Security Advisory

CVE-2018-11691: DeltaV Smart Switch Default Password

Last updated:
  • CVE-2018-11691

CVE-2018-11691 is a default password problem in Emerson DeltaV Smart Switches. The Smart Switch Command Center in DeltaV 11.3.x and 12.3.1 never changed the switches' management password on commissioning, so the default stayed in effect. NVD scores it 9.8 and CISA 6.1. Emerson's DSN19003 workstation patch fixes the tool, after which the switches must be re-commissioned or re-passworded.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

2.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-11691 · Source: NVD

Affected components

ComponentCPEVersion range
Emerson DeltaV DCS 11.3.x and 12.3.1 Smart Switch Command Center—11.3.x and 12.3.1 (CVE record; CISA lists 11.3.x and 12.3.x); fixed by workstation patch DSN19003 (KBA NK-1900-0808), then commission the switches or change the password; 13.3 and later not affected
Emerson DeltaV Smart Switch VE6046 firmwarecpe:2.3:o:emerson:ve6046_firmware:09.0.12:*:*:*:*:*:*:*09.0.12 (NVD CPE only; the patch goes on the DeltaV workstations, not the switch)

What does this mean for affected devices?

The CVE record, from MITRE: "Emerson DeltaV Smart Switch Command Center application, available in versions 11.3.x and 12.3.1, was unable to change the DeltaV Smart Switches' management password upon commissioning." It adds that DeltaV 13.3 and higher use the Network Device Command Center application, which is not affected, and that after patching, users must commission the switches or change the password with the tool. NVD's Primary score is CVSS v3.0 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 10.0, with CWE-798. NVD's CPE names only Smart Switch firmware VE6046 09.0.12, not the DeltaV workstations that need the patch. The record was published on 2019-05-14 (NVD, CVE record).

Why is CISA's score so much lower?

CISA's ICSA-19-190-01, "Emerson DeltaV Distributed Control System", released on 2019-07-09, scores 6.1 (CVSS:3.0/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H): adjacent network and high privileges, with no confidentiality impact. CISA says the flaw is not exploitable remotely and lets an attacker gain administrative access to the Smart Switches. NVD scored the default password as reachable from the network with no privileges. CISA lists DeltaV DCS 11.3.x and 12.3.x, and said no known public exploits targeted it. Benjamin Crosasso of Sanofi reported it to Emerson (CSAF).

What should DeltaV owners do?

Install the patch described in DSN19003 (KBA NK-1900-0808) from the Guardian Support Portal, which needs a login. Then commission each DeltaV Smart Switch again or change its password with the patched tool; the patch alone leaves the default password on switches already in service. Emerson also recommends the DeltaV Security Manual for deployment. Other DeltaV flaws from the same period are the maintenance-port bypass CVE-2018-19021 and the workstation overflow CVE-2018-14793. See the Emerson DeltaV, Ovation and ROC guide and the hard-coded credentials fix guide.

CVE-2018-11691 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.02297, the 83.7th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2019-05-14; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE-798; CPE emerson:ve6046_firmware 09.0.12 running on ve6046. — NVD
  • CISA ICSA-19-190-01 (2019-07-09), CSAF read 2026-11-23: DeltaV DCS 11.3.x and 12.3.x; Smart Switch Command Center does not change the management password on commissioning; CVSS v3.0 6.1 CVSS:3.0/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H; CWE-798; administrative access to DeltaV Smart Switches; not exploitable remotely; no known public exploits; patch per DSN19003 (KBA NK-1900-0808) on Guardian; reported by Benjamin Crosasso (Sanofi). — CISA ICSA-19-190-01
  • CVE record (checked 2026-11-23): state PUBLISHED, CNA MITRE, published 2019-05-14, product n/a; text names Smart Switch Command Center 11.3.x and 12.3.1, DSN19003 (KBA NK-1900-0808), Network Device Command Center in 13.3 and higher not affected, re-commission or change password after patching. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.02297, percentile 0.83713, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-19-190-01: Emerson DeltaV Distributed Control System
  3. CISA ICSA-19-190-01 CSAF (machine-readable advisory)
  4. CVE.org record CVE-2018-11691
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which DeltaV versions are affected by CVE-2018-11691?

The Smart Switch Command Center in DeltaV 11.3.x and 12.3.1 (CVE record); CISA lists DeltaV DCS 11.3.x and 12.3.x. DeltaV 13.3 and higher use the Network Device Command Center, which is not affected.

Is installing the patch enough?

No. After the DSN19003 patch, the CVE record says users must commission the DeltaV Smart Switches or change the password with the tool, otherwise switches already in service keep the default.

Why does NVD say 9.8 while CISA says 6.1?

NVD scored it as reachable over the network with no privileges. CISA scored adjacent network access with high privileges and no confidentiality impact, and states the flaw is not exploitable remotely.

Is CVE-2018-11691 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.02297 (83.7th percentile) in the 2026-11-22 dataset.