CVE-2019-6528 is a cross-site scripting flaw in the web interface of PSI GridConnect Telecontrol Gateway 3G, XS-MU and VM, the Smart Telecontrol Unit TCG and the IEC104 Security Proxy, energy-sector telecontrol devices. A logged-in attacker can make the browser run injected script. NVD scores it 8.8, CISA 8.5. Fixes are in 5.1.20, 6.0.17 and Proxy 2.2.11.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
2.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-6528 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| PSI GridConnect Telecontrol Gateway 3G | cpe:2.3:o:psigridconnect:telecontrol_gateway_3g_firmware:*:*:*:*:*:*:*:* | 4.2.21, 5.0.27, 5.1.19, 6.0.16 and prior (CISA ICSA-19-059-01); fixed in 5.1.20 and 6.0.17; 4.2.x and 5.0.x unsupported. NVD ranges: before 5.1.20, and 5.1.21 up to but excluding 6.0.16 |
| PSI GridConnect Telecontrol Gateway XS-MU | cpe:2.3:o:psigridconnect:telecontrol_gateway_xs-mu_firmware:*:*:*:*:*:*:*:* | 4.2.21, 5.0.27, 5.1.19, 6.0.16 and prior (CISA ICSA-19-059-01); fixed in 5.1.20 and 6.0.17; 4.2.x and 5.0.x unsupported. NVD ranges: before 5.1.20, and 5.1.21 through 6.0.16 |
| PSI GridConnect Telecontrol Gateway VM | cpe:2.3:o:psigridconnect:telecontrol_gateway_vm_firmware:*:*:*:*:*:*:*:* | 4.2.21, 5.0.27, 5.1.19, 6.0.16 and prior (CISA ICSA-19-059-01); fixed in 5.1.20 and 6.0.17; 4.2.x and 5.0.x unsupported. NVD ranges: before 5.1.20, and 5.1.21 through 6.0.16 |
| PSI GridConnect Smart Telecontrol Unit TCG | cpe:2.3:o:psigridconnect:smart_telecontrol_unit_tcg_firmware:*:*:*:*:*:*:*:* | 5.0.27, 5.1.19, 6.0.16 and prior (CISA ICSA-19-059-01); fixed in 5.1.20 and 6.0.17; 5.0.x unsupported. NVD ranges: before 5.1.20, and 5.1.21 up to but excluding 6.0.16 |
| PSI GridConnect IEC104 Security Proxy | cpe:2.3:o:psigridconnect:iec104_security_proxy_firmware:*:*:*:*:*:*:*:* | 2.2.10 and prior (CISA ICSA-19-059-01, NVD); fixed in 2.2.11 |
What does this mean for affected devices?
The CVE record from CISA describes a cross-site scripting flaw in the PSI GridConnect GmbH (formerly PSI Nentec GmbH) Telecontrol Gateway and Smart Telecontrol Unit family and the IEC104 Security Proxy: "The web application browser interprets input as active HTML, JavaScript, or VBScript, which could allow an attacker to execute arbitrary code." NVD's Primary score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; CVSS 2.0 6.5). CISA scores it 8.5 (CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L/A:N) in its advisory: changed scope, high confidentiality but low integrity impact and no availability impact. The CVE record carries no CVSS score. NVD and CISA both map it to CWE-79, improper neutralization of input during web page generation (NVD, CVE record).
Which PSI GridConnect devices and versions are affected?
CISA's ICSA-19-059-01, released on 2019-02-28, lists:
- Telecontrol Gateway 3G, XS-MU and VM: versions 4.2.21, 5.0.27, 5.1.19, 6.0.16 and prior;
- Smart Telecontrol Unit TCG: versions 5.0.27, 5.1.19, 6.0.16 and prior;
- IEC104 Security Proxy: version 2.2.10 and prior.
The products are used in the Energy sector worldwide, and the vendor is headquartered in Germany. M. Can Kurnaz reported the flaw to NCCIC, which coordinated with BSI Germany. CISA's summary is that exploitation could let an attacker execute dynamic scripts in the context of the application. It is the only CVE in the advisory.
NVD's CPE ranges do not match the advisory exactly. For all four gateway firmware products NVD marks everything before 5.1.20 as vulnerable, then a second range starting at 5.1.21, so it also flags any later 5.1.x release, which the advisory does not list. That second range ends at 6.0.16 inclusive for XS-MU and VM but excludes 6.0.16 for the 3G and Smart Telecontrol Unit TCG, although the advisory names 6.0.16 as affected for both. The IEC104 Security Proxy range, up to and including 2.2.10, matches the advisory. Use the advisory's lists, not the CPE ranges, to decide whether a unit needs the update.
How do you fix CVE-2019-6528?
PSI GridConnect recommends updating to a release with the fix: 5.1.20 or 6.0.17 for the gateways and telecontrol unit, and 2.2.11 for the IEC104 Security Proxy. Updates are obtained from PSI GridConnect support by email; there is no public download. Releases 4.2.x and 5.0.x are no longer supported, so units on those branches need a move to a supported branch. PSI also recommends deactivating the web server through the command line interface, since the web interface is not essential for configuring the device. In addition:
- reach the device's management interfaces only from a dedicated engineering network, never from the internet;
- give web accounts only to staff who need them, since the attack needs a logged-in user.
The input handling fix guide covers output encoding in device web interfaces, and the IEC 60870-5-104 security guide covers the telecontrol protocol these gateways carry. A comparable flaw in another IEC 104 telecontrol device is CVE-2023-5767 (Hitachi Energy RTU500 web server XSS); see also CVE-2021-35533 (RTU500 IEC 104 reboot).
Is CVE-2019-6528 exploited?
CVE-2019-6528 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.02579, the 85.95th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting this vulnerability at publication.


Evidence
- NVD (read 2026-11-27): status Modified; published 2019-03-05; [email protected] Primary CVSS 3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 6.5; CWE-79 (NVD Primary and ICS-CERT); CPEs: telecontrol_gateway_3g/xs-mu/vm and smart_telecontrol_unit_tcg firmware before 5.1.20 plus from 5.1.21 to 6.0.16 (inclusive for XS-MU and VM, exclusive for 3G and TCG); iec104_security_proxy_firmware up to and including 2.2.10. — NVD
- CISA ICSA-19-059-01 (initial release 2019-02-28, single revision): Telecontrol Gateway 3G/XS-MU/VM <= 4.2.21, 5.0.27, 5.1.19, 6.0.16; Smart Telecontrol Unit TCG <= 5.0.27, 5.1.19, 6.0.16; IEC104 Security Proxy <= 2.2.10; CWE-79 CVSS 3.0 8.5 AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L/A:N; fixes 5.1.20, 6.0.17, Proxy 2.2.11 via [email protected]; 4.2.x and 5.0.x no longer supported; recommends deactivating the webserver via CLI; reported by M. Can Kurnaz, NCCIC coordinated with BSI Germany; Energy; HQ Germany; no known public exploits. — CISA CSAF
- CVE.org record (CNA icscert): published 2019-03-05; affected versions as in the CISA advisory; CWE-79; no CVSS. — CVE.org
- CISA KEV catalog version 2026.11.25: CVE-2019-6528 not listed; checked 2026-11-27. — CISA KEV
- EPSS 0.02579, percentile 0.85946, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which PSI GridConnect products are affected by CVE-2019-6528?
Telecontrol Gateway 3G, XS-MU and VM versions 4.2.21, 5.0.27, 5.1.19, 6.0.16 and prior, Smart Telecontrol Unit TCG versions 5.0.27, 5.1.19, 6.0.16 and prior, and IEC104 Security Proxy 2.2.10 and prior (per CISA ICSA-19-059-01 and the CVE record).
How do I fix CVE-2019-6528?
Update to 5.1.20 or 6.0.17, or to 2.2.11 for the IEC104 Security Proxy, obtained from PSI GridConnect support; 4.2.x and 5.0.x are no longer supported. PSI also recommends deactivating the web server through the CLI, since it is not needed to configure the device (per CISA ICSA-19-059-01).
Do NVD's CPE ranges match the CISA advisory?
Not exactly. NVD excludes 6.0.16 itself for the Telecontrol Gateway 3G and Smart Telecontrol Unit TCG, although the advisory lists it as affected, and its range from 5.1.21 also flags later 5.1.x releases that the advisory does not list (per NVD and CISA ICSA-19-059-01).
Is CVE-2019-6528 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS rates it 0.02579, the 85.95th percentile, in the 2026-11-26 dataset, and CISA reported no known public exploits at publication (per CISA KEV, FIRST EPSS and ICSA-19-059-01).
Questions about this page?