CVE-2017-5166 is an information exposure flaw in the BINOM3 Universal Multifunctional Electric Power Quality Meter that can be used to gain privileged access to the device. NVD and CISA both score it 9.8 (critical). CISA lists every BINOM3 power meter as affected, and BINOM3 has not created mitigations, so the meters must be isolated on the network.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-5166 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| BINOM3 Universal Multifunctional Electric Power Quality Meter | cpe:2.3:o:binom3:universal_multifunctional_electric_power_quality_meter_firmware:-:*:*:*:*:*:*:* | all versions listed by CISA ("BINOM3 power meters"); no vendor mitigation (CISA ICSA-17-031-01A) |
What does this mean for affected devices?
What is CVE-2017-5166?
NVD describes it briefly: "An issue was discovered in BINOM3 Universal Multifunctional Electric Power Quality Meter. An INFORMATION EXPOSURE flaw can be used to gain privileged access to the device." NVD's Primary score is CVSS v3.0 9.8 (critical), vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with CVSS v2 5.0 and CWE-200, Exposure of Sensitive Information to an Unauthorized Actor (NVD). NVD's configuration names the meter firmware with no version, matching every build. The CVE record was published on 2017-02-13 by the CISA ICS CNA.
Which advisory covers the BINOM3 meter?
CISA released ICSA-17-031-01 on 2017-01-31 and Update A on 2017-02-07. The advisory describes the product as a "universal multifunctional electric power quality meter", names the Energy sector, lists Russia as the deployment area and credits researcher Karn Ganeshen. Its CISA CSAF record marks all BINOM3 power meters as affected and scores CVE-2017-5166 at 9.8 with the same vector as NVD, so there is no scoring split.
The meter's web interface carries four more CVEs in the same advisory:
- CVE-2017-5162, improper access control (CWE-284, 10.0): no authentication for a remote service that gives access to the application set-up
- CVE-2017-5167, hard-coded password (CWE-259, 8.6): users cannot change their own passwords
- CVE-2017-5164, cross-site scripting (CWE-79, 8.8)
- CVE-2017-5165, cross-site request forgery (CWE-352, 8.8)
At release, CISA knew of no public exploits that specifically targeted these flaws.
How do I protect BINOM3 meters?
There is no fix. CISA states: "BINOM3 has not created mitigations for these vulnerabilities." The remaining defence is network placement: keep the meters unreachable from the internet, put them on a separate metering or OT network behind a firewall that admits only the systems that poll them, and use a VPN for any remote access. Because the sibling flaws include an unchangeable password and an unauthenticated set-up service, treat any meter that has been reachable from an untrusted network as possibly reconfigured. For utility-grade controls, see our ISO/IEC 27019 energy utility controls guide; our hard-coded credentials fix guide covers the root-cause fix for device makers. A newer metering example on this site is the Iskra iHUB smart metering gateway (CVE-2025-13510).
Is CVE-2017-5166 exploited?
CVE-2017-5166 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.01692, the 78th percentile, in the 2026-11-26 dataset, as of 2026-11-27 (CISA KEV, FIRST EPSS).


Evidence
- BINOM3 Universal Multifunctional Electric Power Quality Meter: information exposure flaw can be used to gain privileged access; NVD Primary CVSS v3.0 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; v2 5.0; CWE-200; CPE firmware with no version; published 2017-02-13. — NVD
- ICSA-17-031-01 released 2017-01-31, Update A 2017-02-07; all BINOM3 power meters affected; CVE-2017-5166 9.8 same vector; siblings CVE-2017-5162 (CWE-284, 10.0), 5167 (CWE-259, 8.6), 5164 (CWE-79, 8.8), 5165 (CWE-352, 8.8); BINOM3 has not created mitigations; Energy sector; deployed in Russia; credited to Karn Ganeshen; no known public exploits. — CISA ICSA-17-031-01A (CSAF)
- Not in the KEV catalog, version 2026.11.25, checked 2026-11-27. — CISA KEV
- EPSS 0.01692, 78th percentile, 2026-11-26 dataset. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Is there a firmware fix for CVE-2017-5166?
No. CISA states that BINOM3 has not created mitigations for this or the other four vulnerabilities in the advisory, so the meters must be protected by network isolation (per CISA ICSA-17-031-01A).
Which BINOM3 meters are affected?
CISA lists BINOM3 power meters without a version limit, and NVD's CPE names the meter firmware with no version, so every build should be treated as affected (per CISA ICSA-17-031-01A and NVD).
What other flaws does the BINOM3 advisory list?
Improper access control (CVE-2017-5162, 10.0), a hard-coded password users cannot change (CVE-2017-5167, 8.6), cross-site scripting (CVE-2017-5164, 8.8) and cross-site request forgery (CVE-2017-5165, 8.8) (per CISA ICSA-17-031-01A).
Is CVE-2017-5166 in the CISA KEV catalog?
No. It is not listed in catalog version 2026.11.25, checked 2026-11-27, and FIRST EPSS gives it 0.01692, the 78th percentile, in the 2026-11-26 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?