CVE-2017-16744 is a path traversal flaw in the Tridium Niagara AX and Niagara 4 frameworks on Windows, which also ships in Johnson Controls Facility Explorer. A user with valid platform administrator credentials can reach files outside the allowed directory. NVD scores it CVSS v3.0 7.2; CISA says 6.6. Johnson Controls fixed it in Facility Explorer 14.6, 14.4u1 and 6.6 and recommends 14.6.
Vulnerability summary
CVSS base score
7.2
High severity
EPSS score (FIRST)
6.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-16744 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Johnson Controls Facility Explorer 6.x (Niagara AX Framework) | cpe:2.3:a:tridium:niagara_ax_framework:*:*:*:*:*:*:*:* | 6.x before 6.6; fixed in Facility Explorer 6.6 (August 2018) or 14.6 (ICSA-19-022-01) |
| Johnson Controls Facility Explorer 14.x (Niagara 4 Framework) | cpe:2.3:a:tridium:niagara:*:*:*:*:*:*:*:* | 14.x before 14.4u1; fixed in 14.4u1 (August 2018) or 14.6 (September 2018, recommended) (ICSA-19-022-01) |
| Tridium Niagara AX Framework and Niagara 4 Framework on Microsoft Windows | cpe:2.3:a:tridium:niagara:*:*:*:*:*:*:*:* | Niagara AX 3.8 and earlier (fix: Update 4, 3.8.401); Niagara 4 4.0 to 4.4 (fix: Update 1, 4.4.92.2.1) (ICSA-18-191-03); NVD CPE niagara_ax_framework up to 3.8 and niagara 4.0 to 4.4 |
What does this mean for affected devices?
NVD describes "a path traversal vulnerability in Tridium Niagara AX Versions 3.8 and prior and Niagara 4 systems Versions 4.4 and prior installed on Microsoft Windows Systems" that "can be exploited by leveraging valid platform (administrator) credentials." NVD's Primary scores are CVSS v3.0 7.2 (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H) and CVSS v2 6.5, with CWE-22. ICS-CERT (CNA icscert) published the record on 2018-08-20 without a CNA score (NVD, CVE record).
Which Facility Explorer versions are affected?
CISA's ICSA-19-022-01 of 2019-01-22 applies the flaw to Johnson Controls Facility Explorer, which runs on the Niagara frameworks: Facility Explorer 6.x before 6.6 and 14.x before 14.4u1. The fixed releases are Facility Explorer 14.6 (September 2018), 14.4u1 (August 2018) and 6.6 (August 2018), and Johnson Controls recommends FX14.6. CISA scores CVSS v3 6.6 (AV:N/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:H), rates the skill needed as high, and says a successful attack could "read, write, and delete sensitive files to gain administrator privileges in the Facility Explorer system." No known public exploits specifically target it. Johnson Controls' security advisory table lists the matching advisory CPP-PSA-20180-02 v1 for Facility Explorer, covering CVE-2017-16744 and CVE-2017-16748, and points to ICSA-19-022-01.
For the Tridium products themselves, CISA's ICSA-18-191-03 gives the fixes: Niagara AX 3.8 Update 4 (3.8.401) and Niagara 4.4 Update 1 (4.4.92.2.1). NVD's CPE data covers Niagara AX up to 3.8 and Niagara 4.0 to 4.4; it has no Facility Explorer entry, so match FX installs by version.
What else matters for Niagara-based systems?
The attack needs valid platform administrator credentials. The Johnson Controls Metasys guide covers the Facility Explorer line, and the Niagara Fox protocol guide covers the framework. Related traversal flaws: CVE-2012-4027 in NiagaraAX and CVE-2020-9050 in the Metasys Reporting Engine.
CVE-2017-16744 is not in the CISA KEV catalog as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS gives it 0.06142, the 93.6th percentile, in the 2026-11-23 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-24): status Modified; published 2018-08-20; NVD Primary CVSS v3.0 7.2 AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H and v2 6.5; CWE-22; CPE tridium niagara 4.0-4.4 and niagara_ax_framework up to 3.8. — NVD
- CISA ICSA-19-022-01 CSAF (released 2019-01-22), read 2026-11-24: Facility Explorer 6.x before 6.6 and 14.x before 14.4u1; fixes FX 14.6 (Sept 2018), 14.4u1 and 6.6 (Aug 2018), FX14.6 recommended; CVSS v3 6.6; no known public exploits; high skill level. — CISA ICSA-19-022-01
- CISA ICSA-18-191-03 CSAF (Tridium Niagara, updated 2018-08-16), read 2026-11-24: Niagara AX 3.8 and prior, Niagara 4 4.4 and prior on Windows; fixes 3.8.401 (Update 4) and 4.4.92.2.1 (Update 1); CVSS v3 6.6. — CISA ICSA-18-191-03
- Johnson Controls security advisories table (read 2026-11-24): CPP-PSA-20180-02 v1 Facility Explorer path traversal and improper authentication, ICSA-19-022-01, CVE-2017-16744 and CVE-2017-16748. — Johnson Controls
- CVE record (checked 2026-11-24): PUBLISHED, CNA icscert, published 2018-08-20, no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.23, 1,792 entries, checked 2026-11-24. — CISA KEV
- EPSS 0.06142, percentile 0.9363, dataset 2026-11-23, read 2026-11-24. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Facility Explorer release fixes CVE-2017-16744?
Facility Explorer 14.6, 14.4u1 or 6.6. Johnson Controls recommends 14.6 (ICSA-19-022-01).
Does an attacker need credentials?
Yes. NVD and CISA both say the flaw is exploited by leveraging valid platform (administrator) credentials, which is why the CVSS privileges metric is high.
Why does NVD say 7.2 and CISA 6.6?
Both use the same impact values; CISA rates attack complexity high, NVD rates it low.
Is CVE-2017-16744 in the CISA KEV catalog?
No, not as of 2026-11-24 (catalog version 2026.11.23, 1,792 entries). FIRST EPSS rates it 0.06142 (93.6th percentile) in the 2026-11-23 dataset.
Questions about this page?