CVE-2020-10634 is a path traversal flaw in the web server of the SAE IT-systems FW-50 remote telemetry unit with the CPU-5B card. A crafted request shows the device's file structure and opens files that should be off-limits. NVD and CISA score it 9.1. SAE IT-systems' remedy is a replacement CPU card or disabling the web server port.
Vulnerability summary
CVSS base score
9.1
Critical severity
EPSS score (FIRST)
1.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-10634 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| SAE IT-systems FW-50 RTU, 5 Series, CPU-5B | cpe:2.3:o:sae-it:net-line_fw-50_firmware:-:*:*:*:*:*:*:* | CPU-5B card, hardware revision 2, CPLD revision 6 (CVE record, CISA ICSA-20-126-02); NVD CPE carries no version; fix: replacement CPU card programmed with the new setIT version, or disable the web server port |
What does this mean for affected devices?
The CVE record from CISA says that in the SAE IT-systems FW-50 Remote Telemetry Unit (RTU), "a specially crafted request could allow an attacker to view the file structure of the affected device and access files that should be inaccessible." It names the FW-50 RTU 5 Series with CPU type CPU-5B, hardware revision 2 and CPLD revision 6. NVD's Primary score is 9.1 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N, CVSS 2.0 6.4), the same base score and vector CISA gives in CVSS 3.0, and both use CWE-22 (NVD, CVE record). NVD's CPE for the FW-50 firmware carries no version, so the hardware details from the advisory are the way to identify affected units.
Which FW-50 units are affected?
CISA advisory ICSA-20-126-02, released on 2020-05-05, lists the FW-50 RTU 5 Series with a CPU-5B card at hardware revision 2 and CPLD revision 6, used worldwide in the Critical Manufacturing, Energy, Transportation Systems and Water and Wastewater sectors; the vendor is based in Germany. The advisory has one sibling, a cross-site scripting flaw in the same web server (CVE-2020-10630, CISA 8.1, NVD 6.1). CISA's risk summary is that an attacker could execute remote code through input injection or browse and read files on the device. Murat Aydemir of Biznet Bilisim reported both flaws to CISA.
How do you fix CVE-2020-10634?
SAE IT-systems' remedy, as CISA records it, is hardware: replace the CPU card with a new one, then program the new card with the current version of the setIT configuration software from the SAE IT-systems website; customers contact SAE IT-systems for the replacement card. Because both flaws sit in the web server, SAE IT-systems also recommends disabling the project web server port, and disabling it anyway when it is not used; its hotline handles questions about doing so. CISA adds the usual network measures: no internet exposure, firewalls between the control network and the business network, and secure remote access.
A fire-alarm web server with the same weakness from the same months is the Honeywell NOTI-FIRE-NET Web Server, CVE-2020-6974, and an older Honeywell path traversal is the Experion PKS CVE-2014-5436. For device makers, the path traversal fix guide covers confining file access in embedded web servers, and the OT security guide for small manufacturers covers exposure of field devices.
Is CVE-2020-10634 exploited?
CVE-2020-10634 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01406, the 72.77th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploitation specifically targeting these vulnerabilities.


Evidence
- NVD (read 2026-11-27): status Modified; published 2020-05-05; [email protected] Primary CVSS 3.1 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N, CVSS 2.0 6.4; CWE-22 (NVD and ICS-CERT); CPE sae-it net-line_fw-50_firmware (no version) on net-line_fw-50. — NVD
- CVE record (CNA icscert, published 2020-05-05): FW-50 RTU 5 Series, CPU-5B, hardware revision 2, CPLD revision 6; no CNA CVSS. — CVE.org
- CISA ICSA-20-126-02 (CSAF, 2020-05-05): FW-50 RTU 5 Series CPU-5B HW rev 2, CPLD rev 6; CVE-2020-10634 CWE-22 CVSS 3.0 9.1; sibling CVE-2020-10630 CWE-79 8.1; sectors Critical Manufacturing, Energy, Transportation Systems, Water and Wastewater; HQ Germany; remedy: replace CPU card, program with new setIT version, or disable web server port; reported by Murat Aydemir (Biznet Bilisim A.S.); no known public exploitation. — CISA CSAF
- CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2020-10634 not listed; checked 2026-11-27. — CISA KEV
- EPSS 0.01406, percentile 0.72773, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which SAE IT-systems devices are affected by CVE-2020-10634?
The FW-50 Remote Telemetry Unit, 5 Series, with a CPU-5B card at hardware revision 2 and CPLD revision 6, per the CVE record and CISA ICSA-20-126-02.
Is there a firmware update for CVE-2020-10634?
The remedy is hardware: replace the CPU card and program the new card with the current setIT software. Alternatively, SAE IT-systems recommends disabling the web server port.
What is the sibling flaw in the same advisory?
CVE-2020-10630 is a cross-site scripting flaw in the same FW-50 web server, scored 8.1 by CISA and 6.1 by NVD. Disabling the web server port covers both.
Is CVE-2020-10634 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01406, the 72.77th percentile, in the 2026-11-26 dataset.