radek Domanski, Chris Anastasio, Steven Seeley via Trend Micro ZDI. CVE-2020-12004: CWE-306, CVSS v3.0 5.3. — CISA ICSA-20-147-01
  • ZDI-20-685 (ZDI-CAN-10275), published 2020-06-01: getDiffs method of ProjectDownload class lacks authentication, information disclosure, chainable to SYSTEM code execution, CVSS 5.3; reported 2020-02-04; credit Pedro Ribeiro and Radek Domanski. — Zero Day Initiative
  • 8.0.10 release notes (Released March 19, 2020) include 'Resolved information leak by required project download to require authentication'; 7.9.14 Released April 28, 2020. — Inductive Automation
  • CVE record (checked 2026-11-24): state PUBLISHED, CNA icscert, published 2020-06-09. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
  • EPSS 0.13968, percentile 0.96638, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-20-147-01 Inductive Automation Ignition, Update B (CSAF)
  3. Zero Day Initiative ZDI-20-685
  4. Inductive Automation: Ignition 8.0.10 release notes
  5. Inductive Automation: Ignition 7.9.14 release notes
  6. CVE.org record CVE-2020-12004
  7. CISA KEV
  8. FIRST EPSS

Frequently asked questions

Which Ignition versions fix CVE-2020-12004?

Ignition 8.0.10 for the 8.0 line and 7.9.14 for the 7.9 line, per CISA ICSA-20-147-01.

Can CVE-2020-12004 alone run code?

No. On its own it discloses information. ZDI says it can be combined with other flaws to run code as SYSTEM, as Pedro Ribeiro and Radek Domanski did with CVE-2020-10644.

Why does NVD score it higher than CISA?

NVD's Primary vector sets confidentiality impact to high (7.5). CISA and ZDI set it to low (5.3).

Is CVE-2020-12004 in the CISA KEV catalog?

No, not as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS rates it 0.13968 (96.6th percentile) in the 2026-11-23 dataset.