Security Advisory

CVE-2017-5145: Carlo Gavazzi VMU-C Web Server CSRF

Last updated:
  • CVE-2017-5145

CVE-2017-5145 is a cross-site request forgery flaw in the web server of the Carlo Gavazzi VMU-C EM and VMU-C PV units: a forged request can change and save the device's configuration without the operator's intent. NVD scores it 10.0 (critical). Carlo Gavazzi fixed it in VMU-C EM firmware A11_U05 and VMU-C PV firmware A17.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

1.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2017-5145 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Carlo Gavazzi VMU-C EMcpe:2.3:o:carlosgavazzi:vmu-c_em_firmware:-:*:*:*:*:*:*:*firmware before A11_U05; fixed in A11_U05 (CISA ICSA-17-012-03; the NVD CPE names no version)
Carlo Gavazzi VMU-C PVcpe:2.3:o:carlosgavazzi:vmu-c_pv_firmware:-:*:*:*:*:*:*:*firmware before A17; fixed in A17 (CISA ICSA-17-012-03; the NVD CPE names no version)

What does this mean for affected devices?

What is CVE-2017-5145?

NVD describes it as follows: "An issue was discovered in Carlo Gavazzi VMU-C EM prior to firmware Version A11_U05, and VMU-C PV prior to firmware Version A17. Successful exploitation of this CROSS-SITE REQUEST FORGERY (CSRF) vulnerability can allow execution of unauthorized actions on the device such as configuration parameter changes, and saving modified configuration." NVD's Primary score is CVSS v3.0 10.0 (critical), vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H, with a legacy CVSS v2 score of 7.5 and CWE-352, Cross-Site Request Forgery, as its weakness (NVD). The CVE record was published on 2017-02-13 by the CISA ICS CNA (then ICS-CERT).

The scope-changed vector is what lifts the score to 10.0: the forged request runs in the browser of a logged-in user but acts on the device, and a configuration change on a monitoring unit affects the data and equipment behind it.

Which VMU-C firmware is affected?

CISA released ICSA-17-012-03 in January 2017. Its CISA CSAF record lists two products:

  • VMU-C EM, firmware versions before A11_U05
  • VMU-C PV, firmware versions before A17

CISA assigns the same 10.0 score, vector and CWE-352 as NVD, so there is no scoring split. NVD's configuration names carlosgavazzi:vmu-c_em_firmware and vmu-c_pv_firmware without a version, so a CPE match alone flags every build; use the firmware string to decide. CISA credits Karn Ganeshen with the report and, at release, knew of no public exploits that specifically targeted these flaws.

The same advisory covers two sibling CVEs: CVE-2017-5144, improper access control (CWE-284, CVSS v3 9.8 in CISA's scoring), and CVE-2017-5146, an information exposure (CWE-200, 7.5). The same firmware releases fix all three.

How do I fix CVE-2017-5145?

CISA quotes the vendor: "Carlo Gavazzi recommends upgrading to the following firmware versions: VMU-C EM A11_U05 for VMUC EM, and VMU-C PV A17 for VMUC PV." The firmware can be installed through the update function built into the VMU-C or downloaded from Carlo Gavazzi's website, where CISA's instructions list both models under the "Web-Server" function. Until a unit is updated, keep its web interface off the internet, reach it only through a VPN, and do not browse other sites in the same browser session while logged in to it; CISA's recommended practices point to its defence-in-depth guidance for control systems.

How does this compare with other energy-monitoring devices?

Monitoring units for solar and energy installations keep showing the same web-interface weaknesses: the ABB VSN300 logger card information leak (CVE-2017-7920) and the SolarView Compact command injection (CVE-2022-29303) are two examples on this site. Our NIST SP 1800-32 guide to securing distributed energy resources covers how to put such devices behind authenticated, segmented communication paths. The root-cause fix for this class, checking a per-request token and the session on every state-changing route, is part of our authentication bypass fix guide.

Is CVE-2017-5145 exploited?

CVE-2017-5145 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.01247, the 69th percentile, in the 2026-11-26 dataset, as of 2026-11-27 (CISA KEV, FIRST EPSS). For how to weigh a critical score against a low exploitation signal, see KEV and EPSS vulnerability prioritization.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • CSRF in Carlo Gavazzi VMU-C EM before A11_U05 and VMU-C PV before A17 allows unauthorized configuration changes and saving; NVD Primary CVSS v3.0 10.0 AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H; Primary CVSS v2 7.5; CWE-352; CPEs vmu-c_em_firmware and vmu-c_pv_firmware with no version; published 2017-02-13. — NVD
  • ICSA-17-012-03: VMU-C EM < A11_U05 and VMU-C PV < A17; CVE-2017-5144 (CWE-284, 9.8), CVE-2017-5145 (CWE-352, 10.0, same vector as NVD), CVE-2017-5146 (CWE-200, 7.5); fix firmware A11_U05 / A17 via the built-in update function or the vendor website (Web-Server function); credited to Karn Ganeshen; no known public exploits. — CISA ICSA-17-012-03 (CSAF)
  • Not in the KEV catalog, version 2026.11.25, checked 2026-11-27. — CISA KEV
  • EPSS 0.01247, 69th percentile, 2026-11-26 dataset. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICS Advisory ICSA-17-012-03: Carlo Gavazzi VMU-C EM and VMU-C PV
  3. CISA CSAF record for ICSA-17-012-03
  4. CVE.org record
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2017-5145?

VMU-C EM firmware A11_U05 and VMU-C PV firmware A17. Both can be installed with the update function built into the VMU-C or downloaded from Carlo Gavazzi's website (per CISA ICSA-17-012-03).

What can an attacker do through CVE-2017-5145?

Make the unit carry out actions such as changing configuration parameters and saving the modified configuration, by getting a logged-in user's browser to send a forged request. NVD scores it 10.0 with a changed scope (per NVD).

Are there other flaws in the same VMU-C advisory?

Yes. CVE-2017-5144 is an improper access control flaw scored 9.8 by CISA and CVE-2017-5146 is an information exposure scored 7.5. The same firmware versions fix all three (per CISA ICSA-17-012-03).

Is CVE-2017-5145 in the CISA KEV catalog?

No. It is not listed in catalog version 2026.11.25, checked 2026-11-27, and FIRST EPSS gives it 0.01247, the 69th percentile, in the 2026-11-26 dataset (per CISA KEV and FIRST EPSS).