CVE-2020-10611 is a type confusion flaw in Triangle MicroWorks SCADA Data Gateway, a protocol gateway used in energy and water SCADA systems. On installations that use DNP3 Data Sets, an unauthenticated remote attacker can run arbitrary code. NVD and CISA score it 9.8. Version 4.0.123 fixes it.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
5.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-10611 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Triangle MicroWorks SCADA Data Gateway | cpe:2.3:a:trianglemicroworks:scada_data_gateway:*:*:*:*:*:*:*:* | 2.41.0213 through 4.0.122 (NVD, CISA ICSA-20-105-03; the CVE record also names 3.02.0697 through 4.0.122); only installations using DNP3 Data Sets; fixed in 4.0.123 |
What does this mean for affected devices?
The CVE record from CISA says that Triangle MicroWorks SCADA Data Gateway "3.02.0697 through 4.0.122, 2.41.0213 through 4.0.122 allows remote attackers to execute arbitrary code due to the lack of proper validation of user-supplied data, which can result in a type confusion condition", that authentication is not required, and that it is "only applicable to installations using DNP3 Data Sets." NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5), and CISA gives the same 9.8 vector in CVSS 3.0. NVD and CISA agree on CWE-843, access of a resource using an incompatible type (NVD, CVE record).
The Zero Day Initiative published the flaw as ZDI-20-549 on 2020-04-16, with the same 9.8 score. ZDI says the flaw lies in the handling of data set elements and that an attacker can execute code in the context of SYSTEM. It was reported to the vendor on 2020-01-30 and credited to Tobias Scharnowski, Niklas Breitfeld and Ali Abbasi.
Which SCADA Data Gateway versions are affected?
CISA advisory ICSA-20-105-03, released on 2020-04-14, lists SCADA Data Gateway from 2.41.0213 through 4.0.122, used worldwide in the Energy and Water and Wastewater sectors, and NVD's CPE uses the same range. The advisory covers three flaws on installations with DNP3 Outstation channels; the siblings are a stack-based buffer overflow (CVE-2020-10615) and an out-of-bounds read (CVE-2020-10613), both 7.5 on NVD. Besides the ZDI researchers, CISA credits Steven Seeley and Chris Anastasio of Incite Team.
How do you fix CVE-2020-10611?
Triangle MicroWorks recommends updating SCADA Data Gateway to version 4.0.123 and asks users to contact its support for details. Installations that do not use DNP3 Data Sets are outside the scope of this CVE, according to the CVE record. As defence in depth, keep the gateway's DNP3 interfaces reachable only from the control network and not from the internet. Triangle MicroWorks' DNP3 Outstation libraries had their own overflow in the same months, see CVE-2020-6996, and a later denial of service is CVE-2022-38138. Our DNP3 protocol security guide covers the protocol side, and the memory corruption fix guide covers type confusion and overflows in parsers.
Is CVE-2020-10611 exploited?
CVE-2020-10611 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.05226, the 93.29th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting these vulnerabilities.


Evidence
- NVD (read 2026-11-27): status Modified; published 2020-04-15; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5; CWE-843 (NVD and ICS-CERT); CPE trianglemicroworks scada_data_gateway from 2.41.0213 up to and including 4.0.122. — NVD
- CISA ICSA-20-105-03 (CSAF, 2020-04-14): SCADA Data Gateway >= 2.41.0213, <= 4.0.122; CVE-2020-10611 CWE-843 CVSS 3.0 9.8; siblings CVE-2020-10615 (CWE-121) and CVE-2020-10613 (CWE-125); DNP3 Outstation channels; sectors Energy, Water and Wastewater; fix: update to 4.0.123, contact support; credits Incite Team and ZDI researchers; no known public exploits. — CISA CSAF
- ZDI-20-549 (2020-04-16, ZDI-CAN-10301): CVSS 9.8; handling of data set elements, type confusion, code execution in the context of SYSTEM, no authentication; reported 2020-01-30; credit Tobias Scharnowski, Niklas Breitfeld, Ali Abbasi. — Zero Day Initiative
- CVE record (CNA icscert, published 2020-04-15): 3.02.0697 through 4.0.122, 2.41.0213 through 4.0.122; only DNP3 Data Sets; no CNA CVSS. NVD Primary of CVE-2020-10613 and CVE-2020-10615: 7.5 each. — CVE.org
- CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2020-10611 not listed; checked 2026-11-27. — CISA KEV
- EPSS 0.05226, percentile 0.93287, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which SCADA Data Gateway versions are affected by CVE-2020-10611?
Versions 2.41.0213 through 4.0.122, per CISA ICSA-20-105-03 and NVD, and only installations that use DNP3 Data Sets. The CVE record also names 3.02.0697 through 4.0.122.
Which version fixes CVE-2020-10611?
Triangle MicroWorks recommends updating to SCADA Data Gateway 4.0.123 and contacting its support for details, per CISA.
Does an attacker need credentials to exploit CVE-2020-10611?
No. The CVE record, CISA and ZDI all state that authentication is not required; ZDI says code runs in the context of SYSTEM.
Is CVE-2020-10611 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.05226, the 93.29th percentile, in the 2026-11-26 dataset.
Questions about this page?