Security Advisory

CVE-2019-18250: ABB PGIM and Plant Connect Auth Bypass

Last updated:
  • CVE-2019-18250

CVE-2019-18250 is an authentication bypass in ABB's PGIM and Plant Connect plant historians, used in power generation: an attacker with network access can bypass login and pull out the stored user credentials. NVD and ABB score it 9.8. ABB issued no patch; the fix is to migrate to Symphony Plus Historian 3.1 or later.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-18250 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
ABB Power Generation Information Manager (PGIM)cpe:2.3:a:abb:power_generation_information_manager:*:*:*:*:*:*:*:*All versions (ABB 8VZZ002158, CISA ICSA-19-318-05, NVD); no patch, migrate to Symphony Plus Historian 3.1 or later
ABB Plant Connectcpe:2.3:a:abb:plant_connect:*:*:*:*:*:*:*:*All versions; product obsolete, migrate to Symphony Plus Historian (ABB 8VZZ002158)

What does this mean for affected devices?

CVE-2019-18250 affects ABB's Power Generation Information Manager (PGIM) and Plant Connect. The CVE record, published by CISA, says that in all versions "the affected product is vulnerable to authentication bypass, which may allow an attacker to remotely bypass authentication and extract credentials from the affected device" (NVD, CVE record). NVD's Primary score is 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CWE-287 (improper authentication); CISA's CWE is CWE-288, authentication bypass using an alternate path or channel. ABB and CISA give the same 9.8 base score (CVSS 3.0); ABB adds a temporal score of 9.0.

What are PGIM and Plant Connect, and who is affected?

ABB's cyber security advisory 8VZZ002158, revision A dated 2019-11-01, describes PGIM as a plant historian and data analysis tool that produces reports and trends from collected process values. The weakness is in how the application manages its own user accounts: ABB says these applications "were not designed to withstand the techniques that attackers can utilize on exposed networks and endpoints", and that if network traffic is not encrypted, PGIM logins can be intercepted. Where operators reuse their Windows username and password in PGIM, stolen credentials also open Windows resources. ABB adds that if the control system is configured to accept writes from the historian, an attacker could use PGIM to send unauthorised data to the plant control system. CISA's ICSA-19-318-05, released on 2019-11-14, lists the Chemical, Critical Manufacturing, Dams, Energy, Food and Agriculture, and Water sectors, deployed worldwide; Rikard Bodforss of Bodforss Consulting reported it to ABB.

How do you fix CVE-2019-18250?

There is no patch for either product. ABB says Plant Connect is already obsolete and PGIM moved to a limited support phase in January 2020; the fix is to upgrade to Symphony Plus Historian 3.1 or later on a supported Windows version, which ABB says is not affected because its server uses Windows authentication and cannot be configured to use the PGIM protocol. Until then, ABB advises using different credentials for PGIM and for Windows login, protecting the network traffic with IPsec or similar, and keeping the historian behind a firewall with no direct internet connection. The ABB OT advisories guide groups other ABB issues, and the authentication bypass fix guide covers the bug class. Other ABB pages include the Central Licensing System flaw CVE-2020-8479 and the Relion 670 relay issue CVE-2019-18253.

Is CVE-2019-18250 exploited?

CVE-2019-18250 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). ABB's advisory says the issue had been publicly presented and that exploit code had been made public, but ABB had no report of malicious exploitation when it was issued. FIRST EPSS gives it 0.01678, the 77.31th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified, published 2019-11-26; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5; CWE-287 (NVD), CWE-288 (ICS-CERT); CPEs abb power_generation_information_manager and plant_connect, all versions. — NVD
  • ABB 8VZZ002158 rev A (2019-11-01), ABBVU-IAPG-8VZZ002158: PGIM and Plant Connect all versions; CVSS v3 base 9.8, temporal 9.0; PGIM limited support January 2020, Plant Connect obsolete; upgrade to Symphony Plus Historian 3.1 or later; workarounds: separate PGIM/Windows credentials, IPsec; publicly presented, exploit code public, no known malicious exploitation; acknowledges Rikard Bodforss. — ABB
  • CISA ICSA-19-318-05 (2019-11-14): CWE-288, CVSS v3 9.8; sectors Chemical, Critical Manufacturing, Dams, Energy, Food and Agriculture, Water and Wastewater; worldwide. — CISA CSAF
  • CVE record (CNA ICS-CERT): published 2019-11-25; CWE-288; PGIM and Plant Connect all versions. — CVE.org
  • CISA KEV catalog 2026.11.25 (1,805 entries): not listed, checked 2026-11-27. — CISA KEV
  • EPSS 0.01678, percentile 0.77309, dataset 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. ABB cyber security advisory 8VZZ002158: Power Generation Information Manager
  3. CISA ICSA-19-318-05: ABB PGIM and Plant Connect (CSAF)
  4. CISA ICSA-19-318-05 advisory page
  5. CVE.org record CVE-2019-18250
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which ABB products are affected by CVE-2019-18250?

All versions of ABB Power Generation Information Manager (PGIM) and Plant Connect, per ABB advisory 8VZZ002158, CISA ICSA-19-318-05 and NVD.

Is there a patch for CVE-2019-18250?

No. Plant Connect is obsolete and PGIM entered limited support in January 2020. ABB's fix is to migrate to Symphony Plus Historian 3.1 or later, which it says is not affected.

What can owners do before migrating off PGIM?

ABB advises not reusing Windows login credentials in PGIM or Plant Connect, protecting the historian's network traffic with IPsec or similar, and keeping it behind a firewall with no direct internet access.

Is CVE-2019-18250 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). ABB noted that exploit code was public in 2019 but had no report of malicious use. FIRST EPSS rates it 0.01678, the 77.31th percentile, in the 2026-11-26 dataset.