Security Advisory

CVE-2020-6974: Honeywell Notifier Web Server Path Traversal

Last updated:
  • CVE-2020-6974

CVE-2020-6974 is a path traversal flaw in the Honeywell NOTI-FIRE-NET Web Server (NWS-3), the web server of Honeywell's Notifier fire alarm network, which lets an attacker read past restricted directories. NVD scores it 9.8, CISA 9.4. Honeywell released a firmware update; keep the web server off the internet until it is applied.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-6974 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Honeywell NOTI-FIRE-NET Web Server (NWS-3)cpe:2.3:a:honeywell:notifier_webserver:*:*:*:*:*:*:*:*3.50 and earlier (CVE record, NVD, CISA ICSA-20-051-03); Honeywell's product security table lists 'Version 5.50 and prior'; fixed by the NWS-3 firmware update package named in Honeywell Security Notification SN 2020-02-04 01

What does this mean for affected devices?

The CVE record from CISA says that "Honeywell Notifier Web Server (NWS) Version 3.50 is vulnerable to a path traversal attack, which allows an attacker to bypass access to restricted directories", and that Honeywell has released a firmware update. NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5), and NVD and CISA agree on CWE-22. CISA's own score is 9.4 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L); the CVE record carries no CVSS score (NVD, CVE record).

Which Honeywell fire products are affected?

CISA advisory ICSA-20-051-03, released on 2020-02-20, names the NOTI-FIRE-NET Web Server (NWS-3) at version 3.50 and earlier, deployed worldwide, and NVD's CPE uses the same bound. Honeywell's product security table lists the same advisory as "NWS Authentication Bypass and Path Traversal Vulnerabilities" with "Notifier Web Server (NWS) Version 5.50 and prior" and severity Critical, so the vendor's version bound is wider than the CVE record's. The sibling CVE-2020-6972 is an authentication bypass by capture-replay (CWE-294), CISA 9.3 and NVD 9.1. CISA's risk summary is that an attacker could bypass the web server's authentication. Gjoko Krstikj reported both flaws to Honeywell.

How do you fix CVE-2020-6974?

Honeywell released a firmware update package for all affected products, available after login on its Security and Fire site, and described it in Security Notification SN 2020-02-04 01. CISA's mitigations, taken from that notification:

  • update the NWS-3 firmware as the security notification describes;
  • isolate the system from the internet, or put the hardware behind a firewall or in a DMZ;
  • if remote connections are needed, use a VPN or other secure remote access;
  • use strong passwords on installations.

Another Honeywell path traversal on this site is the Experion PKS CVE-2014-5436, and a remote telemetry unit with the same weakness from the same months is SAE IT-systems FW-50 CVE-2020-10634. For device makers, the path traversal fix guide covers how to canonicalise and confine file paths in embedded web servers.

Is CVE-2020-6974 exploited?

CVE-2020-6974 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.01898, the 80.24th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting these vulnerabilities.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Path traversal. Our practical guide covers how to detect, fix, verify and disclose it: How to fix path traversal in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2020-04-07; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5; CWE-22 (NVD and ICS-CERT); CPE honeywell notifier_webserver up to and including 3.50. — NVD
  • CISA ICSA-20-051-03 (CSAF, 2020-02-20): NOTI-FIRE-NET Web Server (NWS-3) <= 3.50; CVE-2020-6974 CWE-22 CVSS 3.0 9.4 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L; sibling CVE-2020-6972 CWE-294 9.3; firmware update package (login required) on securityandfire.honeywell.com; Honeywell Security Notification SN 2020-02-04 01; mitigations: update firmware, isolate from internet/firewall/DMZ, VPN, strong passwords; reported by Gjoko Krstikj; no known public exploits. — CISA CSAF
  • Honeywell product security table (read 2026-11-27): 'NWS Authentication Bypass and Path Traversal Vulnerabilities', ICSA-20-051-03, 'Notifier Web Server (NWS) Version 5.50 and prior', CVE-2020-6972 and CVE-2020-6974, Critical, 2020-02-20. — Honeywell
  • CVE record (CNA icscert, published 2020-04-07): Honeywell Notifier Web Server (NWS), Version 3.50 and earlier; no CNA CVSS. NVD Primary of CVE-2020-6972: 9.1. — CVE.org
  • CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2020-6974 not listed; checked 2026-11-27. — CISA KEV
  • EPSS 0.01898, percentile 0.80240, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-20-051-03: Honeywell NOTI-FIRE-NET Web Server (NWS-3) (CSAF)
  3. CISA ICSA-20-051-03 advisory page
  4. Honeywell product security advisories
  5. CVE.org record CVE-2020-6974
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which NWS versions are affected by CVE-2020-6974?

The CVE record, NVD and CISA ICSA-20-051-03 list the NOTI-FIRE-NET Web Server (NWS-3) at version 3.50 and earlier. Honeywell's own product security table lists 'Version 5.50 and prior' for the same advisory, so check with Honeywell if you run a later release.

How is CVE-2020-6974 fixed?

Honeywell released an NWS-3 firmware update package (login required) described in Security Notification SN 2020-02-04 01. CISA also advises isolating the web server from the internet, using a VPN for remote access and strong passwords.

Does CVE-2020-6974 affect the fire alarm panels themselves?

The CVE record and CISA's advisory name only the NOTI-FIRE-NET Web Server (NWS-3); no fire alarm panel firmware is listed as affected. CISA's risk summary is a bypass of the web server's authentication methods.

Is CVE-2020-6974 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.01898, the 80.24th percentile, in the 2026-11-26 dataset.