  • CVE-2020-10641

CVE-2020-10641 is a denial of service in the Inductive Automation Ignition 8 Gateway before 8.0.10. A logging route in the Perspective module needs no login, so anyone who can reach the Gateway can write log entries into its database until the disk is full. NVD scores it 7.5 and CISA 9.1. Ignition 8.0.10 fixes it.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-10641 · Source: NVD

Affected components

ComponentCPEVersion range
Inductive Automation Ignition 8 Gatewaycpe:2.3:a:inductiveautomation:ignition_gateway:*:*:*:*:*:*:*:*8.0 before 8.0.10; fixed in 8.0.10 (CISA ICSA-20-112-01, NVD 8.0 to before 8.0.10)

What does this mean for affected devices?

NVD carries the CISA description: "An unprotected logging route may allow an attacker to write endless log statements into the database without space limits or authentication." The result is that the Gateway's free disk space is used up. NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) and NVD CVSS v2 5.0, with CWE-306, missing authentication for a critical function. CISA, the CNA, scores it CVSS v3.0 9.1 (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H) and lists CWE-284. The record was published on 2020-04-28 (NVD, CVE record).

Which Ignition versions are affected?

CISA's ICSA-20-112-01, released on 2020-04-21, names the Ignition 8 Gateway before 8.0.10. NVD's CPE range matches: 8.0 up to, but not including, 8.0.10. Ignition 7.9 is not listed. Sharon Brizinov and Mashav Sapir of Claroty reported it.

What should operators do?

Upgrade to 8.0.10 or later; the 8.0.10 release notes date that release to March 19, 2020. Until then, CISA gives two workarounds. With the Perspective Module running, set the "perspective.routes" logger to WARN or higher, because the exploit logs at INFO. Behind a reverse proxy or web application firewall, deny every Gateway HTTP request whose path includes /data/perspective/print-to-log. Keep the Gateway's web ports off the internet in any case.

The Ignition SCADA guide covers the other Gateway web flaws from the same period, such as the unauthenticated file path check CVE-2020-14520 and the Pwn2Own 2020 chain built on CVE-2020-12004. The authentication bypass fix guide covers unprotected routes in general.

CVE-2020-10641 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.01278, the 70.7th percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD (read 2026-11-24): status Modified; published 2020-04-28; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H and NVD CVSS v2 5.0; CWE-306 (NVD), CWE-284 (ICS-CERT); CPE ignition_gateway 8.0 to before 8.0.10. — NVD
  • CISA ICSA-20-112-01 CSAF (released 2020-04-21), read 2026-11-24: Ignition 8 Gateway < 8.0.10; CVSS v3.0 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H; CWE-284; fix: upgrade to 8.0.10; mitigations: perspective.routes logger WARN or higher, deny /data/perspective/print-to-log at WAF/reverse proxy; credit Sharon Brizinov and Mashav Sapir of Claroty. — CISA ICSA-20-112-01
  • Ignition 8.0.10 release notes: Released March 19, 2020. — Inductive Automation
  • CVE record (checked 2026-11-24): state PUBLISHED, CNA icscert, published 2020-04-28. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
  • EPSS 0.01278, percentile 0.70734, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-20-112-01 Inductive Automation Ignition (CSAF)
  3. Inductive Automation: Ignition 8.0.10 release notes
  4. CVE.org record CVE-2020-10641
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Ignition version fixes CVE-2020-10641?

Ignition 8.0.10. CISA's ICSA-20-112-01 lists the Ignition 8 Gateway before 8.0.10 as affected; Ignition 7.9 is not listed.

Can I mitigate CVE-2020-10641 without upgrading?

CISA lists two ways: set the "perspective.routes" logger to WARN or higher when the Perspective Module runs, or block requests to /data/perspective/print-to-log at a reverse proxy or web application firewall.

Why do NVD and CISA scores differ?

NVD rates only availability impact and gets CVSS v3.1 7.5. CISA's CVSS v3.0 vector also sets integrity impact to high (I:H) and gets 9.1.